XLS-REL Technical Reference Manual

1.1

Chapter 1

Installing the XLS-REL

Summary

The XLS-REL supports a variety of fire suppression applications. 

These applications include sprinkler systems and automatic fire 

extinguishing systems. When you install the XLS-REL, follow 

agency and local requirements along with the instructions in this 

manual.

Content

Introducing the XLS-REL • 1.2

Description • 1.2
Features • 1.2

Fire suppression systems • 1.3

Sprinkler systems • 1.3
Automatic fire extinguishing systems • 1.4

Compatible panels and devices • 1.5

Panels • 1.5
Power supplies • 1.5
Solenoid polarizing relays • 1.5
Abort stations • 1.5
Service disconnect stations • 1.5
Releasing solenoid valves • 1.6
Listing agencies • 1.6

Specifications • 1.7
Mounting the XLS-REL • 1.9
Setting abort mode and delay times • 1.11

Choosing the abort mode • 1.11
Setting the DIP switches • 1.11

Reading LEDs • 1.13
Wiring the XLS-REL • 1.14

Observing equipment and personal safety • 1.14
Running the wires • 1.14

Содержание XLS-REL

Страница 1: ... U S Registered Trademark Copyright 2001 Honeywell All Rights Reserved 74 3338 XLS REL Technical Reference Manual P N 3100321 Rev 2 0 01SEP01 ...

Страница 2: ...in this manual to unauthorized persons you have violated all distributor agreements and may be subject to legal action DOCUMENT HISTORY Date Revision Reason for change 14FEB01 1 0 Initial release 01SEP01 2 0 Added testing information FMRC agency information drawing for preaction deluge sprinkler systems compatibility information for releasing solenoid valves programming statements Deleted Halon as...

Страница 3: ... Reading LEDs 1 13 Wiring the XLS REL 1 14 Chapter 2 Programming the XLS REL 2 1 Programming the XLS REL in the XLS100 SDU 2 2 Programming the XLS REL in the XLS1000 SDU Revision 1 5 2 6 Programming the XLS REL in the XLS1000 SDU Revision 2 0 2 10 System testing 2 14 Chapter 3 Operational description 3 1 Integrating the Releasing Module with fire alarm systems 3 2 Developing a fire suppression pla...

Страница 4: ...ght to make product improvements and change product specifications at any time While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents Honeywell assumes no responsibility for errors or omissions FCC warning This equipment can generate and radiate radio frequency energy If this equipment is not installed in accordance with this manual it ma...

Страница 5: ...tallation Sheets P N 74 3441 XLS1000 International Supplement Manual P N 74 3117 XLS1000 SDU Help Signature Series documentation The Signature Series Intelligent Smoke and Heat Detectors Applications Bulletin P N 74 3065 provides instructions and illustrations for various arrays of smoke and heat detectors The Signature Series Component Installation Manual P N 74 3066 supports the installation of ...

Страница 6: ...e Protection Agency National Fire Protection Agency NFPA 1 Batterymarch Park PO Box 9101 Quincy MA 02269 9101 NFPA 11 Low Expansion Foam NFPA 11A Medium and High Expansion Foam Systems NFPA 13 Sprinkler Systems NFPA 15 Water Spray Fixed Systems for Fire Protection NFPA 16 Deluge Foam Water Sprinkler and Foam Water Spray systems NFPA 17 Dry Chemical Extinguishing Systems NFPA 70 National Electric C...

Страница 7: ...n 1151 Boston Providence Turnpike PO Box 9102 Norwood MA 02062 1011 1012 Deluge and Preaction Systems European standards 73 23 EEC Low Voltage Directive 89 336 EEC as amended by 9 31 EEC Electromagnetic Compatibility Directive EN50130 4 1995 Immunity requirements for Components of Fire Intruder and Social Alarm Systems EN55022 1995 Limits and Methods of Measurement of Radio Disturbance Characteris...

Страница 8: ...ce Disabled points will not prevent activation of the release circuits Failure to follow these instructions may result in loss of life serious injury or property damage Cautions Cautions alert you to practices that may damage equipment software or project databases For example the manual provides a caution against corrupting the database Caution Do not use the Accept Actual function in the Signatu...

Страница 9: ... 2 Description 1 2 Features 1 2 Fire suppression systems 1 3 Sprinkler systems 1 3 Automatic fire extinguishing systems 1 4 Compatible panels and devices 1 5 Panels 1 5 Power supplies 1 5 Solenoid polarizing relays 1 5 Abort stations 1 5 Service disconnect stations 1 5 Releasing solenoid valves 1 6 Listing agencies 1 6 Specifications 1 7 Mounting the XLS REL 1 9 Setting abort mode and delay times ...

