Y8610U INTERMITTENT PILOT RETROFIT KIT
68-0133—2
11
Fig. 15. Y8610 in typical atmospheric burner heating system with D80D Vent Damper.
1
2
3
4
5
5
4
M3274
PILOT
BURNER
GROUND
MV MV/PV
PV
GND
(BURNER)
24V
GND
24V
TH-W
SPARK
SENSE
VENT
DAMPER
PLUG
S8610U
L1
(HOT)
L2
1
2
3
LIMIT
CONTROLLER
THERMOSTAT
PV
PV/MV
MV
VR8304M
COMBINATION
GAS CONTROL
IGNITER
SENSOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ALTERNATE LIMIT CONTROLLER LOCATION.
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS REMOVED AND VENT
DAMPER WIRING HARNESS IS INSTALLED; THEN MODULE OPERATES ONLY WHEN VENT DAMPER IS CONNECTED.
JUMPER WIRE FROM CIRCUIT BOARD TO SENSE CONNECTOR REMAINS IN PLACE.
WIRING
HARNESS
D80D VENT
DAMPER
Fig. 16. Y8610 in typical atmospheric burner heating system with D80B Vent Damper.
1
2
3
4
5
6
6
5
4
4
M3310
PILOT
BURNER
GROUND
MV MV/PV
PV
GND
(BURNER)
24V
GND
24V
TH-W
SPARK
SENSE
VENT
DAMPER
PLUG
S8610U
L1
(HOT)
L2
1
2
3
MOTOR
RED
BLUE
BLACK
ORANGE
YELLOW
PV
PV/MV
MV
VR8304M
COMBINATION
GAS CONTROL
IGNITER
SENSOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ALTERNATE LIMIT CONTROLLER LOCATION.
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
CONNECT VENT DAMPER TERMINAL 1 TO TH-W. LEAVE 24V OPEN. DO NOT REMOVE VENT DAMPER PLUG.
COLORS REFER TO WIRE HARNESS, IF USED.
JUMPER WIRE FROM CIRCUIT BOARD TO SENSE CONNECTOR REMAINS IN PLACE.
TRANSFORMER
LIMIT
CONTROLLER
THERMOSTAT
OR
CONTROLLER
LIMIT
CONTROLLER
1
2
3
4
5
N. O.
END SWITCH
N. C.
1K1
1K2
1K3
1K
D80B
R