XLS-REL Technical Reference Manual
2.9
Programming the XLS-REL
Reconciling the Signature map
Caution!
Do not use
Accept Actual
in the Signature Series
mapping tool. Accepted devices may appear as two devices in the
SDC database and corrupt it. Use the
Break Chain
and
Commit
Expected
functions to reconcile the Signature map.
Writing rules for the XLS-REL
To write the rules:
1
In the Rules Editor, write the mandatory rules in Figure 2-3
and the optional rules in Figure 2-4.
2
Compile the rules and run the required conversions.
3
Download and upload the new information.
Note:
See the system testing section, at the end of this chapter,
before you test of your system.
Figure 2-3: Mandatory rules for the XLS-REL
Figure 2-4: Optional rules for the XLS-REL
Avoid using the Drill switch to test the XLS-REL. If you activate
a Drill, press the Reset switch before you deactivate it. The
deactivation of the Drill switch, alone, will not silence the
prerelease tones.
[ALARM1]
ALARM 'ALARM_1' :
ON 'PRERELEASE_1';
[ALARM2]
ALARM 'ALARM_2' :
ON 'PRERELEASE_1';
[ANDGROUP DUMP]
ALARM 'AND_GROUP1' :
DLYA 10,
ON 'RELEASE_1',
DLYR 10;
[DUMP]
ALARM 'MANUAL' : ON -HIGH 'RELEASE_1';
RELEASE011.CDR
Note:
[ALARM_1] and [ALARM_2] require the addition
of alarm devices to the panel configuration. Make sure
that the object labels match the labels assigned to
them in the Object Configuration.
[DRILL]
DRILL :
ON 'PRERELEASE_1';
[LED1]
RLYCFG 'PRERELEASE_1' :
ON 'LED_1_1';
[LED2]
RLYCFG 'RELEASE_1' :
ON 'LED_1_2';
RELEASE033.CDR
Note:
[LED1] and [LED2] require the addition of an LED
module to the Cabinet Configuration (Modules tab,
operator layer). Make sure that the labels for the LEDs
match the labels assigned to them in the Object
Configuration.