V8200A,C,H,M AND VR8200A,C,H,M CONTINUOUS PILOT COMBINATION GAS CONTROLS

69-0422—03

6

Turn On Main Burner

Follow instructions provided by appliance manufacturer or 
turn thermostat up to call for heat.

Adjust Pilot Flame

The pilot flame should envelop 3/8 to 1/2 in. 
(10 to 13 mm) of the tip of the thermocouple. Refer to 
Fig. 9.

1.

Remove pilot adjustment cover screw. 
Refer to Fig. 4.

2.

Turn inner adjustment screw clockwise 

 to 

decrease or counterclockwise 

 to increase 

pilot flame.

3.

Always replace cover screw after adjustment. 
Tighten firmly to prevent gas leakage.

Fig. 9. Proper Flame Adjustment.

CAUTION

Check and Adjust Gas Input to Main Burner 

1. Do not exceed input rating stamped on 

appliance nameplate, or manufacturer's 
recommended burner orifice pressure for size 
orifice(s) used. Make certain primary air supply 
to main burner is properly adjusted for complete 
combustion. Follow appliance manufacturer's 
instructions.

2. IF CHECKING GAS INPUT BY CLOCKING 

GAS METER: Make certain there is no gas flow 
through the meter other than to the appliance 
being checked. Other appliances must remain 
off with their pilots extinguished (or their 
consumption must be deducted from the meter 
reading). Convert flow rate to Btuh as described 
in form 70-2602, Gas Controls Handbook, and 
compare to the Btuh input rating on appliance 
nameplate.

3. IF CHECKING GAS INPUT WITH 

MANOMETER: Make certain gas control is in 
PILOT position before removing outlet pressure 
tap plug to connect manometer (pressure 
gauge). Also turn gas control knob back to 
PILOT when removing gauge and replacing 
plug. Before removing inlet pressure tap plug, 
shut off gas supply at the manual valve in the 
gas piping to the appliance or, for LP, at the 
tank. Also shut off gas supply before 
disconnecting manometer and replacing plug. 
Repeat Gas Leak Test at plug with main burner 
operating.

Standard Pressure Regulator

1.

Check the manifold pressure listed on the appliance 
nameplate. Gas control outlet pressure should 
match the nameplate.

2.

With main burner operating, check gas control flow 
rate using the meter clocking method or pressure 
using a manometer connected to the outlet 
pressure tap on the gas control. Refer to Fig. 4.

3.

If necessary, adjust pressure regulator to match 
appliance rating. Refer to Table 7 for factory set 
nominal outlet pressure and adjustment range.
a. Remove pressure regulator adjustment cap and 

screw.

b. Using screwdriver, turn inner adjustment screw 

clockwise 

 to increase or counterclockwise 

 to decrease gas pressure to burner.

c. Always replace cap screw and tighten firmly to 

ensure proper operation.

4.

If desired outlet pressure or flow rate cannot be 
achieved by adjusting the control, check the control 
inlet pressure using a manometer at the inlet 
pressure tap. If inlet pressure is in normal range 
(refer to Table 7), replace the control. Otherwise, 
take the necessary steps to provide proper gas 
pressure on the control.

Step-Opening and Slow Opening 
Pressure Regulator

1.

Check the full rate manifold pressure listed on the 
appliance nameplate. Gas control full rate outlet 
pressure should match this rating.

2.

With main burner operating, check the control flow 
rate using the meter clocking method or pressure 
using a manometer connected to outlet pressure 
tap on the control. Refer to Fig. 4.

3.

If necessary, adjust pressure regulator to match 
appliance rating. Refer to Table 7 for factory set 
nominal outlet pressure and adjustment range.
a. Remove pressure regulator adjustment cap 

screw.

b. Using screwdriver, turn inner adjustment screw 

clockwise 

 to increase or counterclockwise    

 

 to decrease gas pressure to burner

c. Always replace cap screw and tighten firmly to 

ensure proper operation.

4.

If desired outlet pressure or flow rate cannot be 
achieved by adjusting the control, check the inlet 
pressure using a manometer at inlet pressure tap or 
upstream of the gas control. If inlet pressure is in 
the normal range (refer to Table 7), replace the 
existing control. Otherwise, take the necessary 
steps to provide proper gas pressure to the control.

5.

STEP-OPENING PRESSURE REGULATORS 
ONLY. Carefully check burner lightoff at step 
pressure. Make sure burner lights smoothly and 
without flashback to orifice. Make sure all ports 
remain lit. Cycle burner several times, allowing at 
least 30 seconds between cycles for regulator to 
resume step function. Repeat after allowing burner 
to cool. Readjust full rate outlet pressure if 
necessary to improve lightoff characteristics.

M3086B

PROPER FLAME

ADJUSTMENT

3/8 TO 1/2 IN.

(10 TO 13 MM)

THERMOCOUPLE

Содержание V8200A

Страница 1: ... one gas to the other with a conversion kit order separately Order Part No 393691 to convert from natural manufactured to LP gas order Part No 394588 to convert from LP to natural manufactured gas Controls with step opening regulators cannot be converted CSA Certificate 112395 Australian Gas Association Certificate 4752 Table 1 Continuous Pilot Combination Gas Control Models Table 2 Model Number S...

Страница 2: ... valve coil terminals This may burn out the heat anticipator in the thermostat IMPORTANT These gas controls are shipped with protective seals over inlet and outlet tappings Do not remove seals until ready to connect piping Follow the appliance manufacturer s instructions if available otherwise use the instructions provided below as a guide Convert between Natural and LP Gas WARNING Fire or Explosi...

Страница 3: ... ordinances or with the Natural Fuel Gas Codes ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing is used obtain a tube to p...

Страница 4: ...onnection and must be clean and dry Never use pipe compound Tighten only 1 4 turn beyond finger tight to give good electrical continuity DO NOT OVERTIGHTEN Wiring Follow the wiring instructions furnished by the appliance manufacturer if available or use the general instructions provided below Where these instructions differ from the appliance manufacturer s follow the appliance manufacturer s inst...

Страница 5: ...h main burner in operation paint pipe joints including adapters and control inlet and outlet with rich soap and water solution 5 If another leak is detected tighten adapter screws joints and pipe connections 6 Replace part if leak can t be stopped Light Pilot 1 Rotate the gas control knob clockwise to OFF Wait five minutes to allow any unburned gas to dissipate Sniff around the appliance near the ...

Страница 6: ...as control Refer to Fig 4 3 If necessary adjust pressure regulator to match appliance rating Refer to Table 7 for factory set nominal outlet pressure and adjustment range a Remove pressure regulator adjustment cap and screw b Using screwdriver turn inner adjustment screw clockwise to increase or counterclockwise to decrease gas pressure to burner c Always replace cap screw and tighten firmly to en...

Страница 7: ...stment see page 6 3 Check the connection to the power unit This is an electrical connection and must be clean and secure 4 If pilot still goes out use a millivoltmeter to measure the exact open circuit output voltages of the thermocouple Compare to acceptable range charts in the thermocouple specifications Replace the thermocouple if voltages are outside the acceptable range otherwise replace the ...

Страница 8: ...instructions exactly 2 Set thermostat to lowest setting and shut off elec tric power to appliance 3 Remove burner access panel if provided on your appliance 4 Turn gas control knob Fig 4 clockwise to OFF position 5 Wait five minutes to allow any gas in the combustion chamber to vent If you then smell gas in the appliance area or near the floor in an LP installation immediately shut off the manual ...

Отзывы: