Honeywell VR8215N Скачать руководство пользователя страница 6

VR8215S,T SINGLE STAGE VR8215Q,N TWO STAGE DIRECT IGNITION GAS CONTROLS

69-2253—07

6

4.

If necessary, adjust the pressure regulator to 
match the appliance rating.

5.

If the desired outlet pressure or flow rate cannot 
be achieved by adjusting the gas control, check 
the gas control inlet pressure using a 
manometer at the inlet pressure tap of the gas 
control. If the inlet pressure is in the nominal 
range (see Table 6), replace the gas control. 
Otherwise, take the necessary steps to provide 
proper gas pressure to the control.

6.

Two stage valves will require outlet pressure 
verification for both HI and LO fire.

Check Safety Lockout 
Slow-Opening (T, N) Controls Only

1.

With the system power off and the thermostat 
set to call for heat, manually shut off the gas 
supply.

2.

Energize ignition control and start timing safety 
lockout time. When spark ignition terminates, 
stop timing.

NOTE:

When using the VR8215T or VR8215N, 
the specified ignition control safety 
lockout time must exceed 8.5 seconds 
for the system to function properly.

3.

After spark cutoff, manually reopen the gas 
control switch. No gas should flow to the main 
burner.

4.

Reset the system by adjusting the thermostat 
below room temperature, wait 30 seconds, and 
then move the thermostat setting up to call for 
heat. Normal ignition should occur.

5.

Two stage valves will require outlet pressure 
verification for both HI and LO fire. 

Table 6.  Pressure Regulator Specification 

Pressures in inches WC (kPa).

1

Some models 3.0 - 5.0 (0.8 - 1.3).

Check Safety Shutdown 
Performance

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury 
or death.

Perform the safety shutdown test any time 
work is done on a gas system.

NOTE:

Read steps 1 through 7 before starting, and 
compare to the safety shutdown or safety 
lockout tests recommended for the direct 
ignition (DI) module. Where different, use the 
procedure recommended for the ignition 
module.

1.

Turn off gas supply.

2.

Set thermostat or controller above room 
temperature to call for heat.

3.

Watch for ignition spark or for glow at hot sur-
face igniter either immediately or following pre-
purge. See Direct Ignition module specifications.

4.

Time the length of spark operation. See the 
Direct Ignition module specifications.

5.

After the module locks out, open the manual gas 
cock and make sure no gas is flowing to the main 
burner.

6.

Set the thermostat below room temperature and 
wait one minute.

7.

Operate system through one complete cycle to 
make sure all controls operate properly.

MAINTENANCE

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury, 
or death.

Do not disassembly the gas control; it contains 
no replaceable components. Attempted 
disassembly, repair, or cleaning can damage 
the control, resulting in gas leakage.

Model Type

Type of 

Gas

Nominal Inlet 

Pressure Range

Factory Set Nominal 

Outlet Pressure

Setting Range

Single Stage

Standard, 

Slow

NAT

5.0-7.0

(1.2-1.7)

3.5

(0.9)

2.5-3.5

1

(0.6-0.9)

1

LP

12.0-14.0

(3.0-3.5)

10.0
(2.5)

8.0-12.0
(2.0-3.0)

Two Stage

Standard, 

Slow

NAT

5.0-7.0

(1.2-1.7)

1.7 (0.4) Low

3.5 (0.9) High

1.5 - 2.5 Low

(0.4-0.6) Low

2.5-3.7 High

(0.6-0.9) High

LP

12.0-14.0

(3.0-3.5)

5.0 (1.3) Low

10.0 (2.5) High

4.5 - 7.0 Low

(1.1-1.7) Low

8.0-11.0 High
(2.0-2.7) High

Содержание VR8215N

Страница 1: ... 6 4 mm SPECIFICATIONS Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw Single Stage 0 5 A Two Stage 0 9 A Field Wiring Single Stage Two 1 4 in spade quick connect terminals Two Stage Molex and spade quick connect terminals two 1 4 in and one 3 16 in Capacity See Table 1 Conversion Use conversion factors in Ta...

Страница 2: ... attack the control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the control Where chemicals are suspended in air as in some industrial or agricultural applications protect the control with an enclosure Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide co...

Страница 3: ...the ambient temperature ratings for each component Cover gas control if appliance is cleaned with water steam or chemicals or to avoid dust and grease accumulation Avoid locating gas control where exposure to corrosive chemical fumes or dripping water are likely Install Piping to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 5...

Страница 4: ... ignition coils HI Second stage or high fire 4 For single stage controls VR8215S T adjust thermostat heat anticipator to 0 50A rating stamped on valve label For two stage controls VR8215Q N adjust thermostat heat anticipator to 0 90A rating stamped on valve label Fig 4 Typical wiring connections for 24 volt control in S87 Direct Ignition System GAS CONTROL GAS CONTROL HORIZONTAL DROP PIPED GAS SUP...

Страница 5: ... burner is properly adjusted for complete combustion Follow appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING GAS METER Make certain there is no gas flow through the meter other than to the appliance being checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2...

Страница 6: ...afety Shutdown Performance WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Perform the safety shutdown test any time work is done on a gas system NOTE Read steps 1 through 7 before starting and compare to the safety shutdown or safety lockout tests recommended for the direct ignition DI module Where different use the procedure recommended for the ignition module 1...

Страница 7: ... of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environments Since these environments can cause the gas control to deteriorate more rapidly the system should be checked more often The system should be replaced if It does not perform properly on checkout or troubleshooting The gas control is likely to have operated for more than 200 000 cycles...

Страница 8: ...g spring 5 Insert the replacement spring See Fig 6 6 Install the new plastic pressure regulator adjust ment screw 7 Check the regulator setting using a manometer or by clocking the gas meter See Check and Adjust Gas Input and Burner Ignition on page 5 8 Adjust regulator by following the Single Stage Regulator Adjust ment process below 9 Reinstall the regulator cap screw 10 Mount conversion label o...

Страница 9: ...ting using a manometer or by clocking the gas meter See Check and Adjust Gas Input and Burner Ignition on page 5 8 Adjust high fire first by adjusting exterior 7 16 Hex After high fire has been set adjust low fire utilizing interior 3 32 allen See Fig 8 and the Two Stage Regulator Adjustment process below 9 Reinstall the plastic regulator cap 10 Mount conversion label on the gas control 11 Install...

Страница 10: ...e same measurement method to calibrate the low stage Two stage appliance operating sequences vary Consult the appliance manufacturer instructions for the specific operating sequence and for instructions on how to prevent the control from moving to high stage while calibrating the low pressure regulator setting 6 With the main burner operating on low fire cali brate the low fire regulator setting u...

Страница 11: ...requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the main burner 2 If the furnace does not come on when the thermostat is set several degrees above room temperature set the thermostat to its lowest setting to reset the safety control 3 Remove the burner access p...

Страница 12: ...rth Golden Valley MN 55422 3992 customer honeywell com U S Registered Trademark 2017 Honeywell International Inc 69 2253 07 M S Rev 04 17 Printed in United States WEEE Directive At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre Do not dispose of with normal household waste Do not burn ...

Отзывы: