Y8610U INTERMITTENT PILOT RETROFIT KIT
68-0133—2
9
Fig. 11. Use moderate amount of pipe compound.
쐂
Connect the pipe to the gas control inlet and outlet.
Tighten the inlet and outlet connections using a wrench
on the gas control projecting wrench boss. See Fig. 3.
Connect Pilot Gas Tubing
쐃
Cut the pilot gas tubing and bend as necessary for
routing to the pilot burner.
•
Do not make sharp bends or deform the tubing.
•
Do not bend the tubing at the gas control after the
compression nut has been tightened; gas leakage at
the connection can result.
쐇
Square off and remove the burrs from the tubing end.
쐋
Unscrew the brass compression fitting from pilot gas
outlet (see Fig. 3). Slip the fitting over the pilot gas
tubing and slide out of the way.
NOTE:
When replacing a gas control, cut off the old
compression fitting and replace with the new
compression fitting provided on the new gas
control. Never use the old compression fitting
as it might not provide a gas tight seal. See
Fig. 12.
쐏
Push pilot gas tubing into the pilot gas tapping until it
bottoms. While holding the tubing all the way in, slide
the compression fitting into place and engage threads.
Turn the fitting until finger tight. Use a wrench to tighten
one more turn. Do not overtighten.
쐄
Connect other end of the pilot gas tubing to the pilot
burner according to pilot burner manufacturer
instructions.
TWO IMPERFECT
THREADS
GAS CONTROL
THREAD PIPE CORRECT LENGTH
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
M3312
PIPE
Fig. 12. Always use new compression fitting.
Mounting S8610U Intermittent Pilot Module
Select a location close to the pilot burner to allow the ignition
cable to run to the igniter-sensor. The ambient temperature
and other conditions should match those listed in the
Specifications.
We recommend mounting the module with the terminals down
so the terminals are protected from dripping water and dust. It
can also be mounted with the terminals on either side. Do not
mount the module with the terminals pointing up. See Fig. 13
for mounting recommendations. Fasten the module securely
with four No. 6-32 machine screws or No. 8 sheetmetal
screws of appropriate length.
GAS CONTROL
TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT
FITTING BREAKS OFF AND CLINCHES
TUBING AS NUT IS TIGHTENED
PILOT
TUBING
M6868
Fig. 13. S8610 mounting recommendations.
Wiring the System
CAUTION
Disconnect the power supply before making wiring
connections to prevent electrical shock or equipment
damage.
Connect the Ignition Cable
쐃
Connect one end of the ignition cable to the male quick-
connect SPARK terminal on the S8610 Module.
쐇
Connect the other ignition cable end to the 392431
Igniter-Sensor.
Connect the Vent Damper
The D80D Vent Damper can be used with all ignition modules,
although the Molex plug provided on some modules simplifies
wiring connections when used with the D80D Plug-in Vent
Damper. Once a module with a vent damper plug has powered
a vent damper circuit, it cannot be used in a gas system without
a vent damper. A non-replaceable fuse in the module blows on
TERMINALS FACING DOWN
TERMINALS FACING LEFT
TERMINALS FACING RIGHT
MOUNT IN ONE OF THESE POSITIONS
DO NOT MOUNT
WITH TERMINALS FACING UP
M2647