Honeywell VC Series Скачать руководство пользователя страница 3

MU1H-2806GE23 R0107

4

Honeywell GmbH

GB

1. Application

The VC series 2-position hydronic valves are used in 

domestic and small commercial applications to control 

the flow of hot and/or cold water or  glycol solution to 

50% concentration. They consist of an actuator, valve 

and a replaceable cartrige assembly.

These 3-Way valves are designed for ON-OFF control 

and can be piped for either diverting or mixing valve 

applications for domestic hot water service, in central 

heating and/or cooling systems; or for individual room 

temperature control (fan coil, radiator or convector 

applications).

Depending on the model selected, they can be cont-

rolled by either a low or line voltage SPST  

 or 

SPDT  

 controller, such as a room thermostat, 

a chronotherm or other suitable two-position controller.

2. Specifications

The following specifications are nominal and conform to generally accepted industry standards. Honeywell is not 

responsible for damages resulting from misapplication or misuse of its product.

Voltage

230V 50-60Hz, standard models. 24V 50-60Hz models are available on 

request

Power Consumption

6 Watts Max. at nominal Voltage (during valve position change). 

Use 24 V class 2 transformer. Provide 6 VA for transformer and connection 

wire size.

Maximum duty Cycle 

15 %

End switch rating 

2.2 A inductive from 5 to 110 Vac,

1.0 A inductive above 110 to 277 Vac.

Min. DC switching capability: 5 mA @ 24 Vdc

Nominal timing 

Valve opens in  7 seconds 

 50 Hz (20% faster 

 60 Hz)

Electrical termination 

With integral 1 meter leadwire cable or with Molex™ connector

Operating ambient temperature 

0...65°C 

Shipping & storage temperature 

-40...+65°C

Atmosphere

non-corrosive, non-explosive

Min. & max. fluid temperatures 

1...95°C

Operating pressure differential 

Max. -  4 bar (400 kPa)

Pressure rating 

Static -   20 bar (2000 kPa)

Burst - 100 bar

Valve materials 

Body of bronze; cartridge of Ryton™  (polyphenylene sulphide) & Noryl™ 

(polyphenylene oxide); O-ring seals of EPDM rubber; stainless steel stem

Insulation class 

Double insulation

Protection class 

IP40

Approval

CE

C

D

98

136

94

130

94

130

94

136

94

136

Fig. 1: Dimensions (mm)

Fig. 2: Flow direction

Open

B-AB

Open

A-AB

Port A normally closed without actuator

Содержание VC Series

Страница 1: ...VC Series Installation instruction Einbauanleitung Keep instructions for later use Anleitung zum späteren Gebrauch aufbewahren 3 Way Zone Valves 3 Wege Zonenventile MU1H 2806GE25 R0107 ...

Страница 2: ...ell com GB 1 Application 4 2 Specifications 4 3 Manual Opener 5 4 Installation 5 5 Wiring 6 6 Checkout and service 7 D 1 Anwendungsbereich 8 2 Spezifikationen 8 3 Handöffner 9 4 Einbau 9 5 Verdrahtung 10 6 Probebetrieb und Wartung 11 ...

Страница 3: ...suse of its product Voltage 230V 50 60Hz standard models 24V 50 60Hz models are available on request Power Consumption 6 Watts Max at nominal Voltage during valve position change Use 24 V class 2 transformer Provide 6 VA for transformer and connection wire size Maximum duty Cycle 15 End switch rating 2 2 A inductive from 5 to 110 Vac 1 0 A inductive above 110 to 277 Vac Min DC switching capability...

Страница 4: ...ly latched to the valve To remove Fig 4 press up on the latch mecha nism 1 located directly below the white manual open lever with thumb Simultaneously press the actuator down towards the body with moderate hand force and turn the actuator counter clockwise by 1 8 turn 45 degrees Lift actuator off the valve body 3 The valve may be installed with flow from A to B or B to A Fig 2 The valve body may ...

Страница 5: ...f the Port A opening stroke On Molex connector models valve auxiliary switch voltage must be the same to meet approval require ment Fig 3 Valve mounting position Fig 4 Removing the actuator Fig 5 Valve mounting Fig 6 The manual opener X A B Manual opener WARNING Electrical installation cables and related accessories must comply with local laws directives and competent authorities Table 1 Electrica...

Страница 6: ...one thermostat above room temperature to initiate a call for heat White valve position lever should move 2 For auxiliary switch models observe all control devices The valve should open and the auxiliary switch if present should close and make at the end of the opening stroke to activate auxiliary equip ment 3 Lower the set point of the zone thermostat below room temperature 4 Observe the control d...

Страница 7: ...en die durch falsche Verwendung oder Zweckentfremdung seiner Produkte entstehen Spannung 230V 50 60Hz Standardmodelle Modelle mit 24V 50 60Hz sind auf Anfrage erhältlich Leistungsaufnahme Max 6 Watt bei Nennspannung bei Wechsel der Ventilspannung Transformator 24 V Klasse 2 verwenden 6 VA für Transformator und Anschlusskabelgröße vorsehen Maximales Schaltverhältnis 15 Endschalterbelastung 2 2 A in...

Страница 8: ... Der entsprechende Hebel befindet sich direkt unterhalb des Hebels zur Handöffnung Gleichzeitig muss das Stellglied mit moderater Kraft nach unten auf den Ventilkörper gedrückt und im entgegengesetzten Uhrzeigersinn um 1 8 gedreht werden 45 Grad Dann kann das Stellglied vom Ventilkörper abgehoben werden 3 Das Ventil kann mit der Flussrichtung A nach B oder B nach A eingebaut werden Abb 2 Der Venti...

Страница 9: ...Anschluss muss die Spannung an Ventil und Hilfsschalter identisch sein um die Zulas sung zu erhalten Fig 3 Lage des Ventils Fig 4 Entfernung des Stellglieds Fig 5 Einbau des Ventils Fig 6 Manuelle Öffnung X A B Manual opener WARNUNG Elektrische Installationen Kabel und Zu satzbauteile müssen örtlichen Gesetzen Richtlinien und behördlichen Vorschriften entsprechen Table 1 Elektrische Anschlüsse Far...

Страница 10: ...bewegen 2 Bei Modellen mit Hilfsschalter müssen alle Regelein richtungen beobachtet werden Das Ventil sollte sich öffenen und der Hilfsschalter wenn vorhanden sollte sich am Ende des Öffnungsvorgangs schließen um die Hilfseinrichtungen zu aktivieren 3 Stellen Sie den Sollwert des Zonenthermostats auf einen Wert unterhalb der Raumtemperatur 4 Beobachten Sie die Regeleinrichtungen Anschluss A sollte...