Страница 10: ... abort circuit for a normally open abort switch One first alarm output relay Form C contact The XLS REL controls operations for deluge preaction and automatic fire extinguishing systems The module controls the release of gas and other fire suppression agents through release solenoids Figure 1 1 XLS REL Releasing Module Features The XLS REL includes Deluge sprinkler operation Preaction sprinkler op...

Страница 11: ...inklers are useful for applications that require the simultaneous discharge of water through every sprinkler The following fire detection systems meet FRMC requirements for deluge systems Wet pilot sprinkler line Dry pilot sprinkler line Hydraulic rate of rise Pneumatic rate of rise Electric Preaction sprinkler systems In preaction sprinkler systems closed valve sprinkler heads terminate pipes con...

Страница 12: ... Table 1 2 provides a list of the fire suppression agents and the applicable NFPA documents Warning The XLS REL is not listed for use with CO2 or Halon suppression systems Table 1 3 outlines the FMRC requirements for automatic fire extinguishing systems Table 1 2 Fire suppression agents and NFPA documentation Agent NFPA documentation Low expansion foam NFPA 11 Medium and high expansion foam NFPA 1...

Страница 13: ...PS 220 2 PPS 6A 220 SIGA APS 220 3 BPS M 220 3 PPS M 220 XLS BPS6 220 XLS BPS10 220 Not compatible with FMRC sprinkler applications that require 90 hours of standby Solenoid polarizing relays Use the RELA EOL with the XLS REL For more information see the RELA EOL installation sheet Abort stations The XLS REL is only compatible with normally open momentary action abort stations Abort stations must ...

Страница 14: ...ase valves that work with the Releasing Module For other listing agencies that may apply to your area see Listing agencies Listing agencies Listing agencies include Factory Mutual Research Corporation FMRC Underwriters Laboratories Inc UL Underwriters Laboratories Canada ULC Table 1 4 FM approved solenoid release valves Group Company Model A Skinner LV2LBX25 D ASCO 8210G207 E Skinner 73218BN4UNLVN...

Страница 15: ...uits TB5 Output prerelease circuit 1 2 A 24 Vdc max See riser current TB5 1 and TB5 2 Output prerelease circuit 2 2 A 24 Vdc max See riser current TB5 3 and TB5 4 Line resistance See Table 1 6 End of line device 47 kW resistor Manual release input circuit TB3 1 and TB3 2 Line resistance 25 W wire 18 AWG 3800 ft 0 75 mm2 1158 m End of line device 47 kW resistor Circuit capacitance 0 1 mF max Abort ...

Страница 16: ... m 0 057 3 0 39 ft 11 89 m 27 ft 8 23 m 0 067 2 5 47 ft 14 33 m 32 ft 9 75 m 0 080 2 0 59 ft 17 98 m 40 ft 12 19 m 0 100 1 5 78 ft 23 77 m 53 ft 16 15 m 0 133 1 0 118 ft 35 97 m 80 ft 24 38 m 0 200 Table 1 6 Prerelease and release circuits per circuit Total riser current Amps Distance from XLS REL to signals Wire resistance W per wire 12 AWG 2 5 mm2 14 AWG 1 5 mm2 2 00 176 ft 53 64 m 120 ft 36 58 ...

Страница 17: ...d mounting holes in the MFC A Figure 1 2 and Figure 1 3 2 Secure the XLS REL to the MFC A with the washers and screws provided 3 Run the wiring from the XLS REL to the fire suppression components through the conduit knockouts in the MFC A Figure 1 2 Mounting the XLS REL To mount the XLS REL in other enclosures 1 Use the XLS REL to mark the mounting hole locations Figure 1 4 2 Drill the mounting ho...

Страница 18: ...uit knockout Conduit knockout RELEASE024 CDR 6 Flat Washers 6 32 Self tapping Screws Releasing Module Mounting space See compatible enclosure installation sheets for the routing of power limited and nonpower limited wiring Mounting hole diameter is 0 125 in or 3 175 mm Interior surface of enclosure Interior surface of enclosure Mark the mounting hole locations here 2 1 Notes 1 RELEASE036 CDR ...

Страница 19: ...on of the automatic delay timer or the abort delay timer whichever occurs last 2 If the abort is initiated before the automatic delay timer expires it will prevent the releasing action The automatic delay timer will stop running When the abort is restored the automatic delay timer will resume and the release will occur with the expiration of the timer 3 Industrial Risk Insurers To be recognized as...

