Honeywell V800 Скачать руководство пользователя страница 14

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY,  
OR DEATH

,

Do not apply jumper across (or short) valve coil

terminals, even temporarily. Doing so may burn out

heat anticipator in thermostat.

IMPORTANT

Allow 60 seconds after shutdown before 

 step-opening model to ensure 

 at step

pressure.

IF PILOT WILL NOT LIGHT

1. Make sure the main gas supply valve is open and the

pilot gas supply line is purged of air.

2. Attempt to light pilot following procedure in “Light

Pilot”. page 9. If pilot still will not light:

a. Check pilot gas adjustment screw. If closed,
readjust pilot flame. Refer to page 9.
b. Perform gas leak test at compression fitting. If
leak is detected, replace old compression fitting or
tighten new one. Refer to page 7.
c. Ensure that pilot burner tubing or orifice is not
clogged. If clogged, replace combination gas con-
trol.

IF PILOT GOES OUT WHEN GAS CONTROL KNOB IS
RELEASED

1. Make sure the gas control knob is held in at least one

minute 

 therm 

 

 heat.

2. Adjust thermostat several degrees above room

temperature.

3. For 

 and VS821, disconnect 

 lower

left TH terminal and lower right PP terminal to isolate valve

operator coil from balance of circuit. Measure resistance of
coil. If coil is not 2 ohms   10 percent, replace VS824A

Valve Operator.

4.

 Powerpile applications, ensure jumper between

valve operator and power unit is secure and connections
are clean.

5. In thermocouple applications, ensure connection to

power unit is tightened 1/4 turn beyond finger tight.

6. If pilot still goes out, measure the open and closed

thermocouple or generator circuit output voltages. Com-
pare to acceptable range charts in the thermocouple or
generator specifications or in the Gas Controls Handbook.

Replace the thermocouple or generator if voltages are

outside the acceptable range.

7. Check power unit resistance. If above 11 ohms,

replace gas control,

IF MAIN BURNER WILL NOT COME WITH CALL FOR
HEAT

1. Make sure gas control knob is in the ON position.

2. Adjust thermostat several degrees above room

temperature.

3. For VS820 and VS821, disconnect 

 lower

left TH terminal and lower right PP terminal to isolate valve
operator coil from balance of circuit. Measure resistance of
coil. If coil is not 2 ohms   10 percent, replace VS824A
Valve Operator.

4. For all other models, use an 

 measure

voltage across terminals TH and TR. If:

a. No voltage is present, check the control circuit for
proper operation.
b. 24 Vac is present, but first operator did not “click”
open, check for excessive inlet gas pressure. If inlet
pressure is correct, replace the control.
c. 24 Vac is present and first valve operator
“clicked” open, replace second operator assembly.

5. Measure the open and closed thermocouple or gen-

erator output voltages and compare to acceptable range
charts in 

 

 specifications or in

the Gas Controls Handbook. Replace the thermocouple or

generator if voltages are outside the acceptable range.

IF BURNER IS OVERFIRING

Adjust pressure regulator to correct pressure. If regula-

tor cannot be adjusted and supply pressure is in normal

range, replace complete gas 

INSTRUCTIONS TO THE HOMEOWNER

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH
Follow these warnings  and lighting instructions

exact 
1. Before lighting, smell all around the appli-

ance area for gas. If appliance uses LP
(bottled) gas, also be  
sure to smell next to
floor because LP gas is heavier than air. If you
smell gas, immediately shut off the manual

valve 

 

 

SYSTEMS, AT THE TANK. Do not try to light
any appliances in the house. Do not touch
electrical switches or use the phone. LEAVE
THE BUILDING and call your gas supplier
from a neighbor’s house. If your gas supplier
cannot be reached, call the fire department.

2. Do not force the gas control knob on the ap-

pliance. Use only your hand to push down or

turn the gas control knob. Never use any
tools. If the gas control knob will not operate

by hand, the control should be replaced by a
qualified service technician. Force or at-
tempted repair may result in fire or explosion.

3. The control must be replaced if it has been

flooded with water.

4. The control is a SAFETY DEVICE. It must be

replaced in case of any physical damage,
tampering, bent terminals, missing or broken
parts, stripped threads, or evidence of expo-
sure to heat.

14

Содержание V800

Страница 1: ...l of gas flow Available in standard opening and step opening pressure regulator models Can be mounted from O to 90 degrees from the vertical position of the gas control knob El Controls with the prefix V require 30 mV thermo couple and suitable pilot burner Controls with the prefix VS require 750 mV ther mopile generator in a self generating Powerpile system If gas or power supply is interrupted m...

Страница 2: ...ELS AVAILABLE straight through outlet Refer to Fig 3 Ambient Temperature Range Models available V400A Combination Gas Control with either 1 2 in left for 32 F to 175 F 0 C to 79 C hand or right hand side outlet Reducer fittings included to fit variety of sizes V800A C Combination Gas Control with either 1 2 in TRADELINE pack with cross reference label and left hand or right hand side outlet specia...

Страница 3: ...RAVITY CAPACITY BY Manufactured 0 60 0 516 Mixed 0 70 0 765 Propane 1 53 1 62 TABLE 2 CAPACITIES AND PIPE SIZES INLET OUTLET CAPACITYb CAPACITYb MODEL SIZE cfh m lhr NUMBER ELECTRICAL CONNECTIONS VALVE OPERATOR TYPE CONNECTION 10OV 120V and 36 in 0 9 mm 2201240V leadwires 2 112 X 318 110 3 1 V801 VS821 l 2x l 2 225 5 1 V400 V800 112 x 314 250 5 8 V810 VS820 314 x 314 I 335 15 9 314 x 3 4 1450 112 ...

Страница 4: ...l l SIOE VIEW 30 END VIEW OUTLET w TI v5306 ILL sTRATE0 v53070RV8305FIRESS RE REG LAToR 24V MOOELS 3 1 2 89 120V MOOEL 3 5 8 2 MANUAL MODELS 2 13 16 71J FOR V5308 AOO 5 8 16 TO DIMENSIONS GIVEN S DEOUTLETS LEFT ANO R GI IT HAND STANOAROONLYONTRAOEL NE MODELS CONTFIOLWITH24V VALVE OPERATOR SHOWN L NEVOLT MOOELi iASCC3VER FOR CONDU TCONNECT ON TOP SURFACE EC J CONNECTOR AVAILABLE FOR STANOARDCAPAC T...

Страница 5: ...resuit in fire or expiosion 1 Disconnect power supply before wiring to prevent electrical shock or equipment damage 2 Never apply a jumper across or short valve coil terminals This may burn out heat anticipator in thermostat r IMPORTANT These gas controis are shipped with protective seals over inlet and outiet tappings Do not remove seals until ready to connect piping OPTiONAL PiPiNG PATTERNS TRAD...

Страница 6: ...L r 1 PRESSURE INSTALL REGULATOR LONG ADJUSTMENT SCREW IN BENEATH COVER OUTSIOE CREW W CORNER MANUAL GAS CONTROL KNOB 3 76 mml ALL BENDS flLLIC TUBING SHO LD BE SMOOTH CAUTION HUTOFFTHE MAIN GAS SUPPLY BEFORE REh CIVING END CAP TO PREVENT GAS FROM FILLING THE WORK AREA TEST FOR GAS LEAK AGE WHEN INSTALLATION IS COMPLETE 6933D FIG 4 sEDIMENT TRAP INSTALLATION INSTALL CONTROL 1 This control can be m...

Страница 7: ...tight to give good electrical continuity CONNECT ECO Standard capacity 24V 10OV 120V and 220 240 models If the ECO is provided the leadwires must be equipped with insulated 1 4 in female quick connect ter minals Leadwire lengths must not exceed the lengths shown in Tables 5 and 6 Connect the high limit or ECO Ieadwires to the two terminals on the ECO If ECO is not provided connect a Q313B thermopi...

Страница 8: ...ws a Slip conduit fittings over integral leadwires and screw securely into hole in operator cover b Cut flexible conduit to appropriate length Slip conduit over leadwires and attach to fittings c Route and connect both flexible conduits to junc tion box Connect integral wires to control circuit Do not splice except within a junction box LINE VOLTAGE OPERATOR OR CONTROLLER L2 I I 1 Ll 1 JUNCTION BO...

Страница 9: ...on Bubbles indicate gas leak 2 If leak is detected tighten pipe connections 3 Stand clear of main burner while lighting to prevent injury caused from hidden leaks which could cause flash back in the appliance vestibule Light main burner 4 With main burner in operation paint pipe joints in cluding adapters and control inlet and outlet with rich soap and water solution 5 If another leak is detected ...

Страница 10: ...c Always replace cap screw and tighten firmly to ensure proper operation 4 If desired outlet pressure or flow rate cannot be achieved by adjusting the control check the control inlet pressure using a manometer at the inlet pressure tap If inlet pressure is in normal range refer to Table 9 re place the control Otherwise take the necessary steps to provide proper gas pressure on the control Step Ope...

Страница 11: ... such as in the commercial cooking and agricultural and industrial industries because In many such applications particularly commercial cooking the equipment operates 100 000 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years Exposure to water dirt chemicals and heat can damage the gas control and shut down the control system The maintenance program should ...

Страница 12: ...s control if the pilot flame becomes extinguished or too small for satisfactory burner ignition As the pilot burns it constantly heats the thermo couple or Powerpile generator providing current for the Pilotstat power unit in the gas control A properly burning pilot supplies the power unit with enough current to keep the safety valve open and allow pilot gas flow If the pilot goes out or decreases...

Страница 13: ...LET GAS CONTROL ON p LOT OFF KNOB SERVO PRESSURE REGULATOR D MAIN VALVE woRK NG GAS lMAIN VALVE PRESSURE CHAMBER DIAPHRAGM 12 882 FIG 14 GAS FLOW THROUGH THE V800 COMBINATION GAS CONTROL FAMILY 13 60 201 9 7 ...

Страница 14: ... disconnect Ieadwiresto lower left TH terminal and lower right PP terminal to isolate valve operator coil from balance of circuit Measure resistance of coil If coil is not 2 ohms 10 percent replace VS824A Valve Operator 4 For all other models use an acvoltmeterto measure voltage across terminals TH and TR If a No voltage is present check the control circuit for proper operation b 24 Vac is present...

Страница 15: ...e the pilot access panel located below and behind the gas control unit 7 Find the pilot follow metal tube from gas control The pilot is between the two burner tubes behind the pilot access panel 8 Turn knob on gas control counterclockwise m t o PILOT 9 Push in control knob all the way and hold in immedi ately Iightthe pilot with a match continue to hold the control knob in for about one 1 minute a...

Отзывы: