VR8200, VR4200

SERVICE

15

68-0046—4

Service

WARNING

FIRE OR EXPLOSION HAZARD,
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH.
Do not disassemble the gas control; it contains no
replaceable components. Attempted disassembly
or repair may damage the gas control.

CAUTION

Do not apply a jumper across or short the valve coil
terminals. This may burn out the heat anticipator in
the thermostat or damage the DI module.

IMPORTANT: Allow 60 seconds after shutdown before re-

energizing step-opening model to assure lightoff at
step pressure.

IF THE PILOT BURNER FLAME WILL NOT LIGHT

1. Assure the main gas supply valve is open and the

pilot gas supply line is purged of air.

2. Attempt to light pilot burner flame following proce-

dures in the Light the Pilot Burner Flame section. If pilot
burner flame still will not light:

a. Check the pilot gas adjustment screw. If closed, read-

just the pilot flame. Refer to  the Adjust the Pilot
Burner Flame section.

b. Perform the Gas Leak Test at the compression fit-

ting. If a gas leak is detected, replace the old com-
pression fitting or tighten the newly installed one.
Refer to Fig. 9.

c. Assure the pilot burner tubing or pilot burner orifice

is not clogged.

IF THE PILOT BURNER FLAME GOES OUT
WHEN THE GAS CONTROL KNOB IS RELEASED

1. Assure the gas control knob is held in at least one

minute to allow the thermocouple time to heat.

!

2. Check the pilot burner flame adjustment. Refer to  the

Adjust the Pilot Burner Flame section.

3. Check the wiring between the thermocouple and the

gas control valve operator.

4. Assure thermocouple connection to the power unit is

tightened 1/4 turn beyond finger tight.

5. If pilot burner flame still goes out, measure the open

and closed thermocouple output voltage. Compare it to the
acceptable range charts in the thermocouple specifications or
in the Gas Controls Handbook. Replace the thermocouple if
voltages are outside the acceptable range.

6. Check the power unit resistance. If above 11 ohms,

replace the gas control.

IF THE MAIN BURNER WILL NOT COME ON
WITH A CALL FOR HEAT

1. Assure the gas control knob is in the ON position.
2. Adjust the thermostat several degrees above room

temperature.

3. Use an ac voltmeter to measure the voltage across

terminals TH and TR. If:

a. No voltage is present, check the control circuit for

proper operation.

b. Correct voltage (VR8200, 24 Vac; VR4200, 120 Vac)

is present, but first operator did not click open, check
for excessive inlet gas pressure. If inlet gas pressure
is correct, replace the gas control.

4. Measure the open and closed thermocouple output

voltages and compare to the acceptable range charts in the
thermocouple specifications or in the Gas Controls Hand-
book. Replace the thermocouple if voltages are outside the
acceptable range.

IF THE MAIN BURNER IS OVERFIRING

Adjust the gas control pressure regulator to the correct

pressure. If the regulator cannot be adjusted and supply
pressure is in the normal range, replace the gas control.

!

Содержание VR4200A

Страница 1: ... be pushed down only in PILOT position All adjustments wiring connections and pilot out let are accessible from the top of the gas control Compact size Straight through body pattern right angle adapters available for inlet and outlet 1 2 in inlet and 1 2 inch outlet adapters available for 3 8 or 3 4 inch Adjustable servo regulator effectively maintains almost constant gas output pressure under wid...

Страница 2: ...n request POWER UNIT Hold in current 300 mA maximum Drop out current 250 to 90 mA THERMOCOUPLE Nominal output 30 mV 0 018 ohms Open Circuit Turndown Voltage 2 mV ELECTRICAL CONNECTIONS 2 1 4 inch male quick connects Two convenience terminals on top of control optional Terminal block color coded beige THERMOSTAT HEAT ANTICIPATOR SETTING VR4200 0 1A VR8200 0 5A TYPE OF GAS VR8200 and VR4200 set up f...

Страница 3: ...as 5 5 as 1 37 as 8 12 2 to 3 ordereda ordereda ordereda ordereda Full Rate Full Rate Full Rate Full Rate 10 2 5 8 to 12 2 to 3 VR8200H Slow Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 VR4200H opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 VR8200J Delayed and Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 Slow opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 a Step pressure not ad...

Страница 4: ...ment damage 2 To avoid dangerous accumulation of fuel gas turnoffgassupplyattheapplianceservicevalve before starting installation and perform Gas Leak Test after completion of installation 3 Do not bend pilot tubing at gas control or pilot burner after compression fitting has been tight ened or gas leakage at the connection may result 4 Always install sediment trap in gas supply line to prevent co...

Страница 5: ...ING TERMINALS 2 INLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW GAS CONTROL KNOB M2916 RED RESET BUTTON THERMOCOUPLE CONNECTION SCREW TERMINALS 2 for LP regulator and 3 5 in wc 0 9 kPa for natural gas regulator 6 Check the regulator setting either with a manometer or by clocking the gas meter Refer to Startup and Check out section 7 In...

Страница 6: ... gas control in the same location as the old gas control Install Piping to Gas Control All piping must comply with local codes and ordi nances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubingisused ensuretheendsaresquare deburredandclean All tubi...

Страница 7: ...ntroluntilitbottoms Whileholdingtubingall the way in slide compression fitting into place and engage threads turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 9 5 Connect the other end of tubing to pilot burner according to pilot burner manufacturer instructions 7 68 0046 4 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to ...

Страница 8: ...ctions furnished by the appli ance manufacturer if available or use the general instruc tions provided below Where these instructions differ from the appliance manufacturer follow the appliance manufacturer instructions All wiring including 1 4 in quick connect terminals must comply with applicable electrical codes and ordi nances Disconnect power supply before making wiring con nections to preven...

Страница 9: ... DEATH 1 Do not force the gas control knob Use only your hand to push down the reset button or turn the gas control knob Never use any tools 2 If the gas control knob or reset button will not operate by hand or if the reset button stays depressed after it is released the gas control should be replaced by a qualified service technician GAS CONTROL KNOB SETTINGS The gas control knob has three settin...

Страница 10: ...t rating stamped on the appliance nameplate or manufacturer recom mended burner orifice pressure for the size orifice s used Assure the main burner primary air supply is properly adjusted for complete combustion refertotheappliancemanufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Assure that the only gas flow through the meter is that of the appliance being tested Assure ...

Страница 11: ... Standard NATURAL 1 2 1 7 0 9 0 7 1 2 Slow LP 2 9 3 9 2 7 2 0 3 0 opening Step NATURAL 1 2 1 7 0 2 0 9 0 7 1 2 opening LP 2 9 3 9 0 9 2 7 2 0 3 0 CHECK SAFETY SHUTDOWN PERFORMANCE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Perform the safety shutdown test any time work is done on a gas system 1 Place gas control knob in PILOT position Main burner should go of...

Страница 12: ...thepilotisburning Theservopressure regulator monitors outlet pressure to provide an even main burner gas flow Loss of power closes the automatic valves butleavesthepilotlit readytoreturntonormalservicewhen power is restored Loss of pilot flame or flame too small to reliably light the main burner closes the safety shutoff valve and the second automatic valve The gas control must be manually reset G...

Страница 13: ... the gas control outlet This decreases gas pressure under the second automatic valve diaphragm and repositions the valve disc further from the seat Thus flow of gas through the second automatic valve is increased and outlet pres sure rises to the desired level Slow Opening Pressure Regulation VR8200H and VR4200H Delayed and Slow opening Regulation VR8200J Slow opening gas controls function the sam...

Страница 14: ... closes and is held closed by spring pressure on the diaphrahm When Pilot Flame Goes Out When pilot flame goes out or is too small to reliably light the main burner thermocouple output drops below the power unit hold in valve The power unit drops out closing the safety valve and stopping all gas flow through the con trol With the loss of outlet pressure the second automatic valve closes and is hel...

Страница 15: ...ot burner flame adjustment Refer to the Adjust the Pilot Burner Flame section 3 Check the wiring between the thermocouple and the gas control valve operator 4 Assure thermocouple connection to the power unit is tightened 1 4 turn beyond finger tight 5 If pilot burner flame still goes out measure the open and closed thermocouple output voltage Compare it to the acceptablerangechartsinthethermocoupl...

Страница 16: ...specific controls used and the procedures outlined by the manufacturer of your appliancemaydiffer andrequirespecialinstructions TO LIGHT THE PILOT BURNER STOP Read the safety information in the WARNING This appliance has a pilot burner which must be lit by hand If the pilot flame has gone out follow these instruc tions exactly 1 Set the thermostat to the lowest setting and shut off electric power ...

Отзывы: