TM

 MODEL 30 EXPANSION IO MODULES - INSTALLATION INSTRUCTIONS 

 

3

 

31-00319-02 

 

Dimension Drawings 

 

 

WEB-O3022H

 

WEB-O9056H

 

Installation 

 

WARNING 

 

Install all equipment in accordance with the National Electric Code and in a manner acceptable to 
the  local  authority  having  jurisdiction.  Read  these  instructions  and  the  CIPer    30  Expansion  IO 
Modules (EXPIO) Installation Instructions (31-00319) carefully before installing equipment. Fail-
ure to follow all instructions may result in equipment damage or a hazardous condition. 

 

The CIPer 30 EXPIO module is susceptible to electrostatic discharge (ESD). Use appropriate ESD 
grounding techniques while handling the product. When possible, always handle the product by its 
non-electrical components. Review the power, input, and output specifications before installing the 
controller. 

The CIPer 30 EXPIO must be mounted in a position that allows clearance for wiring, servicing, removal, connection 
of the terminal blocks and access to the IP address and DIP switches. Both the CIPer 30 EXPIO (WEB-O9056H

 

and 

WEB-O3022H) can be connected directly or remotely with CIPer Model 30 controller (WEB-C3036EPUBNH and 
WEB-C3036EPVBNH).  

Power Guidelines 

 

For multiple devices operating from a single transformer, the same side of the transformer secondary must 
be connected to the same power input terminal in each device.  

 

The earth ground terminal must be connected to a verified earth ground and keep the earth ground con-
nection wire run as short as possible.  

 

Each configuration may not necessarily limit to three devices, but the total power draw, including accesso-
ries, cannot exceed 100 VA when powered by the same transformer. In case it exceeds 100VA, use separate 
transformer to power up the modules. 

 

Do not connect earth ground to the device’s digital or analog ground terminals

Содержание WEB-O3022H

Страница 1: ...t connections along with the on board IO connections The I O points which user can add externally as an expansion to existing on board points are called as expansion I O points The CIPer Model 30 Expansion IO EXPIO modules are available in two models as described in the table below Devices UI BO UIO WEB O9056H 9 6 5 WEB O3022H 3 2 2 Each device is programmable because the user chooses which functi...

Страница 2: ...loads connected 207VA Without any binary output loads connected 35VA WEB O3022H With all binary output loads connected 87VA Without any binary output loads connected 15VA Digital Output voltage rating 20 to 30 VAC 50 60 Hz Digital Output type rating Solid State Relay 1 5A Continuous 3 5A inrush for 100 ms Environmental Ambient temperature 4 to 131F 20 to 55C Storage temperature 4 to 150F 20 to 65C...

Страница 3: ...the controller The CIPer 30 EXPIO must be mounted in a position that allows clearance for wiring servicing removal connection of the terminal blocks and access to the IP address and DIP switches Both the CIPer 30 EXPIO WEB O9056H and WEB O3022H can be connected directly or remotely with CIPer Model 30 controller WEB C3036EPUBNH and WEB C3036EPVBNH Power Guidelines For multiple devices operating fr...

Страница 4: ...unting tabs can be broken off if user needed to save space when DIN rail mounting WARNING All the terminals and power connections should be wired before mounting to a panel or DIN rail Make sure the CIPer Model 30 controller is not connected to power supply while mounting CIPer 30 EXPIO device To mount the CIPer 30 EXPIO on a DIN rail 1 Hold the EXPIO with its top tilted in towards the DIN rail ho...

Страница 5: ... MODULES INSTALLATION INSTRUCTIONS 5 31 00319 02 Figure 1 Stacked power wiring connection for CIPer Model 30 Controllers and EXPIO Remotely Mounting Figure 2 Remotely power wiring connection for CIPer Model 30 Controllers and EXPIO ...

Страница 6: ...nd Expansion I O devices The H O A switch overrides all the software commands when set to HAND or OFF Digital Outputs DOs If you configure the HOA switches to Off Mode the Physical Digital Output is disabled irrespective of the Control program logic output If you configure the HOA switches to Auto Mode the Physical Output responses as per the value pro vided by the Control program logic output If ...

Страница 7: ... a small screwdriver to turn the adjustment screw fully counter clockwise The clamps in the wire slot separate as you turn the screw 3 When the clamps in the wire slot are fully open insert the stripped end of the cable the insulation end must be flush with the terminal block Be sure to insert all cable strands into the wire slot 4 Hold the cable in place and turn the adjustment screw clockwise to...

Страница 8: ...I 2 4 Universal inputs UI 3 5 COM terminal for UI 3 6 Supplies 20V DC 7 24V AC output from controller for DO devices 8 HOT B terminal Supplies power to common side of controller s DO 2 9 HOT A terminal Supplies power to common side of controller s DO 1 10 DO 1 A 11 GND terminal for DO 1 A DO 2 B 12 DO 2 B 13 15 Universal inputs UI 4 AO 1 UI 5 AO 2 14 COM terminal for UI 4 AO 1 UI 5 AO 2 ...

Страница 9: ...2 Universal inputs UI 6 UI 7 11 COM terminal for UI 6 UI 7 13 15 Universal inputs UI 8 UI 9 14 COM terminal for UI 8 UI 9 16 Supplies 20V DC 17 24V AC output from controller for DO devices 18 HOT B terminal Supplies power to common side of controller s DO 5 DO 6 19 HOT A terminal Supplies power to common side of controller s DO 1 to DO 4 20 22 DO 1 A DO 2 A 21 GND terminal for DO 1 A DO 2 A 23 25 ...

Страница 10: ...r and device To conform to Class II restrictions U S only the transformer must not be larger than 100 VA IMPORTANT Power must be off prior to connecting to or removing connections from the 24 VAC power 24 VAC 24 VAC COM earth ground EGND and 20 VDC power 20 VDC terminals Use the heaviest gauge wire available up to 14 AWG 2 0 sq mm with a minimum of 18 AWG 1 0 sq mm for all power and earth ground w...

Страница 11: ...trical contact see Fig 4 Prepare wiring for the terminal blocks as follows 1 Strip 1 2 in 13 mm insulation from the conductor 2 Cut a single wire to 3 16 in 5 mm Insert the wire in the required terminal location and tighten the screw 3 If two or more wires are being inserted into one terminal location twist the wires together a minimum of three turns before inserting them see Fig 4 4 Cut the twist...

Страница 12: ... verified earth ground for each controller or device in the group Keep the earth ground connection wire run as short as possible Do not connect the universal input COM terminals analog output COM terminals or the digital input output COM terminals to earth ground Disposal The product should not be disposed of with other household waste Check for the nearest authorized collection centers or authori...

Страница 13: ...llation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harm ful interference to radio or television reception which can be determined by...

Отзывы: