M
ULTI
-S
OURCE
S
YSTEM BASED ON
S
YSTEM
7001RC
14 / 31
Multi-Source Function System 7001RC - V02.01
hopf
Elektronik GmbH
Nottebohmstr. 41 • D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
8
-
R r
Primary
source
Internal
quartz base
"Sync. status change after sync. fail"
timer expired
Loss of synchronisation via small "r"
system status
System operates with internal
quartz base
9
-
R C
Secondary
source
Internal
quartz base
Change to secondary source
System operates with internal
quartz base
10
-
R r
Secondary
source
Secondary
source
System synchronises to secondary
source
Time leap possible -
in the event of a difference in the
sync. source times.
11
-
R R
Secondary
source
Secondary
source
After one minute system status
goes to synchronisation with control
of the internal quartz base
12
Secondary source
failure
- -
R
Secondary
source
Internal
quartz base
Detection of a fault in reception from
the secondary source
System status is maintained as
radio synchronous by means of
"sync. status change after sync. fail”
timer.
13
- -
r
Secondary
source
Internal
quartz base
"Sync. status change after sync. fail"
timer expired
Loss of synchronisation via small "r"
system status
System operates with internal
quartz base
14
- -
C
Primary
source
Internal
quartz base
No synchronisation, change to
primary source
System operates with internal
quartz base
15
Secondary source
refreshed with valid
information
-
R C
Secondary
source
Internal
quartz base
Secondary source is synchronised
(duration: approx. 3-5 min.)
System operates with internal
quartz base
16
-
R r
Secondary
source
Secondary
source
System synchronises to secondary
source
Time leap possible
(only on long operation with the
internal quartz base)
17
-
R R
Secondary
source
Secondary
source
After one minute system status
goes to synchronisation with control
of the internal quartz base
18
Primary source
refreshed with valid
time information
(secondary source
continues
synchronous)
R R C
Primary
source
Internal
quartz base
Primary source is synchronised
(duration: approx. 3-5 min.)
System status leaps to Quartz "C"
System operates with internal
quartz base
19
R R r
Primary
source
Primary
source
System synchronises to primary
source;
Time leap possible -
in the event of a difference in the
sync. source times.
20
R R R
Primary
source
Primary
source
After one minute system status
goes to synchronisation with control
of the internal quartz base