 MODEL 30 EXPANSION IO MODULES - INSTALLATION INSTRUCTIONS 

31-00319-02 

 

 

 

In case all binary loads connected to the CIPer Model 30 controller and CIPer 30 EXPIO device, then con-
troller must use separate transformers for powering controller and additional transformer for powering EX-
PIO device.  

 

Use heavier gauge wire for the power run. 14 AWG (2.0 sq mm) wire is the recommended wire size for 24 
VAC wiring. 

 

Locate the transformer closer to the device. This reduces the length of the wire run, and the line-loss. 

Transformer VA load for module power only (without any binary output loads connected) 

a)

 

WEB-C3036EPUBNH = 50VA 

b)

 

WEB-C3036EPVBNH = 50VA 

c)

 

WEB-O9056H = 35VA 

d)

 

WEB-O3022H = 15VA 

DIN Rail Mounting 

The CIPer 30 EXPIO mounts on a standard DIN rail in one of two ways: 

o

 

Vertically, with the connections on the right and left sides of the unit. 

o

 

Horizontally, with the connections on the top and bottom of the unit. 

The CIPer 30 EXPIO has a locking clip, similarly like CIPer Model 30 controller. Mounting on DIN rail ensures accu-
rate alignment between all modules and controller. The CIPer 30 EXPIO can also be screw-mounted using the four 
mounting tabs, accessible under the covers. These mounting tabs can be broken off if user needed to save space 
when DIN rail mounting. 

 

WARNING 

 

All the terminals and power connections should be wired before mounting to a panel or DIN rail.  

 

Make sure the CIPer Model 30 controller is not connected to power supply while mounting CIPer 30 
EXPIO device. 

To mount the CIPer 30 EXPIO on a DIN rail 

1.

 

Hold the EXPIO with its top tilted in towards the DIN rail, hook the two top tabs on the back of the EXPIO 
onto the top of the DIN rail. Ensure EXPIO serial expansion plug is facing toward the Controller serial ex-
pansion socket.  

2.

 

Push down the EXPIO and latching all the tabs of the EXPIO onto the DIN rail. 

3.

 

Move EXPIO along the DIN rail toward the CIPer Model 30 Controller, ensure both the raised alignment tabs 
of CIPer Model 30 Controller align to the depression of the EXPIO, and latch them together. 

4.

 

Properly ground the panel, then terminate grounded components of power, communications, and I/O wir-
ing. 

To remove the CIPer 30 EXPIO from the DIN rail 

1.

 

Push straight down from the top to release the bottom tabs. 

2.

 

Rotate the bottom of the EXPIO out towards you and pull the EXPIO up and away from the DIN rail to release 
the bottom latching tabs. 

 

IMPORTANT  

Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the 
controller, or in areas where escaping gas or other explosive vapors are present.  

Содержание WEB-O3022H

Страница 1: ...t connections along with the on board IO connections The I O points which user can add externally as an expansion to existing on board points are called as expansion I O points The CIPer Model 30 Expansion IO EXPIO modules are available in two models as described in the table below Devices UI BO UIO WEB O9056H 9 6 5 WEB O3022H 3 2 2 Each device is programmable because the user chooses which functi...

Страница 2: ...loads connected 207VA Without any binary output loads connected 35VA WEB O3022H With all binary output loads connected 87VA Without any binary output loads connected 15VA Digital Output voltage rating 20 to 30 VAC 50 60 Hz Digital Output type rating Solid State Relay 1 5A Continuous 3 5A inrush for 100 ms Environmental Ambient temperature 4 to 131F 20 to 55C Storage temperature 4 to 150F 20 to 65C...

Страница 3: ...the controller The CIPer 30 EXPIO must be mounted in a position that allows clearance for wiring servicing removal connection of the terminal blocks and access to the IP address and DIP switches Both the CIPer 30 EXPIO WEB O9056H and WEB O3022H can be connected directly or remotely with CIPer Model 30 controller WEB C3036EPUBNH and WEB C3036EPVBNH Power Guidelines For multiple devices operating fr...

Страница 4: ...unting tabs can be broken off if user needed to save space when DIN rail mounting WARNING All the terminals and power connections should be wired before mounting to a panel or DIN rail Make sure the CIPer Model 30 controller is not connected to power supply while mounting CIPer 30 EXPIO device To mount the CIPer 30 EXPIO on a DIN rail 1 Hold the EXPIO with its top tilted in towards the DIN rail ho...

Страница 5: ... MODULES INSTALLATION INSTRUCTIONS 5 31 00319 02 Figure 1 Stacked power wiring connection for CIPer Model 30 Controllers and EXPIO Remotely Mounting Figure 2 Remotely power wiring connection for CIPer Model 30 Controllers and EXPIO ...

Страница 6: ...nd Expansion I O devices The H O A switch overrides all the software commands when set to HAND or OFF Digital Outputs DOs If you configure the HOA switches to Off Mode the Physical Digital Output is disabled irrespective of the Control program logic output If you configure the HOA switches to Auto Mode the Physical Output responses as per the value pro vided by the Control program logic output If ...

Страница 7: ... a small screwdriver to turn the adjustment screw fully counter clockwise The clamps in the wire slot separate as you turn the screw 3 When the clamps in the wire slot are fully open insert the stripped end of the cable the insulation end must be flush with the terminal block Be sure to insert all cable strands into the wire slot 4 Hold the cable in place and turn the adjustment screw clockwise to...

Страница 8: ...I 2 4 Universal inputs UI 3 5 COM terminal for UI 3 6 Supplies 20V DC 7 24V AC output from controller for DO devices 8 HOT B terminal Supplies power to common side of controller s DO 2 9 HOT A terminal Supplies power to common side of controller s DO 1 10 DO 1 A 11 GND terminal for DO 1 A DO 2 B 12 DO 2 B 13 15 Universal inputs UI 4 AO 1 UI 5 AO 2 14 COM terminal for UI 4 AO 1 UI 5 AO 2 ...

Страница 9: ...2 Universal inputs UI 6 UI 7 11 COM terminal for UI 6 UI 7 13 15 Universal inputs UI 8 UI 9 14 COM terminal for UI 8 UI 9 16 Supplies 20V DC 17 24V AC output from controller for DO devices 18 HOT B terminal Supplies power to common side of controller s DO 5 DO 6 19 HOT A terminal Supplies power to common side of controller s DO 1 to DO 4 20 22 DO 1 A DO 2 A 21 GND terminal for DO 1 A DO 2 A 23 25 ...

Страница 10: ...r and device To conform to Class II restrictions U S only the transformer must not be larger than 100 VA IMPORTANT Power must be off prior to connecting to or removing connections from the 24 VAC power 24 VAC 24 VAC COM earth ground EGND and 20 VDC power 20 VDC terminals Use the heaviest gauge wire available up to 14 AWG 2 0 sq mm with a minimum of 18 AWG 1 0 sq mm for all power and earth ground w...

Страница 11: ...trical contact see Fig 4 Prepare wiring for the terminal blocks as follows 1 Strip 1 2 in 13 mm insulation from the conductor 2 Cut a single wire to 3 16 in 5 mm Insert the wire in the required terminal location and tighten the screw 3 If two or more wires are being inserted into one terminal location twist the wires together a minimum of three turns before inserting them see Fig 4 4 Cut the twist...

Страница 12: ... verified earth ground for each controller or device in the group Keep the earth ground connection wire run as short as possible Do not connect the universal input COM terminals analog output COM terminals or the digital input output COM terminals to earth ground Disposal The product should not be disposed of with other household waste Check for the nearest authorized collection centers or authori...

Страница 13: ...llation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harm ful interference to radio or television reception which can be determined by...

Отзывы: