3.2 Special conditions
Flameproof joints in the housing
The housing must be replaced if there is any damage to the joint area. The flameproof thread
gaps and the cylindrical joint between the terminal and the electronics compartments must be
inspected visually after opening.
Electrostatics
For painted versions, risks due to electrostatic charge must be minimized.
For further information refer to
Electrostatic charge
on page 28.
Thermal and electrical data
Observe the maximum ambient and product temperatures and electrical data. For further
information refer to
Ambient temperature / temperature classes
on page 9 and refer to
Surface
temperature for equipment protection level Db
on page 17 and refer to
Electrical data
on page
17.
WARNING!
Repairs of the flameproof joints are not allowed.