Installing the XLS-REL
1.8
XLS-REL Technical Reference Manual
Environmental conditions
Operating temperature
32 to 120
°
F (0 to 49
°
C)
Storage temperature
-4 to 140
°
F (-20 to 60
°
C)
Humidity
0 to 93% RH, non-condensing
Table 1-5: Power riser
Total riser
current
(Amps)
Distance from XLS-REL to power supply
Wire
resistance
(
W
per wire)
#12 AWG
2.5 mm
2
#14 AWG
1.5 mm
2
4.0
29 ft
8.84 m
20 ft
6.10 m
0.050
3.5
34 ft
10.36 m
23 ft
7.01 m
0.057
3.0
39 ft
11.89 m
27 ft
8.23 m
0.067
2.5
47 ft
14.33 m
32 ft
9.75 m
0.080
2.0
59 ft
17.98 m
40 ft
12.19 m
0.100
1.5
78 ft
23.77 m
53 ft
16.15 m
0.133
1.0
118 ft
35.97 m
80 ft
24.38 m
0.200
Table 1-6: Prerelease and release circuits (per circuit)
Total riser
current
(Amps)
Distance from XLS-REL to signals
Wire
resistance
(
W
per wire)
#12 AWG
2.5 mm
2
#14 AWG
1.5 mm
2
2.00
176 ft
53.64 m
120 ft
36.58 m
0.300
1.75
202 ft
61.57 m
137 ft
41.76 m
0.343
1.50
235 ft
71.63 m
160 ft
48.77 m
0.400
1.25
282 ft
85.95 m
192 ft
58.52 m
0.480
1.00
353 ft
107.59 m
240 ft
73.15 m
0.600
0.50
706 ft
215.19 m
480 ft
146.30 m
1.200