V8200A,C,H,M AND VR8200A,C,H,M CONTINUOUS PILOT COMBINATION GAS CONTROLS

69-0422—03

4

Fig. 4. Top View of Gas Control.

Fig. 5. Proper use of Wrench on Gas Control with and 

without Flanges.

Connect Pilot Gas Tubing

1.

Cut tubing to desired length and bend as necessary 
for routing to pilot burner. Do not make sharp bends 
or deform the tubing. Do not bend tubing at control 
after compression nut has been tightened, as this 
may result in gas leakage at the connection.

2.

Square off and remove burrs from end of tubing.

3.

Unscrew brass compression fitting from the pilot 
outlet (Fig. 4). Slip the fitting over the tubing and 
slide out of the way.

NOTE: When replacing a control, cut off old 

compression fitting and replace with the 
compression fitting provided on the combination 
gas control. Never use the old compression 
fitting as it may not provide a gas-tight seal. 
Refer to Fig. 6.

Fig. 6. Always use New Compression Fitting.

4.

Push tubing into the pilot gas tapping on the outlet 
end of the control until it bottoms. While holding 
tubing all the way in, slide fitting into place and 
engage threads-turn until finger tight. Then tighten 
one more turn with wrench. Do not overtighten.

5.

Connect other end of tubing to pilot burner 
according to pilot burner manufacturer's 
instructions.

Fig. 7. Installing Thermocouple and Optional ECO 

Adapter to the Power Unit.

Connect Thermocouple

If a supplementary limit or energy cutoff will be used, 
insert the ECO connector (order Part No. 393200-1) as 
shown in Fig. 7, then connect thermocouple lead. If not, 
insert thermocouple lead directly. This is an electrical 
connection and must be clean and dry. Never use pipe 
compound. Tighten only 1/4 turn beyond finger tight to 
give good electrical continuity. DO NOT OVERTIGHTEN.

Wiring

Follow the wiring instructions furnished by the appliance 
manufacturer, if available, or use the general instructions 
provided below. Where these instructions differ from the 
appliance manufacturer's, follow the appliance 
manufacturer's instructions.

All wiring must comply with applicable electrical codes 
and ordinances.

Disconnect power supply before making wiring 
connections to prevent electrical shock or equipment 
damage.

1.

Check the power supply rating on the valve and 
make sure it matches the available supply. Install 
transformer, thermostat and other controls as 
required.

2.

Connect control circuit to gas control terminals. 
Refer to Fig. 4 and 8.

Connect Supplementary Limit or ECO (if 
used)

The leadwires from the high limit or ECO must be 
equipped with insulated 1/4 in. female quick-connect 
terminals. Leadwire lengths must not exceed the lengths 
shown in Tables 5 and 6. Connect the high-limit or ECO 
leadwires to the two terminals on the ECO connector.

OUTLET

PRESSURE 

TAP

INLET

OUTLET

WIRING

TERMINALS (2)

INLET

PRESSURE TAP

PRESSURE REGULATOR

ADJUSTMENT

(UNDER CAP SCREW)

PILOT OUTLET

PILOT ADJUSTMENT

(UNDER CAP SCREW)

GAS

CONTROL

KNOB

M2916

RED

RESET

BUTTON

THERMOCOUPLE

CONNECTION

SCREW

TERMINALS (2)

APPLY WRENCH 

FROM TOP OR 

BOTTOM OF GAS 

CONTROL TO 

EITHER SHADED AREA

WHEN FLANGE IS NOT USED

APPLY WRENCH

TO FLANGE ONLY

WHEN FLANGE IS USED

M2914A

GAS CONTROL

TIGHTEN NUT ONE TURN

BEYOND FINGER-TIGHT.

TO PILOT

BURNER

FITTING BREAKS OFF AND CLINCHES

TUBING AS NUT IS TIGHTENED.

M3076B

THERMOCOUPLE 

LEAD

ECO

CONNECTOR

1

THIS IS AN ELECTRICAL CONNECTION AND MUST BE

CLEAN AND DRY.  DO NOT USE PIPE COMPOUND.

M3095A

1

Содержание V8200A

Страница 1: ... one gas to the other with a conversion kit order separately Order Part No 393691 to convert from natural manufactured to LP gas order Part No 394588 to convert from LP to natural manufactured gas Controls with step opening regulators cannot be converted CSA Certificate 112395 Australian Gas Association Certificate 4752 Table 1 Continuous Pilot Combination Gas Control Models Table 2 Model Number S...

Страница 2: ... valve coil terminals This may burn out the heat anticipator in the thermostat IMPORTANT These gas controls are shipped with protective seals over inlet and outlet tappings Do not remove seals until ready to connect piping Follow the appliance manufacturer s instructions if available otherwise use the instructions provided below as a guide Convert between Natural and LP Gas WARNING Fire or Explosi...

Страница 3: ... ordinances or with the Natural Fuel Gas Codes ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing is used obtain a tube to p...

Страница 4: ...onnection and must be clean and dry Never use pipe compound Tighten only 1 4 turn beyond finger tight to give good electrical continuity DO NOT OVERTIGHTEN Wiring Follow the wiring instructions furnished by the appliance manufacturer if available or use the general instructions provided below Where these instructions differ from the appliance manufacturer s follow the appliance manufacturer s inst...

Страница 5: ...h main burner in operation paint pipe joints including adapters and control inlet and outlet with rich soap and water solution 5 If another leak is detected tighten adapter screws joints and pipe connections 6 Replace part if leak can t be stopped Light Pilot 1 Rotate the gas control knob clockwise to OFF Wait five minutes to allow any unburned gas to dissipate Sniff around the appliance near the ...

Страница 6: ...as control Refer to Fig 4 3 If necessary adjust pressure regulator to match appliance rating Refer to Table 7 for factory set nominal outlet pressure and adjustment range a Remove pressure regulator adjustment cap and screw b Using screwdriver turn inner adjustment screw clockwise to increase or counterclockwise to decrease gas pressure to burner c Always replace cap screw and tighten firmly to en...

Страница 7: ...stment see page 6 3 Check the connection to the power unit This is an electrical connection and must be clean and secure 4 If pilot still goes out use a millivoltmeter to measure the exact open circuit output voltages of the thermocouple Compare to acceptable range charts in the thermocouple specifications Replace the thermocouple if voltages are outside the acceptable range otherwise replace the ...

Страница 8: ...instructions exactly 2 Set thermostat to lowest setting and shut off elec tric power to appliance 3 Remove burner access panel if provided on your appliance 4 Turn gas control knob Fig 4 clockwise to OFF position 5 Wait five minutes to allow any gas in the combustion chamber to vent If you then smell gas in the appliance area or near the floor in an LP installation immediately shut off the manual ...

Отзывы: