VISIONPRO® 8000 SMART THERMOSTAT
17
33-00096—04
306
Compressor Heat
Diff. Stage 1
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort
Both
ISU 301 Control Options must be set to Advanced to
view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Geothermal Radiant and ISU 205 Geo
Forced Air is set to Heating and Cooling.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn on
the stage of heating. For example, if stage 1 is set to
2° F (1.0° C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before stage 1 turns
on. When set to Comfort, the thermostat will use the
stage of heating as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
306
Compressor Heat
Diff. Stage 2
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort
Both
ISU 301 Control Options must be set to Advanced to
view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Air to Air Heat Pump, Geothermal or
Geothermal Radiant and there are 2 compressor
stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn on
the stage of heating. For example, if stage 2 is set to
2° F (1.0° C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat will use the
stage of heating as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
308,
309
Backup Heat Droop
Stage 1
Note: “Stage 1" is
not displayed if
there is only 1 stage
of Backup Heat.
Comfort
2.0° F to 15.0° F from setpoint
(in 0.5° F increments)
Comfort
Both
A backup heat droop can be set on any system that
has more than one heating equipment type.
See “Backup Heat Droop” beginning on page 53.
The Comfort setting is NOT available for Dual Fuel
systems. For example, Heat Pumps with Gas Forced
Air.
308,
309
Backup Heat Droop
Stage 2
Comfort
2.0° F to 15.5° F from setpoint
(in 0.5° F increments)
Comfort
Both
ISU 301 Control Options must be set to Advanced to
view or adjust Backup Heat Droop Stage 2.
This ISU is only displayed if there are 2 backup heat
stages.
The indoor temperature must drop to the selected
droop setting before the thermostat will turn on
backup heat stage 2. For example, if backup heat
stage 2 is set to 2° F (1.0° C), the indoor temperature
must be 2° F (1.0° C) away from the setpoint before
backup heat stage 2 turns on. When set to Comfort,
the thermostat will use backup heat stage 2 as
needed to keep the indoor temperature within 1° F
(0.5° C) degree of the setpoint.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Notes