VS8421 VENTFREE MILLIVOLT GAS VALVE

69-1219—1

2

CAUTION

Electrical Shock or Equipment Damage 
Hazard.
Can shock individuals or short equipment 
circuitry.

Disconnect all power supplies before installation.

CAUTION

Equipment Damage.
Can burn out heat anticipator in thermostat.

Never apply a jumper across or short the valve 
coil terminals.

IMPORTANT

These gas valves are shipped with protective 
seals over the inlet and outlet tappings. Do not 
remove the seals until ready to connect the 
piping.

Follow the appliance manufacturer instructions, if 
available; otherwise, use these instructions.

Converting Between Natural and LP Gas

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury or 
death.

Do not use a gas valve set for natural gas on an 
LP gas system or a gas valve set for LP gas on a 
natural gas system. Gas valves are factory-set for 
natural (and manufactured) or LP gas. 
VS8421 ventfree valves are not convertible.

Location

Locate the combination gas valve where it cannot be 
affected by steam cleaning, high humidity, dripping water, 
corrosive chemicals, dust or grease accumulation or 
excessive heat. To assure proper operation, follow these 
guidelines:

Locate gas valve in a well-ventilated area.

Mount gas valve high enough to avoid exposure to 
flooding or splashing water.

Assure the ambient temperature does not exceed the 
ambient temperature ratings for each component.

Cover gas valve if appliance is cleaned with water, 
steam, or chemicals or to avoid dust and grease 
accumulation.

Avoid locating gas valve where it can be exposed to 
corrosive chemical fumes or dripping water.

Install Piping to Gas Valve

All piping must comply with local codes and ordinances 
or with the National Fuel Gas code (ANSI Z223.1 NFPA 
No. 54), whichever applies. Tubing installation must 
comply with approved standards and practices.

1.

Use new, properly reamed pipe free from chips. 
When tubing is used, assure the ends are square, 
deburred and clean. All tubing bends must be 
smooth and without deformation.

2.

Run pipe or tubing to the valve. If tubing is used, 
obtain a tube-to-pipe coupling to connect the 
tubing to the valve.

3.

Install sediment trap in the supply line to the gas 
valve. See Fig. 1.

Install Valve

1.

Mount valve 0 to 90 degrees, in any direction—
including vertically—from the upright position of the 
gas control knob.

2.

Mount the valve so gas flow is in the direction of 
the arrow on the side of the valve.

3.

Thread pipe 9/16 in. into the valve. Do not insert 
deeper than 3/8 in. Valve distortion or malfunction 
can result if the pipe is inserted too deeply.

4.

Apply a moderate amount of good quality pipe 
compound (do not use Teflon tape) to pipe only, 
leaving two end threads bare. On LP installations, 
use compound resistant to LP gas. See Fig. 2.

5.

Remove seals over valve inlet and outlet, if 
necessary.

6.

Connect pipe to valve inlet and outlet. Use wrench 
on either side of the pipe outlet. Refer to Fig. 3 
through 5.

Fig. 1. Sediment trap installation.

Fig. 2. Use moderate amount of pipe compound.

GAS
CONTROL

GAS
CONTROL

HORIZONTAL

DROP

PIPED
GAS
SUPPLY

PIPED
GAS
SUPPLY

3 INCHES
(76 MM)
MINIMUM

3 INCHES
(76 MM)
MINIMUM

RISER

GAS
CONTROL

TUBING
GAS
SUPPLY

HORIZONTAL

DROP

3 INCHES
(76 MM)
MINIMUM

RISER

M4603A

1

1

CAUTION

GAS LEAKAGE HAZARD. 
FAILURE TO FOLLOW PRECAUTIONS CAN 
RESULT  IN A GAS-FILLED WORK AREA.
SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP.  
TEST FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

TWO IMPERFECT 
THREADS

GAS CONTROL

THREAD PIPE ACCORDING TO
INSTALLATION PROCEDURE FOR 
INSERTION INTO GAS CONTROL. 

APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).

M6913

PIPE

69-1219-1.fm  Page 2  Thursday, August 18, 2011  7:32 AM

Содержание VS8421

Страница 1: ...icate C2030022 European Community CE Certificate Applied for INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technicia...

Страница 2: ...lies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips When tubing is used assure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the valve If tubing is used obtain a tube to pipe coupling to connect the tubing to the valve 3 Install sediment trap in the supply ...

Страница 3: ...s valve M12670 HI LO REGULATOR WIRING TERMINALS INLET PRESSURE TAP OUTLET PRESSURE TAP GAS CONTROL KNOB OFF PILOT ON PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW M12673 WIRING TERMINALS INLET PRESSURE TAP OUTLET PRESSURE TAP GAS CONTROL KNOB OFF PILOT ON PIEZO SPARKER APPLY WRENCH FROM BOTTOM OF GAS CONTROL TO SHADED AREA M12679 69 1219 1 fm Page 3 Thursday August 18 2011 7 32 AM ...

Страница 4: ...he pilot burner The piezo creates a spark when the plunger is depressed The connecting wires of the piezo include a terminal to connect to the electrode of the pilot burner The piezo is replaceable Refer to the installation instructions for the piezo envelope assembly part no 396079 form 69 1206 Fig 6 Millivolt system wiring diagram with ODS pilot burner Pilot Gas Lighting Procedure Lighting Stand...

Страница 5: ...rate using the meter clocking method or measure the pressure by attaching a plastic tube with a 1 4 in shell ID to the manometer and connecting the manometer to the outlet pressure tap on the gas valve See Fig 4 3 If necessary adjust the pressure regulator to match the appliance rating See Table 1 for factory set nominal outlet pressure and adjustment range a Remove the pressure regulator adjustme...

Страница 6: ...pliance being checked NOTE Other appliances must remain off with the pilots extinguished or the consumption must be deducted from the meter reading 2 Convert the flow rate to Btuh as described in the Gas Controls Handbook form 70 2602 3 Compare to the Btuh input rating on the appliance nameplate Checking Gas Input With Manometer NOTE Both the inlet and outlet pressure taps have a captive screw 1 B...

Страница 7: ...UTION Equipment Damage Can burn out heat anticipator in thermostat Do not apply a jumper across or short the valve coil terminals even temporarily If Main Burner Does Not Come On With Call For Heat 1 Confirm that the gas control knob is in the ON position 2 Adjust the thermostat several degrees above the room temperature 3 Use a dc voltmeter to measure the voltage across the THTP and TP terminals ...

Страница 8: ... is less than 12 mV replace the ODS pilot burner assembly The power unit will hold in down to 3 mV If the output of the thermocouple is less than 3 mV replace the ODS pilot burner assembly 4 Test D Operator Pull In have thermostat contacts open and pilot lit with Pilotstat knob turned to PILOT Close the thermostat contacts Operator will pull in with a minimum of 155 mV Operator makes audible sound...

Отзывы: