VISIONPRO® 8000 SMART THERMOSTAT
27
33-00096—04
411
Keypad Lockout
Unlocked
Partially Locked
Fully Locked
Unlocked
Both
Unlocked: User has access to all thermostat settings.
Partially Locked: User can modify only temperature
settings.
Fully Locked: User cannot modify any settings.
500
Wired Sensor on S
Terminals
No
Yes
No
Both
This ISU is only displayed if ISU 106 was configured
to Wired/Internet.
Select Yes if a wired indoor, outdoor, or discharge
sensor is wired to S1.
500
Wired Remote
Indoor Sensor
No
Yes
No
Both
Select Yes if a wired indoor sensor is wired to S1.
500
Wired Outdoor
Sensor
No
Yes
No
Both
Select Yes if a wired outdoor sensor is wired to S1.
500
Wired Discharge
Sensor
No
Yes
No
Both
Select Yes if a wired discharge sensor is wired to S1
501
Indoor Sensor
Name
[Select Indoor Sensor Name]
Indoor Sensor
Both
Select a name (location) of the Wired Remote Indoor
Sensor.
502
Indoor Sensor
S1
Both
Confirms type of sensor wired to S1.
503
Indoor Sensor Type
10K
20K
10K:
if ISU 101 Application
is Residential
20K:
if ISU 101: Application
is Commercial
Both
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A must
be used in combination with a TR21 sensor or
another TR21-A sensor for the thermostat to
calculate the correct indoor temperature reading).
See “Wiring guide — Wired Indoor Sensors”
beginning on page 89 for information on the sensor
type you should select based on how the sensors are
wired. For example, you would select 20K when you
have two TR21-A (10K) sensors wired in series.
504
Use [T-Stat Sensor]
for Temp Ctrl
Use T-Stat Sensor for Temp Ctrl -
Yes or No
Sensors are Averaged
(T-Stat Sensor and
Remote)
Both
Only displayed when a wired indoor sensor is
configured. Select Yes if you want the thermostat to
average with wired indoor sensor. Select No if you
want to sense temperature only at the wired sensor.
505
Outdoor Sensor
S1
Both
Confirms type of sensor wired to S1.
509
Discharge Sensor
S1
Both
Confirms type of sensor wired to S1.
510
Discharge Sensor
Type
10K
20K
10K
Both
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
511
A-Coil Low Temp.
Cutoff
Off
35° F to 65° F (in 5° F
increments)
Off
Both
If an optional Discharge Sensor is used, this feature
can help prevent icing on the air conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to a safe
level.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Notes