VISIONPRO® 8000 SMART THERMOSTAT
33-00096—04
90
TROUBLESHOOTING
Table 10. Troubleshooting.
Symptom
Action
Screen is blank
•
Check circuit breaker and reset if necessary.
•
Make sure power switch at heating and cooling system is on.
•
Make sure furnace door is closed securely.
Screen is
difficult to read
•
Change screen brightness using Preferences menu.
Red light is on
•
If thermostat is in Emergency Heat mode, the red light is normal. It shows that the thermostat is in
Emergency Heat mode.
•
If thermostat is not in Emergency Heat mode, an alert is active. Check message on the thermostat
screen.
Heating or
cooling system
does not
respond
•
Touch SYSTEM to set system to Heat. Make sure the temperature is set higher than the Inside
temperature.
•
Touch SYSTEM to set system to Cool. Make sure the temperature is set lower than the Inside
temperature.
•
Check circuit breaker and reset if necessary.
•
Make sure power switch at heating & cooling system is on.
•
Make sure furnace door is closed securely.
•
If “Wait” is displayed, the compressor protection timer is on. Wait 5 minutes for the system to restart
safely, without damaging the compressor.