V8200A,C,H,M AND VR8200A,C,H,M CONTINUOUS PILOT COMBINATION GAS CONTROLS

5

69-0422—03

Fig. 8. Wiring Connections.

Table 5. Maximum Length of Supplementary Limit 

Leadwires when using Q340A Thermocouple.

Table 6. Maximum Length of Supplementary Limit 

Leadwires when using Q309A Thermocouple.

STARTUP AND CHECKOUT

WARNING

Fire or Explosion Hazard can cause property 
damage, severe injury or death.

Do not force the gas control knob on the 
appliance. Use only your hand to push down the 
reset button or turn the gas control knob. Never 
use any tools.

If the knob or reset button will not operate by 
hand, or if the reset button stays depressed after it 
is released, the control should be replaced by a 
qualified service technician.

Gas Control Knob Settings

Gas Control knob settings are as follows:
OFF prevents pilot and main gas flow through the control.
PILOT permits gas to flow to the pilot burner as long as 
red knob is held down or thermocouple current is above 
the power unit dropout value.
ON permits gas to flow into the control body. Pilot gas is 
controlled as in the PILOT position. Main burner gas flow 
is controlled by the thermostat and automatic valve 
operator(s).

NOTE: Valves are shipped with the gas control knob in 

the ON position.

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard can cause property 
damage, severe injury or death.
Check for gas leak with soap and water 
solution any time work is done on a gas 
module.

Gas Leak Test
1. Paint pipe connections upstream of gas control 

with rich soap and water solution. Bubbles 
indicate gas leak.

2. If leak is detected, tighten pipe connections.
3. Stand clear of main burner while lighting to 

prevent injury caused from hidden leaks which 
could cause flashback in the appliance 
vestibule. Light main burner.

4. With main burner in operation, paint pipe joints 

(including adapters) and control inlet and outlet 
with rich soap and water solution.

5. If another leak is detected, tighten adapter 

screws, joints, and pipe connections.

6. Replace part if leak can't be stopped.

Light Pilot

1.

Rotate the gas control knob clockwise 

 to OFF. 

Wait five minutes to allow any unburned gas to 
dissipate. Sniff around the appliance near the floor. 
Don't relight if you smell gas.

2.

Rotate the gas control knob counterclockwise 

 

to PILOT. Push down and hold the red reset button 
while you light pilot burner according to appliance 
manufacturer's instructions.

3.

After about one minute, release reset button. Pilot 
should remain lit. If it goes out, turn gas control 
knob clockwise

 to OFF. To relight, repeat 

steps 1-3.

4.

After pilot remains lit when red reset button is 
released, turn gas control knob counterclockwise 

to ON.

Thermocouple

Length

Maximum Leadwires Length X 2 

(wires)

AWG 

No. 14

AWG 

No. 16

AWG 

No. 18

Inches Meters

in.

m

in.

m

in.

m

12

0.3

41

1.0

26

0.7

16

0.4

18

0.5

35

0.9

22

0.6

13

0.3

24

0.6

29

0.7

18

0.5

11

0.3

30

0.8

23

0.6

15

0.4

9

0.2

36

0.9

17

0.4

11

0.3

6

0.2

40

1.0

13

0.3

8

0.2

48

1.2

DO NOT USE

54

1.4

60

1.5

72

1.8

Thermocouple

Length

Maximum Leadwires Length X 2 

(wires)

AWG

No. 14

AWG 

No. 16

AWG 

No. 18

Inches Meters

in.

m

in.

m

in.

m

12

0.3

47

1.2

30

0.8

18

0.5

18

0.5

41

1.0

26

0.7

16

0.4

24

0.6

35

0.9

22

0.6

14

0.4

30

0.8

29

0.8

18

0.5

11

0.3

36

0.9

23

0.6

15

0.4

9

0.2

40

1.0

19

0.5

12

0.3

7

0.2

48

1.2

11

0.3

7

0.2

54

1.4

DO NOT USE

60

1.5

72

1.8

L1 

(HOT)
L2

1

24V

THERMOSTAT

OPTIONAL

CONVENIENCE

TERMINALS

TH/TR

TH
TR

GAS CONTROL

TERMINALS

HIGH LIMIT

CONTROLLER

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

DO NOT JUMPER THESE TERMINALS.  THIS SHORTS VALVE COIL

AND CAN BURN OUT ANTICIPATOR IN THERMOSTAT.

CONVENIENCE TERMINALS SERVE ONLY AS A TIE POINT. 

THEY ARE NOT INTERNALLY WIRED TO THE CONTROL CIRCUIT 

OR TO GROUND.

OPTIONAL HIGH LIMIT.

1

2

3

4

2

3

4

M2915A

Содержание V8200A

Страница 1: ... one gas to the other with a conversion kit order separately Order Part No 393691 to convert from natural manufactured to LP gas order Part No 394588 to convert from LP to natural manufactured gas Controls with step opening regulators cannot be converted CSA Certificate 112395 Australian Gas Association Certificate 4752 Table 1 Continuous Pilot Combination Gas Control Models Table 2 Model Number S...

Страница 2: ... valve coil terminals This may burn out the heat anticipator in the thermostat IMPORTANT These gas controls are shipped with protective seals over inlet and outlet tappings Do not remove seals until ready to connect piping Follow the appliance manufacturer s instructions if available otherwise use the instructions provided below as a guide Convert between Natural and LP Gas WARNING Fire or Explosi...

Страница 3: ... ordinances or with the Natural Fuel Gas Codes ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing is used obtain a tube to p...

Страница 4: ...onnection and must be clean and dry Never use pipe compound Tighten only 1 4 turn beyond finger tight to give good electrical continuity DO NOT OVERTIGHTEN Wiring Follow the wiring instructions furnished by the appliance manufacturer if available or use the general instructions provided below Where these instructions differ from the appliance manufacturer s follow the appliance manufacturer s inst...

Страница 5: ...h main burner in operation paint pipe joints including adapters and control inlet and outlet with rich soap and water solution 5 If another leak is detected tighten adapter screws joints and pipe connections 6 Replace part if leak can t be stopped Light Pilot 1 Rotate the gas control knob clockwise to OFF Wait five minutes to allow any unburned gas to dissipate Sniff around the appliance near the ...

Страница 6: ...as control Refer to Fig 4 3 If necessary adjust pressure regulator to match appliance rating Refer to Table 7 for factory set nominal outlet pressure and adjustment range a Remove pressure regulator adjustment cap and screw b Using screwdriver turn inner adjustment screw clockwise to increase or counterclockwise to decrease gas pressure to burner c Always replace cap screw and tighten firmly to en...

Страница 7: ...stment see page 6 3 Check the connection to the power unit This is an electrical connection and must be clean and secure 4 If pilot still goes out use a millivoltmeter to measure the exact open circuit output voltages of the thermocouple Compare to acceptable range charts in the thermocouple specifications Replace the thermocouple if voltages are outside the acceptable range otherwise replace the ...

Страница 8: ...instructions exactly 2 Set thermostat to lowest setting and shut off elec tric power to appliance 3 Remove burner access panel if provided on your appliance 4 Turn gas control knob Fig 4 clockwise to OFF position 5 Wait five minutes to allow any gas in the combustion chamber to vent If you then smell gas in the appliance area or near the floor in an LP installation immediately shut off the manual ...

Отзывы: