68-0046—4

8

Fig. 10—Installing thermocouple to the power
unit.

VR8200, VR4200

INSTALLATION

THERMOCOUPLE 
LEAD

ECO
CONNECTOR

1

THIS IS AN ELECTRICAL CONECTION AND MUST BE
CLEAN AND DRY.  DO NOT USE PIPE COMPOUND.

M3095

1

Fig. 11—Wiring connections for 24 volt control.

L1 
HOT

L2

1

24 V
THERMOSTAT

OPTIONAL
CONVENIENCE
TERMINALS

TH/TR

TH

TR

GAS CONTROL
TERMINALS

HIGH LIMIT
CONTROLLER

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

DO NOT JUMPER THESE TERMINALS.  THIS SHORTS VALVE COIL
AND MAY BURN OUT ANTICIPATOR IN THERMOSTAT.

CONVENIENCE TERMINALS SERVE AS A TIE POINT ONLY. THEY
ARE NOT INTERNALLY WIRED TO THE CONTROL CIRCUIT 
OR TO GROUND.

OPTIONAL HIGH LIMIT.

1

2

3

4

2

3

4

M2915

Fig. 12—Wiring connections for 120 volt
control.

120V 
THERMOSTAT

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

DO NOT JUMPER THESE TERMINALS.  THIS 
SHORTS VALVE COIL AND MAY BURN OUT 
ANTICIPATOR IN THERMOSTAT.

OPTIONAL HIGH LIMIT.

L1
(HOT)

L2

1

HIGH LIMIT 
CONTROLLER

M3092A

GAS CONTROL TERMINALS

L2

L1

2

3

1

2

3

Fig. 9—Always use new compression fitting.

Connect Thermocouple

Connect thermocouple lead as shown in Fig. 10. This

is an electrical connection and must be clean and dry.
Never use pipe compound. Tighten only 1/4 turn beyond
finger tight to give good electrical continuity. Do not
overtighten.

WIRING

Follow the wiring instructions furnished by the appli-

ance manufacturer, if available, or use the general instruc-
tions provided below. Where these instructions differ
from the appliance manufacturer, follow the appliance
manufacturer instructions.

All wiring including 1/4 in. quick-connect terminals,

must comply with applicable electrical codes and ordi-
nances.

Disconnect power supply before making wiring con-

nections to prevent electrical shock or equipment damage.

1. Check the power supply rating on the valve and

make sure it matches the available supply. Install thermo-
stat, and other controls as required.

2. For the VR4200, when the gas control is installed

external to the appliance, install the conduit cover on the
conduit fitting. Do not secure conduit cover at this time.

3. Connect control circuit to gas control terminals. See

Figs. 2, 3 and 11, 12.

NOTE: Use leadwires with insulated terminals.

4. For the VR4200, make sure the conduit cover is in

position and secured to the gas valve with the screw
provided. See Fig. 5.

5. Adjust thermostat heat anticipator as instructed in

the appliance manual (i.e., usually 0.1A for VR4200
and 0.5A for VR8200).

Connect Supplementry Limit or ECO (If Used)

The leadwires from the high limit or ECO must be

equipped with insulated 1/4 in. female quick-connect
terminals. Leadwire lengths must not exceed the lengths
shown in Tables 5 and 6. Connect the high-limit or ECO
leadwires to the two terminals on the ECO connector.

GAS CONTROL BODY

TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT

FITTING BREAKS OFF AND CLINCHES 
TUBING AS NUT IS TIGHTENED

TO  
BURNER

M3076A

Содержание VR4200A

Страница 1: ... be pushed down only in PILOT position All adjustments wiring connections and pilot out let are accessible from the top of the gas control Compact size Straight through body pattern right angle adapters available for inlet and outlet 1 2 in inlet and 1 2 inch outlet adapters available for 3 8 or 3 4 inch Adjustable servo regulator effectively maintains almost constant gas output pressure under wid...

Страница 2: ...n request POWER UNIT Hold in current 300 mA maximum Drop out current 250 to 90 mA THERMOCOUPLE Nominal output 30 mV 0 018 ohms Open Circuit Turndown Voltage 2 mV ELECTRICAL CONNECTIONS 2 1 4 inch male quick connects Two convenience terminals on top of control optional Terminal block color coded beige THERMOSTAT HEAT ANTICIPATOR SETTING VR4200 0 1A VR8200 0 5A TYPE OF GAS VR8200 and VR4200 set up f...

Страница 3: ...as 5 5 as 1 37 as 8 12 2 to 3 ordereda ordereda ordereda ordereda Full Rate Full Rate Full Rate Full Rate 10 2 5 8 to 12 2 to 3 VR8200H Slow Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 VR4200H opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 VR8200J Delayed and Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 Slow opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 a Step pressure not ad...

