4.4 Grounding and equipotential bonding
For compact versions and measuring devices with flange connections, the flow sensor is
conductively connected to the pipeline.
For compact versions and measuring device of the type "sandwich", a separate conductor
connected either to the internal or external PA terminal must be provided to connect to the
equipotential bonding.
CAUTION!
Equipotential bonding
Equipotential bonding
Equipotential bonding
Equipotential bonding
Vortex signal converters and flow sensors must be included in the on-site equipotential bonding
system according to the installation standard! They are connected to the PA terminals.
Figure 4-1: Ground connection of the compact version
1
Electrical grounding connection on connection piece between the flow sensor and the signal converter
2
Electrical grounding terminal in the housing