Страница 20: ...ngs Time delay SW3 SW4 No delay 0 0 10 seconds Default 0 1 20 seconds 1 0 30 seconds 1 1 Table 1 10 Automatic delay time settings Time delay SW5 SW6 SW7 10 seconds 0 0 0 20 seconds 0 0 1 30 seconds 0 1 0 40 seconds 0 1 1 50 seconds Default 1 0 0 Table 1 11 Abort delay time settings Time delay SW8 No delay 0 10 seconds Default 1 ON ON 0 0 0 1 1 0 0 1 SW 1 2 3 4 5 6 7 8 1 On 0 Off SW TB3 TB2 TB6 Rel...

Страница 21: ... color patterns and functions for each LED Table 1 12 XLS REL LEDs LED Color Pattern Function DS1 Red Flashing Data alarm conditions DS2 Green Flashing Data normal conditions DS3 Red Steady Alarm DS4 Green Steady Power DS5 Yellow Steady Abort DS6 Yellow Steady Trouble DS7 Red Steady Release active TB3 TB2 TB6 TB4 TB5 TB1 Releasing Module DS1 DS2 DS4 DS3 DS5 DS6 DS7 RELEASE027 CDR ...

Страница 22: ...arning next to the XLS REL 4 Inform all appropriate personnel about the posted warning its location and its importance 5 Require compliance with the warning during all installation and service procedures Warning Observe static sensitive material handling practices while installing or servicing the XLS REL Electrostatic discharge may damage the equipment and activate the release circuits Running th...

Страница 23: ... Disconnect all wiring on TB4 of the Releasing Module release circuits 1 and 2 during system service Disabled points will not prevent activation of the release circuits Failure to follow these instructions may result in loss of life serious injury or property damage WARNING RELEASE039 CDR ...

Страница 24: ...ELA EOL Solenoid Polarizing Relay 7 8 Supervised and power limited 9 P W onpolarized valve The releasing solenoid Polarity of circuit shown in supervisory state On alarm polarity reverses ower limited when connected to a power limited source If nonpower limited maintain 1 4 inch 6 4 mm separation Otherwise use FPL FPLR or FPLP in accordance with the National Electric Code NEC Destroy power limited...

Страница 25: ...nstruction carefully Content Programming the XLS REL in the XLS100 SDU 2 2 Adding the XLS REL to the database 2 2 Labeling the XLS REL components 2 4 Programming an AND group 2 4 Reconciling the Signature map 2 4 Writing rules for the XLS REL 2 4 Programming the XLS REL in the XLS1000 SDU Revision 1 5 2 6 Adding the XLS REL to the database 2 6 Labeling the XLS REL components 2 8 Programming an AND...

Страница 26: ...t the XLS100 SDU recognizes it as three SIGA UMs Addresses will differ for each installation but they must be consecutive The XLS REL provides only one serial number label When you scan in the XLS REL only the first two serial numbers will appear in the database To add the XLS REL to the database 1 Scan in the XLS REL serial number label 2 In the SDC Configuration ensure that four blank addresses ...

Страница 27: ...scribed in Tables 2 1 and 2 2 Actual addresses in your system may differ but they must be consecutive Serial numbers must also be consecutive up to the second to last digit Select one of the following DamperControl DoorControl or FanControl Ensure that the selected device type is exclusive for XLS REL use Table 2 1 Device type selections Typical address Typical serial number Device type Model 7 53...

Страница 28: ...1 See Figure 2 1 for the details Reconciling the Signature map Caution Do not use Accept Actual in the Signature Series mapping tool Accepted devices may appear as two devices in the SDC database and corrupt it Use the Break Chain and Commit Expected functions to reconcile the Signature map Writing rules for the XLS REL To write the rules 1 In the Rules Editor write the mandatory rules in Figure 2...

Страница 29: ...PRERELEASE_1 RELEASE DEFINE AND AND_GROUP1 DELAY 10 ON RELEASE_1 RESET DEFINE SYSRESET MCMN1 OFF PRERELEASE_1 OFF RELEASE_1 DUMP ALARM MANUAL ON RELEASE_1 RELEASE010 CDR Note ALARM_1 and ALARM_2 require the addition of two Signature Series alarm devices to the SDC Configuration Make sure that the object labels in the rules match the labels assigned in the Object Configuration RELEASE032 CDR DRILL ...

Страница 30: ...he XLS1000 SDU Revision 1 5 recognizes it as three SIGA UMs Addresses will differ for each installation but they must be consecutive The XLS REL provides only one serial number label When you scan in the XLS REL only the first two serial numbers will appear in the database To add the XLS REL to the database 1 Scan in the XLS REL serial number label 2 In the DSDC configuration Loop X Modules tab en...

Страница 31: ...the device types and personality codes exactly as prescribed in Tables 2 4 and 2 5 Actual addresses in your system may differ but they must be consecutive Serial numbers must also be consecutive up to the second to last digit Table 2 4 Device type selections Typical address Typical serial number Device type Model 126 5300411525 Monitor SIGA UM 127 5300411532 Pull SIGA UM 128 5300411549 SupervisedO...

Страница 32: ...h XLS REL AND group must include a rule with an output statement like the one in ALARM1 See Figure 2 3 for the details Warning Set the AND group to an Activate number 2 or greater Activate number 1 will cause the AND group to become an OR group and any activation of Alarm_1 or Alarm_2 will activate the release sequence Note For preaction operation set the Activate number to 1 This will cause the A...

Страница 33: ...l rules for the XLS REL Avoid using the Drill switch to test the XLS REL If you activate a Drill press the Reset switch before you deactivate it The deactivation of the Drill switch alone will not silence the prerelease tones ALARM1 ALARM ALARM_1 ON PRERELEASE_1 ALARM2 ALARM ALARM_2 ON PRERELEASE_1 ANDGROUP DUMP ALARM AND_GROUP1 DLYA 10 ON RELEASE_1 DLYR 10 DUMP ALARM MANUAL ON HIGH RELEASE_1 RELE...

Страница 34: ...ut the XLS1000 SDU Revision 2 0 recognizes it as three XLS RELs Addresses will differ for each installation but they must be consecutive The XLS REL provides only one serial number label When you scan in the XLS REL only the first two serial numbers will appear in the database To add the XLS REL to the database 1 Scan in the XLS REL serial number label 2 In the DSDC configuration Loop X Modules ta...

Страница 35: ... the device types and personality codes exactly as prescribed in Tables 2 7 and 2 8 Actual addresses in your system may differ but they must be consecutive Serial numbers must also be consecutive up to the second to last digit Table 2 7 Device type selections Typical address Typical serial number Device type Model 126 5300411525 Monitor XLS REL 127 5300411532 Pull XLS REL 128 5300411549 Supervised...

Страница 36: ...arning Set the AND group to an Activate number 2 or greater Activate number 1 will cause the AND group to become an OR group and any activation of Alarm_1 or Alarm_2 will activate the release sequence Check only Q1 for each device in the listbox labeled Devices in Selected Group For Q1 only a detector in alarm will count as a device activation If you check Q2 Q3 or Q4 the release circuit may accid...

Страница 37: ...al rules for the XLS REL Avoid using the Drill switch to test the XLS REL If you activate a Drill press the Reset switch before you deactivate it The deactivation of the Drill switch alone will not silence the prerelease tones ALARM1 ALARM ALARM_1 ON PRERELEASE_1 ALARM2 ALARM ALARM_2 ON PRERELEASE_1 ANDGROUP DUMP ALARM AND_GROUP1 DLYA 10 ON RELEASE_1 DLYR 10 DUMP ALARM MANUAL ON HIGH RELEASE_1 REL...

Страница 38: ...he status LEDs indicate anything pending or in progress This includes Mapping Device new starts Resets Restarts Testing XLS1000 systems Allow the system sufficient time to stabilize after the initial startup or download Before you test the system access the DSDC Status tool in the XLS1000 SDU Do not test the system if the status LEDs indicate anything pending or in progress This includes Mapping D...

Страница 39: ...its into the fire alarm system and behaves during fire alarms Content Integrating the Releasing Module with fire alarm systems 3 2 System overview 3 2 Preaction deluge sprinkler systems 3 2 Automatic fire extinguishing systems 3 3 Developing a fire suppression plan 3 4 Releasing fire suppression agents 3 5 Understanding the automatic release sequence 3 5 Initiating manual releases 3 6 ...

Страница 40: ...pecifications mounting and abort mode settings For wiring resistance calculations see pages 1 7 and 1 8 Preaction deluge sprinkler systems Figure 3 1 illustrates the integration of the XLS REL with the fire alarm control panel and a preaction or deluge sprinkler system Sprinkler systems do not include service disconnect stations abort stations or manual release stations Figure 3 1 Integration of t...

Страница 41: ...rm control panel in an automatic fire extinguishing system Figure 3 2 Integration of the Releasing Module with an automatic extinguishing system Signature loop controller Releasing Module RELEASE012 CDR Fire alarm control panel Fire suppression system 2 RELA EOL Fire suppression system 1 Legend Signature Series smoke detectors Signature Series modules Horn circuit Strobe circuit Service disconnect...

Страница 42: ...Releasing Module Figure 3 3 Typical computer room application Signature loop controller Releasing Module SD RELEASE015 CDR Fire alarm control panel Legend Signature Series smoke detectors Horn circuit Strobe circuit Service disconnect station Manual abort station Manual release station SD Raised floor Slab 2 1 Extinguishing agent storage cylinder Release circuit 1 Release circuit 2 Wall mounted ag...

Страница 43: ...ound at 15 and 60 pulses per minute The audible release signal is a steady tone Prerelease circuit 2 supports visual notification appliances RELEASE013 CDR Release circuits First alarm relay Automatic delay timer Prerelease circuits Selectable automatic delay time 10 to 50 seconds 1 4 5 1 A detector signals the first alarm This event simultaneously activates the First alarm relay Prerelease strobe...

Страница 44: ...e 0 to 30 seconds 1 3 4 Time line See details below 2 1 An active manual release station disables automatic operation and the abort function and simultaneously activates the Manual delay timer Prerelease circuit Prerelease strobe circuit steady On Prerelease horn circuit 60 pulses per minute 2 10 seconds before the expiration of the manual delay timer the pre release horn changes from 60 pulses pe...

Страница 45: ...mmary You may occasionally see XLS REL messages on the front panel display Table 4 1 provides trouble indications for XLS100 panels Table 4 2 provides trouble indications for XLS1000 panels Content XLS REL indications on XLS100 panels 4 2 XLS REL indications on XLS1000 panels 4 4 ...

Страница 46: ...is is a normal indication and it should go away within minutes Table 4 1 lists the indications you may see for the XLS REL on the 2 LCD Table 4 1 Releasing Module indications Device Condition LED 2 LCD message Abort Short Monitor None unless there is another event Open Trouble Open Fault Abort Manual Short Alarm 1st Fire Alarm Manual Open Trouble Open Fault Manual Prerelease_1 Short Trouble Short ...

Страница 47: ...al 4 3 XLS REL trouble indications Release_2 Short Trouble Dev Line Flt Release_2 Open Trouble Open Fault Release_2 Message requires user programming Table 4 1 Releasing Module indications Continued Device Condition LED 2 LCD message ...

Страница 48: ...s the indications you may see for the XLS REL on the 3 LCD Table 4 2 Releasing Module indications Device Condition LED 3 LCD message Abort Short Monitor MONITOR ACT Abort Open Trouble COMMON TRBL ACT Abort Expanded message TROUBLE OPEN ACT Manual Short Alarm PULL STATION ACT Manual Open Trouble COMMON TRBL ACT Manual Expanded message TROUBLE OPEN ACT Prerelease_1 Short Trouble COMMON TRBL ACT Prer...

Страница 49: ...CT Open Trouble COMMON TRBL ACT Release_1 Expanded message TROUBLE OPEN ACT Release_2 Short Trouble COMMON TRBL ACT Release_2 Expanded message TROUBLE SHRT ACT Open Trouble COMMON TRBL ACT Release_2 Expanded message TROUBLE OPEN ACT Message requires user programming Table 4 2 Releasing Module indications Continued Device Condition LED 3 LCD message ...

Страница 50: ...XLS REL trouble indications 4 6 XLS REL Technical Reference Manual ...

Страница 51: ...loping a fire suppression plan 3 4 DIP switch settings 1 11 1 12 distances wire 1 8 documentation related iii E enclosures See panels compatible environmental conditions 1 8 European standards v F first alarm contact 1 7 FCC warning ii FMRC Factory Mutual Research Corporation v 1 3 1 4 L labeling XLS REL components 2 4 2 8 2 12 LEDs 1 13 listing agencies iv v 1 6 M manual delay time settings 1 12 ...

Страница 52: ... cutout 1 15 warnings disabling release circuits vi 1 15 4 2 4 4 FCC ii limitation of liability ii for programming the XLS REL 2 2 2 6 2 10 for servicing the XLS REL 1 14 for system testing 2 14 wire distances 1 8 wiring the XLS REL 1 14 1 16 writing rules for the XLS REL in the XLS100 SDU 2 5 in the XLS1000 SDU Revision 1 5 2 9 in the XLS1000 SDU Revision 2 0 2 13 X XLS100 documentation iii SDU p...

Отзывы: