Honeywell VPI Series Скачать руководство пользователя страница 4

VPI Pressure Independent Control Valves & Actuators 

31-00383-01 

 

Flow Setting Chart for DN 15 -32 

Table 1. Flow Chart for DN15-32 

DN15LF-DN20LF 

DN15HF-DN25HF 

DN32 

Setting 

l/sec

 

l/hr

 

GPM

 

l/sec

 

l/hr

 

GPM

 

l/sec

 

l/hr

 

GPM

 

0.0178 

64 

0.282 

0.240 

865 

3.81 

1.0 

0.0393 

142 

0.624 

0.282 

1010 

4.46 

1.1 

0.0580 

209 

0.920 

0.322 

1160 

5.10 

1.2 

0.0743 

268 

1.180 

0.361 

1300 

5.72 

1.3 

0.0887 

319 

1.41 

0.399 

1430 

6.32 

1.4 

0.102 

366 

1.61 

0.172 

620 

2.73 

0.435 

1570 

6.90 

1.5 

0.113 

408 

1.80 

0.200 

720 

3.17 

0.471 

1700 

7.47 

1.6 

0.124 

446 

1.96 

0.228 

820 

3.61 

0.506 

1820 

8.02 

1.7 

0.134 

482 

2.12 

0.258 

930 

4.10 

0.540 

1940 

8.56 

1.8 

0.143 

516 

2.27 

0.294 

1060 

4.67 

0.573 

2060 

9.08 

1.9 

0.152 

549 

2.42 

0.325 

1170 

5.15 

0.605 

2180 

9.59 

2.0 

0.161 

580 

2.56 

0.350 

1260 

5.55 

0.636 

2290 

10.1 

2.1 

0.170 

611 

2.69 

0.375 

1350 

5.95 

0.667 

2400 

10.6 

2.2 

0.178 

641 

2.82 

0.396 

1430 

6.28 

0.696 

2510 

11.0 

2.3 

0.186 

671 

2.95 

0.417 

1500 

6.61 

0.725 

2610 

11.5 

2.4 

0.194 

700 

3.08 

0.439 

1580 

6.96 

0.753 

2710 

11.9 

2.5 

0.202 

728 

3.21 

0.458 

1650 

7.27 

0.780 

2810 

12.4 

2.6 

0.210 

756 

3.33 

0.481 

1730 

7.62 

0.807 

2900 

12.8 

2.7 

0.218 

783 

3.45 

0.500 

1800 

7.93 

0.832 

3000 

13.2 

2.8 

0.225 

810 

3.56 

0.522 

1880 

8.28 

0.858 

3090 

13.6 

2.9 

0.232 

835 

3.68 

0.542 

1950 

8.59 

0.882 

3180 

14.0 

3.0 

0.239 

860 

3.79 

0.550 

1980 

8.72 

0.906 

3260 

14.4 

3.1 

0.245 

883 

3.89 

0.558 

2010 

8.85 

0.930 

3350 

14.7 

3.2 

0.252 

906 

3.99 

0.567 

2040 

8.99 

0.953 

3430 

15.1 

3.3 

0.257 

927 

4.08 

0.575 

2070 

9.12 

0.975 

3510 

15.5 

3.4 

0.263 

946 

4.17 

0.583 

2100 

9.25 

0.997 

3590 

15.8 

3.5 

0.268 

965 

4.25 

0.597 

2150 

9.47 

1.02 

3670 

16.1 

3.6 

 
 

 

Содержание VPI Series

Страница 1: ...hot water closed loop applications only with a media temperature range of 20ºC to 120ºC 4ºF to 248ºF and static pressures up to 580psi Not suitable for oil combustible gases or high temperature steam These valves are to be operated with the appropriate and compatible Honeywell actuators only Refer VPI series PICV Product Datasheets for more details on valve and actuators compatibility Water should...

Страница 2: ...lean the lines upstream of particles larger than 1 16 inch diameter welding slag pipe scale sand and other suspended particulate Do not use boiler additives solder flux and wetted materials which are petroleum based or contain mineral oil hydrocarbons or ethylene glycol acetate Compounds that can be used with a minimum 50 water dilution are diethylene glycol ethylene glycol and propylene glycol an...

Страница 3: ...sary pull or twist in the valve housing 5 Install the valve housing with the flow directional arrow pointing in the correct direction 6 For threaded connections please clear threads on both valve and piping of debris Honeywell recommends thread or pipe sealant Permabond A1044 or equivalent When using Teflon tape it is recommended to use 4 6 rounds of tape applied tightly in clockwise rotation When...

Страница 4: ... 2 42 0 325 1170 5 15 0 605 2180 9 59 2 0 0 161 580 2 56 0 350 1260 5 55 0 636 2290 10 1 2 1 0 170 611 2 69 0 375 1350 5 95 0 667 2400 10 6 2 2 0 178 641 2 82 0 396 1430 6 28 0 696 2510 11 0 2 3 0 186 671 2 95 0 417 1500 6 61 0 725 2610 11 5 2 4 0 194 700 3 08 0 439 1580 6 96 0 753 2710 11 9 2 5 0 202 728 3 21 0 458 1650 7 27 0 780 2810 12 4 2 6 0 210 756 3 33 0 481 1730 7 62 0 807 2900 12 8 2 7 0...

Страница 5: ...he valve body See Figure 5 Figure 5 Removing Flow regulator from Valve body Procedure to install the Flow Regulator The procedure to install Flow Regulator is as follows 1 Prior to installing the Flow regulator the system should be properly flushed 2 Insert the Flow Regulator in valve body and rotate with the pipe wrench or appropriate tool in Clockwise direction to fit flow regulator in valve bod...

Страница 6: ...ody regulates flow IMPORTANT Do not disassemble or attempt to remove the Flow regulator from the valve body Doing so may damage the valve and will void warranty Pressure ports C facilitates user to gauge pressure across ends The Plugs D comes with valve models without pressure ports See VPI series PICV Product Datasheets for more details on models with and without pressure ports Figure 6 DN40 50 V...

Страница 7: ... The procedure for scale setting is as follows 1 Set the desired flow rate by adjusting scale setting of the dial with a special adjustment key Figure 7 Flow setting for DN 40 50 2 For DN40 50 large white digits numbered 1 to 5 including in between positions showed by dots one dot for every 0 1 positions The specific position is defined by a sign mark on top of the housing Figure 8 Dial Gauge for ...

Страница 8: ... 67 6011 26 4 2 1 1 77 6372 28 0 2 2 1 87 6730 29 6 2 3 1 97 7083 31 2 2 4 2 06 7432 32 7 2 5 2 16 7776 34 2 2 6 2 25 8115 35 7 2 7 2 35 8449 37 2 2 8 2 44 8777 38 6 2 9 2 53 9098 40 0 3 0 2 61 9413 41 4 3 1 2 70 9721 42 8 3 2 2 78 10021 44 1 3 3 2 86 10314 45 4 3 4 2 94 10599 46 6 3 5 3 02 10875 47 8 3 6 3 10 11142 49 0 3 7 3 17 11400 50 2 3 8 3 24 11649 51 3 3 9 3 30 11888 52 3 4 0 3 37 12116 53...

Страница 9: ...n 5 Valves must be installed avoiding unnecessary pull or twist in the valve housing 6 For flanged connections make sure if both flange surfaces are clear 7 Flange ends are compatible with DIN steel flanges PN10 PN16 PN25 and or PN40 according to EN1092 1 or ANSI steel flanges class 150 and or 300 according to ASME B16 5 depending on the product ordered Flanges are not supplied by Honeywell See VP...

Страница 10: ... 42000 185 14 3 51600 227 5 63 20300 89 2 5 63 20300 89 2 7 52 27100 119 11 9 42700 188 11 9 42700 188 14 7 53000 233 5 70 20500 90 4 5 70 20500 90 4 7 63 27500 121 12 0 43400 191 12 0 43400 191 15 1 54300 239 5 77 20800 91 5 5 77 20800 91 5 7 74 27900 123 12 2 43900 194 12 2 43900 194 15 4 55600 245 5 84 21000 92 5 5 84 21000 92 5 7 84 28200 124 12 4 44500 196 12 4 44500 196 15 8 56800 250 5 90 2...

Страница 11: ... 53100 234 17 2 62100 273 17 2 62100 273 19 0 68400 301 66 4 239000 1050 15 3 54900 242 17 8 64200 283 17 8 64200 283 20 0 71900 317 66 9 241000 1060 15 7 56600 249 18 4 66300 292 18 4 66300 292 21 0 75600 333 67 4 243000 1070 16 2 58300 257 19 0 68300 301 19 0 68300 301 22 0 79300 349 68 0 245000 1080 16 6 59900 264 19 5 70200 309 19 5 70200 309 23 1 83100 366 68 4 246000 1080 17 1 61500 271 20 0...

Страница 12: ...VPI Pressure Independent Control Valves Actuators 31 00383 01 8 Control Curve of Flow Figure 11 Control curve of flow from MR series actuators ...

Страница 13: ...w Figure 12 Assembly direction of an actuator on valve example 3 Tighten the connection union as shown below Do not use additional tools as it may damage the actuator Mounting Position The actuators can be mounted in any position IP54 is dependent upon orientation see Figure 13 Choose a mounting position permitting easy access to cables and controls To guarantee IP54 upside down installation is on...

Страница 14: ...e MLP71TNA comes with plug in cable Make sure that the cable is properly fitted next 4 The actuator can now be fitted on the adaptor ring A click noise will indicate that the actuator is correctly fitted as shown below Figure 14 Installation of thermoelectric actuator on valve example Mounting Position The actuators can be mounted in any position IP54 is dependent upon orientation see Figure 15 Ch...

Страница 15: ...rns the snap ring counterclockwise upside view approximately 1 6 of a turn until its stop points touch the actuator legs and the mounting is a lock with a small click Do not use additional tools Figure 16 Actuator Assembly for DN 50 250 Mounting Position The actuators can be mounted in any position IP54 is dependent upon orientation see Figure 17 Choose a mounting position permitting easy access t...

Страница 16: ...LLATIONS Electrical Wiring for Actuators Compatible to DN15 50 The most important part of the electrical installation is the appropriate wiring set up as per application Below are examples of electrical wiring provided as per the actuator model MLP71MAA Actuators MLP41MNA Actuators ...

Страница 17: ... OFF to ON Auto Cycle is activated The actuator will then perform a 50 stroke cycle every 3 weeks if no stroke movement has occurred Electrical Override By moving DIP switch 6 from OFF to ON electrical override is activated and the actuator will open the valve fully During an electrical override the LED indicator will blink red and green When DIP switch 6 is moved back to OFF the actuator will re ...

Страница 18: ...ioning It prevents the valve from jamming when the valve is not moved for a longer period of inactivity By moving DIP switch 1 from OFF to ON Auto Cycle is activated Actuator will then perform 50 stroke cycle every 3 weeks if no stroke movement has occurred Re Calibration MLP75MAB By flipping DIP switch 6 from one setting to the other starting position indifferent re calibration is activated After...

Страница 19: ... final position until return of power Upon power the actuator remains in the final failsafe position until charging mode is reached max 15 sec Hereafter the actuator will return to normal operation mode MLP41TNA and MLP71TNA Thermoelectric Actuators 24V versions must be powered by a safety isolating transformer for AC variant according to EN 61558 2 6 or class II FCC quality proofed or a switching...

Страница 20: ...safe actuators MLE71MAA and MLE75MAB Switch number Switch Function On Off Factory Settings Switch 6 Electrical override ON Electrical override OFF Off Switch 5 No function Normally Closed Switch 4 Equal control Linear control Linear control Switch 3 Normally open Normally close Normally closed 0V DC valve closed Switch 2 Analog 2 10V DC Analog 0 10V DC 0 10V DC Switch 1 Autocycle ON Autocycle OFF ...

Страница 21: ...e Codes Honeywell Part codes Reference Valve Codes VPI050FPH4 50H VPI065FPH4 65H VPI080FPL4 80L VPI080FPH4 80H VPI100FPL4 100L VPI100FPH4 100H VPI125FPL4 125L VPI125FPH4 125H VPI150FPL4 150L VPI150FPH4 150H VPI200FPH4 200H VPI250FPH4 250H While setting up the reference code on the valve please select the reference code on the actuator to get the maximum flow settings ...

Страница 22: ...ng menu simultaneously press and for 6 seconds until the bottom line in display blinks To change a value press or For quick scroll through values hold down or Press to accept a value and go to the next step and press to go to the previous step For fast menu exit press and simultaneously for 6 seconds The actuator will automatically return to normal operation mode if no action is detected on arrow ...

Страница 23: ...nd at least 6 mA greater than the selected minimum limit Increment 0 2 NA if Digital in step 5 8 select feedback signal scrolling top SELECT FEEDBACK SIGNAL Default AU Automatic match of control signal if analog Options 0 10 VDC 2 10 VDC or 4 20 mA or AU If Digital in step 5 AU is not an option 9 Set the designed maximum flow Accuracy Greatest of either 5 of de signed max flow or 2 of max valve fl...

Страница 24: ...DE 01 Use to go to next information line and to go to the previous Table 8 List of information from upper part of display during operation Information Meaning Options Controlsignal Indicates valueof controlsignal 0 10VDCor0 20mAorOpen Stop Close Feedback signal Indicates value of feedback signal 0 10 VDC or 0 20 mA Valve Indicates valve model 50H 65H 80L See Table 5 List of Reference Valve Codes f...

Страница 25: ...n Details 01 FULL ON Valve actuator is over torqued Operation is stopped Actuator will retry operation every 02 BLINKING Actuator has reached its torque limit in the past Actuator is functioning To reset the alarm simultaneously press and for 6 seconds 03 FULL ON Critical over temperature Critical Temperature in actuator is at least 70ºC motor operation is stopped If temperature is decreasing oper...

Страница 26: ... Turn the valve spindle clockwise to close valve and counterclockwise to open Re mount the actuator and connect power Be aware to protect that actuator from water while not on the valve NOTE When manually operating the vale actuator disconnected do not use more than 10 Nm torque Use of higher torque will void warranty Failsafe Mode for DN 50 250 In case of power failure failsafe models will move a...

Страница 27: ... 800 103 0339 Email HBTIndiabuildings honeywell com ASEAN Honeywell Building Technologies ASEAN Honeywell International Sdn Bhd Level 25 UOA Corp Tower Lobby B Avenue 10 The Vertical Bangsar South City 59200 Kuala Lumpur Malaysia Call 60 3 2777 3100 Email buildings asean honeywell com PACIFIC Honeywell 2 Richardson Pl North Ryde NSW 2113 Australia Call 1300 363 936 Email pacificustomercare honeywe...