Страница 4: ...ment damage 2 To avoid dangerous accumulation of fuel gas turnoffgassupplyattheapplianceservicevalve before starting installation and perform Gas Leak Test after completion of installation 3 Do not bend pilot tubing at gas control or pilot burner after compression fitting has been tight ened or gas leakage at the connection may result 4 Always install sediment trap in gas supply line to prevent co...

Страница 5: ...ING TERMINALS 2 INLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW GAS CONTROL KNOB M2916 RED RESET BUTTON THERMOCOUPLE CONNECTION SCREW TERMINALS 2 for LP regulator and 3 5 in wc 0 9 kPa for natural gas regulator 6 Check the regulator setting either with a manometer or by clocking the gas meter Refer to Startup and Check out section 7 In...

Страница 6: ... gas control in the same location as the old gas control Install Piping to Gas Control All piping must comply with local codes and ordi nances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubingisused ensuretheendsaresquare deburredandclean All tubi...

Страница 7: ...ntroluntilitbottoms Whileholdingtubingall the way in slide compression fitting into place and engage threads turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 9 5 Connect the other end of tubing to pilot burner according to pilot burner manufacturer instructions 7 68 0046 4 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to ...

Страница 8: ...ctions furnished by the appli ance manufacturer if available or use the general instruc tions provided below Where these instructions differ from the appliance manufacturer follow the appliance manufacturer instructions All wiring including 1 4 in quick connect terminals must comply with applicable electrical codes and ordi nances Disconnect power supply before making wiring con nections to preven...

Страница 9: ... DEATH 1 Do not force the gas control knob Use only your hand to push down the reset button or turn the gas control knob Never use any tools 2 If the gas control knob or reset button will not operate by hand or if the reset button stays depressed after it is released the gas control should be replaced by a qualified service technician GAS CONTROL KNOB SETTINGS The gas control knob has three settin...

Страница 10: ...t rating stamped on the appliance nameplate or manufacturer recom mended burner orifice pressure for the size orifice s used Assure the main burner primary air supply is properly adjusted for complete combustion refertotheappliancemanufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Assure that the only gas flow through the meter is that of the appliance being tested Assure ...

Страница 11: ... Standard NATURAL 1 2 1 7 0 9 0 7 1 2 Slow LP 2 9 3 9 2 7 2 0 3 0 opening Step NATURAL 1 2 1 7 0 2 0 9 0 7 1 2 opening LP 2 9 3 9 0 9 2 7 2 0 3 0 CHECK SAFETY SHUTDOWN PERFORMANCE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Perform the safety shutdown test any time work is done on a gas system 1 Place gas control knob in PILOT position Main burner should go of...

Страница 12: ...thepilotisburning Theservopressure regulator monitors outlet pressure to provide an even main burner gas flow Loss of power closes the automatic valves butleavesthepilotlit readytoreturntonormalservicewhen power is restored Loss of pilot flame or flame too small to reliably light the main burner closes the safety shutoff valve and the second automatic valve The gas control must be manually reset G...

Страница 13: ... the gas control outlet This decreases gas pressure under the second automatic valve diaphragm and repositions the valve disc further from the seat Thus flow of gas through the second automatic valve is increased and outlet pres sure rises to the desired level Slow Opening Pressure Regulation VR8200H and VR4200H Delayed and Slow opening Regulation VR8200J Slow opening gas controls function the sam...

Страница 14: ... closes and is held closed by spring pressure on the diaphrahm When Pilot Flame Goes Out When pilot flame goes out or is too small to reliably light the main burner thermocouple output drops below the power unit hold in valve The power unit drops out closing the safety valve and stopping all gas flow through the con trol With the loss of outlet pressure the second automatic valve closes and is hel...

Страница 15: ...ot burner flame adjustment Refer to the Adjust the Pilot Burner Flame section 3 Check the wiring between the thermocouple and the gas control valve operator 4 Assure thermocouple connection to the power unit is tightened 1 4 turn beyond finger tight 5 If pilot burner flame still goes out measure the open and closed thermocouple output voltage Compare it to the acceptablerangechartsinthethermocoupl...

Страница 16: ...specific controls used and the procedures outlined by the manufacturer of your appliancemaydiffer andrequirespecialinstructions TO LIGHT THE PILOT BURNER STOP Read the safety information in the WARNING This appliance has a pilot burner which must be lit by hand If the pilot flame has gone out follow these instruc tions exactly 1 Set the thermostat to the lowest setting and shut off electric power ...

Отзывы: