VPI Pressure Independent Control Valves & Actuators
31-00383-01
18
Configuration and Setup
Start-Up Sequence
When power is turned on, the actuator will automatically calibrate to determine the closing point of the valve.
Calibrati
on can take up to 10 minutes depending on the valve’s position at start
-up. During the calibration actuator,
the display will show “CAL”. Hereafter it will proceed to the normal operation mode (according to control signal).
If no control signal is detected, flush is started if enabled in the programming menu (enabled by default), opening the
valve to 5/6 of fully open. Actuator display will show “FLUSH” until control signal is detected.
At first start-up please enter programming menu to set actuator settings.
Programming Menu
Figure 19. Typical display of MR series actuators
The programming menu is always accessible. To enter the programming menu, simultaneously press
and
for 6
seconds, until the bottom line in display blinks.
To change a value, press
, or
. For quick scroll through values hold down
or
. Press
to accept a value and go
to the next step and press
to go to the previous step.
For fast menu exit press
and
simultaneously for 6 seconds. The actuator will automatically return to normal
operation mode if no action is detected on arrow keys for 1 minute.
NOTE
- All values selected in the programming menu are stored in non-volatile memory
Table 6. List of Programming menus
Step
Display
Description
Valve
0
Password
.
*
scrolling top:
ENTER PASSWORD
Disabled by default
Password: 3569266.
Only if Enabled (in step 12).
Change one digit at a time, press
and to move
between digits.
At last digit, press
to go to next step
1
Select language
*scrolling top:
SELECT LANGUAGE
Default: English
.
2
Select valve model onto which the
actuator is installed.
*scrolling top:
SELECT VALVE MODEL
Default: 50H.
Select from the 12 available valve models.
Options: 50H, 65H, 80L