Y8610U INTERMITTENT PILOT RETROFIT KIT

68-0133—2

7

Install Igniter-Sensor Assembly

Install the ground rod, if needed. See Fig. 7.

Mount adapter to the ground rod, if needed.

Align the ground rod so the clip hugs the pilot burner
and keeps the ground rod from rotating. See Fig. 8.

Insert the ground rod in place of the thermocouple
on the pilot burner. Push the ground rod all the way
up and fasten as shown in Fig. 7.

Slide the igniter-sensor mounting bracket over the top
of the ground rod.

Adjust the electrode position so the electrode tip and
spark gas are in the pilot flame. Turn the ground rod to
move the igniter-sensor up and down.

Check that the chosen position allows room to connect
the ignition cable to the stud terminal.

Tighten the setscrews on the mounting bracket using
the hex wrench provided.

Fig. 7. Mount ground rod on pilot burner.

ADD ADAPTER,

INSERT GROUND

ROD IN PILOT

SLIP NUT OFF ADAPTER 
AND CLAMP GROUND ROD 
IN PILOT  WITH SHOULDER 
ABOVE CLAMP AS SHOWN

SCREW-IN TYPE

CLAMP TYPE

PUSH-IN TYPE

TIGHTEN NUT

BE SURE THE GROUND CLIP IS SNAPPED ONTO THE PILOT BURNER OR ITS GAS LINE.

INSERT 
GROUND ROD

M6865

Fig. 8. Fasten igniter-sensor to ground rod.

Install the Gas Control

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Follow these warnings exactly:

1. Do not bend the pilot gas tubing at the gas

control or at the pilot burner after the
compression fitting is tightened. Gas leakage at
the connection can result.

2. Always install a sediment trap in the gas supply

line to prevent contamination of the gas control.

3. Do not force the gas control knob. Use only your

hand to turn the gas control knob. If the gas
control knob does not operate by hand, the gas
control should be replaced by a qualified service
technician. Force or attempted repair can result in
a fire or explosion.

IMPORTANT

These gas controls are shipped with protective seals
over the inlet and outlet tappings. Do not remove the
seals until ready to connect the piping.

Converting Between Natural and LP Gas

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.

1. Do not attempt to use a gas control set for natural

gas on LP gas or a gas control set for LP gas on
natural gas.

2. When making a conversion, main and pilot burner

orifices must be changed to meet appliance
manufacturer specifications.

To convert from natural gas to LP, use the 393691 LP
Conversion Kit that is included with the Y8610U Intermittent
Pilot Retrofit Kit. To convert from LP to natural gas, use the
394588 Natural Gas Conversion Kit (ordered separately).
Step-opening gas controls cannot be converted.

To convert control from one gas to another:

Turn off the main gas supply to the appliance.

Remove the regulator cap screw and pressure
regulator adjusting screw. See Fig. 3.

Remove the existing spring.

Insert the replacement spring with the tapered end
down. See Fig. 9.

Install the new plastic pressure regulator adjustment
screw so that the top of the screw is flush (level) with
the top of the regulator. Turn the pressure regulator
adjustment screw clockwise six complete turns. This
provides a preliminary pressure setting of about 10.0 in.
wc (2.5 kPa) for LP regulator and 3.5 in. wc (0.9 kPa)
for natural gas regulator.

Check the regulator setting either with a manometer or
by clocking the gas meter. See the Checkout section.

Install the new cap screw.

Mount the conversion label on the control.

Install the control and appliance according to the
appliance manufacturer instructions.

M6863

GROUND ROD

GROUND 
ROD CLIP

ELECTRODE 
SETSCREW (2)

ELECTRODE 
GAP

IGNITER-SENSOR

STUD TERMINAL

MOUNTING 
BRACKET

PILOT
BURNER

PILOT GAS 
TUBING

ELECTRODE 

Содержание Y8610U

Страница 1: ...mbination Gas Control 392431 Igniter Sensor 394800 30 Ignition Cable 393691 Natural to LP Gas Conversion Kit Wiring Harness 393690 14 Straight Flange Kit 3 4 in Reducer adapters for gas control Adhesive mounting option for S8610 Installation hardware Temperature Rating VR8304M 40 F to 175 F 40 C to 79 C S8610U 40 F to 165 F 40 C to 74 C If main valve current is 1A or less 175 F 79 C maximum ambien...

Страница 2: ...Module VR8304M Dual Valve Combination Gas Control Refer to Fig 1 for other components Ambient Temperature Rating VR8304M 40 F to 175 F 40 C to 79 C S8610U 40 F to 165 F 40 C to 74 C If main valve current is 1A or less 175 F 79 C maximum ambient applies Also refer to Igniter Sensor specifications Electrical Ratings Voltage and Frequency 20 5 to 28 5 Vac 24 Vac nominal 60 Hz Current Rating 0 7A incl...

Страница 3: ... IGNITION CABLE 30 IN 760 mm 393690 14 STRAIGHT FLANGE KIT 393691 NATURAL GAS TO LP CONVERSION KIT REDUCER BUSHINGS FOR GAS CONTROL SCREWS WIRE NUTS 3 M6866 GROUND ROD IGNITER SENSOR ADAPTER Fig 1 Y8610 retrofit kit components Fig 2 S8610U module dimensions 2 51 M1123A 3 3 16 81 2 5 8 67 1 4 6 3 15 16 100 3 3 8 86 1 1 32 26 5 7 16 138 3 3 8 86 2 3 16 5 2 3 16 5 2 ...

Страница 4: ...rminals 1 4 in male quick connect terminals Igniter Sensor Specifications Model 392431 Igniter Sensor Includes igniter sensor assembly ground rod and adapter refer to Fig 1 Dimensions Refer to Fig 4 Electrode Flame Rod Material Kanthal Maximum Temperature Ratings Ground Rod Tip 1775 F 968 C Ceramic Insulator 1250 F 677 C Mounting Replaces the thermocouple on the existing pilot burner Fig 3 VR8304M...

Страница 5: ...trols Where chemicals could be suspended in air as in some industrial and agricultural applications protect the ignition module from exposure with a NEMA 4 enclosure see the Electronic Ignition Service Manual form 70 6604 Dust or Grease Accumulation Heavy accumulation of dust or grease can cause the controls to malfunction Where dust or grease can cause a problem provide covers for the module and ...

Страница 6: ...n is high the system should be checked more often Dusty wet or corrosive environment Because these environments can cause the controls to deteriorate more rapidly the system should be checked more often Any control should be replaced if it does not perform properly during Checkout or Troubleshooting In addition replace any module if it is wet or looks like it has been wet Protective enclosures see...

Страница 7: ...ced by a qualified service technician Force or attempted repair can result in a fire or explosion IMPORTANT These gas controls are shipped with protective seals over the inlet and outlet tappings Do not remove the seals until ready to connect the piping Converting Between Natural and LP Gas WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH 1 Do not attempt to use a ...

Страница 8: ...nds are square deburred and clean All tubing bends must be smooth and without deformation 쐇 Run the new pipe or tubing to the gas control When tubing is used obtain a tube to pipe coupling to connect the tubing to the gas control 쐋 Install a sediment trap in the gas supply line See Fig 10 Fig 10 Install sediment trap Mount Gas Control 쐃 The gas control can be mounted from 0 to 90 degrees in any di...

Страница 9: ...M3312 PIPE Fig 12 Always use new compression fitting Mounting S8610U Intermittent Pilot Module Select a location close to the pilot burner to allow the ignition cable to run to the igniter sensor The ambient temperature and other conditions should match those listed in the Specifications We recommend mounting the module with the terminals down so the terminals are protected from dripping water and...

Страница 10: ...V PV MV MV VR8304M COMBINATION GAS CONTROL IGNITER SENSOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER JUMPER WIRE FROM CIRCUIT BOARD TO SENSE CONNECTOR REMAINS IN PLACE 쐇 Adjust the thermostat heat anticipator to match the system current draw The current draw equals th...

Страница 11: ...ECTED JUMPER WIRE FROM CIRCUIT BOARD TO SENSE CONNECTOR REMAINS IN PLACE WIRING HARNESS D80D VENT DAMPER Fig 16 Y8610 in typical atmospheric burner heating system with D80B Vent Damper 1 2 3 4 5 6 6 5 4 4 M3310 PILOT BURNER GROUND MV MV PV PV GND BURNER 24V GND 24V TH W SPARK SENSE VENT DAMPER PLUG S8610U L1 HOT L2 1 2 3 MOTOR RED BLUE BLACK ORANGE YELLOW PV PV MV MV VR8304M COMBINATION GAS CONTRO...

Страница 12: ...temperature to call for heat Watch for spark at pilot burner Time spark from start to shutoff See Specifications section Open the gas control knob and ensure no gas is flowing to the pilot or main burner Set the thermostat below the room temperature and wait one minute before continuing STEP 5 Check and Adjust Gas Input to Main Burner CAUTION 1 Do not exceed the input rating stamped on the applian...

Страница 13: ...urner lights smoothly without flashback Make sure the main burner operates smoothly without floating lifting or flame rollout to the furnace vestibule or heat buildup in the vestibule If the gas line has been disturbed complete the Gas Leak Test following Step 1 Turn the thermostat or controller below the room temperature Make sure the main burner and pilot flames go out OPERATION System operation...

Страница 14: ...trained experienced service technicians should service intermittent pilot systems Perform the Checkout see Checkout section as the first step in troubleshooting Then check the appropriate troubleshooting guide Fig 19 and the schematic diagram Fig 22 to pinpoint the cause of the problem When troubleshooting indicates an ignition problem see the Ignition System Checks section to isolate and correct ...

Страница 15: ...t should light but the main burner remains off because the main valve actuator is disconnected Check the pilot flame Make sure it is blue steady and envelops 3 8 to 1 2 in 10 to 13 mm of the flame rod See Fig 20 for possible flame problems and their causes If necessary adjust the pilot flame by turning the pilot adjustment screw on the gas control clockwise to decrease or counterclockwise to incre...

Страница 16: ...eld cable and boot from excessive temperatures YES YES Check that all manual gas valves are open supply tubing and pressures are good and pilot burner orifice is not blocked Check electrical connections between module and pilot operator on gas control Check for 24 Vac across PV MV PV terminals on module If voltage is okay replace gas control if not replace module NO TURN ON GAS SUPPLY YES PILOT BU...

Страница 17: ...e entrance 쐇 Disconnect the control module green ground wire 쐋 Connect the microammeter negative lead to the control module GND BURNER terminal and the positive lead to the green ground wire see Fig 21 쐏 Disconnect the red wire from the gas control TH or MV terminal to disable the gas control 쐄 Loosen the set screws holding the igniter sensor on the ground rod 쐂 Restore power and set thermostat to...

Страница 18: ...ITS LOW VOLTAGE POWER SUPPLY 1K 2K 3K HYBRID CIRCUIT 1K1 1K2 3K2 2K2 3K1 ARC GAP SPARK GND BUR NER MV PV MV PV IGNITER SENSOR BURNER GROUND 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION 3 0 AMP NONREPLACEABLE FUSE FUSE BLOWS WHEN VENT DAMPER IS PLUGGED IN INTERNAL WIRING EXTERNAL WIRING M3311 TH W YELLOW FUSE MAIN VALVE VALVE PILO...

Страница 19: ...uilding doors and windows and all doors between the space in which the appliance is located and other spaces of the building Turn on clothes dryers Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers If after completing steps 7 through 12 it is believed sufficient combustion air is not ...

Страница 20: ... by the transformer b Multiply the total current draw as computed above by 24 V to determine the total VA volt ampere required c The total VA volt ampere required should be equal to or less than the VA rating of the transformer d If the total VA volt ampere required is greater than the VA rating of the transformer the transformer must be replaced with a Class 2 transformer of adequate rating 6 Che...

Отзывы: