Honeywell V5055A Скачать руководство пользователя страница 9

V5055A-F INDUSTRIAL GAS VALVES

9

60-2307—15

4.

Remove the leak test tap plug and connect the test 

apparatus to the Leak Tap (

D

).

5.

Close the downstream manual gas cock (

E

).

6.

Open the upstream manual gas cock (

A

).

7.

Run the safety shutoff valve (

C

) to its fully open position 

(through the safety system); then immediately 

de-energize the system to close the valve.

8.

Immerse a 1/4 in. tube vertically 1/2 in.  (12.7 mm) into 

a jar of water.

9.

Slowly open the test petcock (

F

).

10.

When the rate of bubbles coming through the water 

stabilizes, count the number of bubbles appearing 

during a ten-second period. Each bubble appearing 

during a ten-second period represents a flow rate of 

approximately 0.001 cfh.

To meet U.S. requirements, leakage must not exceed the  

values listed in Table 5.

Table 5. Allowable Leakage for V5055 Valves.

a

Based on natural gas at standard conditions, test pressures 

provided by ANSI Z21.21, Section 2.4.2 and a maximum of 

235 cc/hr (air) per inch of seal-off diameter. Seal-off diameter 

is not to be confused with pipe size.

b

 V5055F leakage rate is 1 bubble in 7.6 seconds.

NOTE: For international leak test requirements, contact 

the office of the appropriate approval agency.

After the test:

11.

Close the upstream manual gas cock (A).

12.

Close the test petcock (F), remove the test apparatus, 

and replace the leak test tap plug (D).

13.

Open the upstream manual gas cock (A) and energize 

the safety shutoff valve (C).

14.

Test with soap bubbles to assure that there is no leak 

at the test tap (D).

15.

De-energize the safety shutoff valve (C).

16.

Open the downstream manual gas cock (E).

17.

Restore the system to normal operation. If two safety 

shutoff valves are utilized, each V5055 valve is to be 

checked for tightness of closure.

SERVICE INFORMATION

WARNING

Explosion and Electrical Shock Hazard.

Can cause serious injury, death or property 

damage.

1. Before servicing, turn off the gas supply and 

disconnect all electrical power to the valve actuator. 

2. Only qualified service technicians should attempt 

to service or repair flame safeguard controls and 

burner systems.

3. Do not disassemble the valve bonnet assembly; 

the valve seat is not replaceable.

4. Failure to properly position and seat the seals in the 

valve body may result in a hazardous gas leak.

Scheduled Inspection and Maintenance

Setup and follow a schedule for periodic inspection and 

maintenance, including the burner, all other controls, and 

the valve(s). It is recommended that the Valve Leak Test in 

the Checkout section be included in this schedule. Refer to 

the Instructions for the primary safety control for more 

information.

Valve Bonnet Replacement

The entire valve bonnet may be replaced without removing 

the valve body from the gas line. Do not disassemble the 

valve bonnet assembly; the valve seat is not replaceable.

For part numbers, refer to Replacement Parts in the 

Specifications section. Complete instructions for replacing 

the bonnet assembly are included with the replacement part.

Replacement of Seals (Fig. 8 or 9)

When removing the bonnet to inspect and clean the valve, 

install new seals (see Replacement Parts in Specifications 

section). Coat the new seals with the grease provided, and 

position them in the valve body as shown in  Fig. 8 or 9.

Failure to properly position and seat the seals in the valve 

body may result in a hazardous gas leak.

After the new bonnet assembly is installed, or the bonnet is 

removed for any reason, check for gas leakage around the 

bonnet seal. Turn on the gas at the manual valve. Paint the 

seal area with a rich soap and water solution. Bubbles 

indicate a gas leak. If a leak is detected, check to see that 

the bonnet screws are tight. If necessary, turn off the gas 

again and remove the bonnet to be sure the seals are 

properly seated.

V5055 Pipe 

Size (in.)

Allowable 

leakage 

(cc/hr)

a,b

Maximum 

Number of 

bubbles per 10 

sec. 

Minimum 

Number of 

Seconds for 

10 bubbles 

3/4, 1, 1-1/4, 

1-1/2

573

14

6.7

2, 2-1/2, 3

940

24

4.1

4

1254

33

3.03

Содержание V5055A

Страница 1: ...Valves have a double seal and are used with V4055D E Actuators to provide proof of closure switch and valve seal overtravel interlock V5055D E F Valves are for high pressure applications see Table 1 Seven valve sizes from 3 4 to 3 inches have NPT threaded connections Models are available with BSP PL threads V5055A B C Valves are available in a 4 inch size and have flange connections Most models ha...

Страница 2: ...nly Pipe Size 3 4 1 1 1 4 1 1 2 2 2 1 2 3 and 4 in only V5055A B C available in 4 in size Pipe Threads NPT or BSP PL Threads equivalent to ISO R7 and DIN 2999 Available on inlet and outlet of 3 4 to 3 inch valves Four inch valves have flange connections Pressure Ratings See Table 1 Valve Body Rating 75 psi 517 1 kPa Valve Capacities At 1 in 0 25 kPa pressure drop based on gas with specific gravity...

Страница 3: ...cf h cu m hr 3 4 665 18 8 1 960 27 2 1 1 4 1406 39 8 1 1 2 1717 48 6 2 3620 102 5 2 1 2 4250 120 3 3 5230 148 1 4 V5055A 10200 288 8 4 V5055B C 9180 259 9 M9542 100 2 8 1 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 1 0 0 25 10 0 2 5 100 0 25 9 8 7 6 5 4 3 2 1 100 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 1000 28 10 000 283 100 000 2...

Страница 4: ... ft for type of gas used 3 Find the capacity in cf h If the capacity is listed in Btu h convert to cfh by the following formula Capacity in cf h Btu h from burner nameplate Btu cu ft from gas utility 4 For gases with specific gravities other than 0 64 multiply the burner cfh by the proper conversion factor See Table 4 Table 4 Gas Conversion Factors 5 Use the corrected burner capacity in cf h when ...

Страница 5: ...08 0 208 0 211 1 223 8 223 8 5 3 4 5 3 4 5 3 4 5 3 4 8 3 8 9 1 4 9 1 4 146 1 146 1 146 1 146 1 212 7 235 0 235 0 2 1 4 2 1 4 2 1 4 2 1 4 2 3 4 2 3 4 2 3 4 57 2 57 2 57 2 57 2 69 9 69 9 69 9 4 13 16 4 13 16 4 13 16 4 13 16 7 19 32 7 19 32 7 19 32 122 2 122 2 122 2 122 2 192 9 192 9 192 9 2 13 16 2 13 16 2 13 16 2 13 16 3 1 2 4 1 2 4 1 2 71 4 71 4 71 4 71 4 88 9 114 3 114 3 DIM A IN MM DIM B IN MM D...

Страница 6: ... must be a trained experienced flame safeguard control technician 4 After installation is complete check out product operations as provided in these instructions WARNING Electrical Shock Hazard and Explosion Hazard Can cause serious injury death or property damage 1 Turn off gas supply before starting installation 2 Disconnect power supply for valve actuator before beginning installation to preven...

Страница 7: ...5 9 Make sure the power supply is disconnected from the valve actuator Then mount the actuator on the valve body and complete the electrical and linkage connections following the instructions packed with the actuator OPERATION AND CHECKOUT Operation A V5055 Industrial Gas Valve is operated by a V4055 V4062 or V9055 Fluid Power Gas Valve Actuator The valve opens when the actuator is energized and c...

Страница 8: ...med by qualified personnel during the initial startup of a burner system or whenever the valve or valve bonnet is replaced see Service Information section It is recommended that this test also be included in the scheduled inspection and maintenance procedures For a periodic inspection test follow steps 1 3 4 5 8 9 10 12 13 16 and 17 Fig 7 Valve leak test 1 De energize the control system to assure ...

Страница 9: ...f the gas supply and disconnect all electrical power to the valve actuator 2 Only qualified service technicians should attempt to service or repair flame safeguard controls and burner systems 3 Do not disassemble the valve bonnet assembly the valve seat is not replaceable 4 Failure to properly position and seat the seals in the valve body may result in a hazardous gas leak Scheduled Inspection and...

Страница 10: ...GAS VALVES 60 2307 15 10 Fig 8 Proper positions of valve and bonnet seals in 3 4 through 3 in valves Fig 9 Proper positions of valve and bonnet seals in 4 in valve s M9578 VALVE SEAL BONNET SEAL SMALL SEAL LARGE SEAL M9579 ...

Страница 11: ...11 60 2307 15 ...

Страница 12: ...neywell com Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 V5055A F INDUSTRIAL GAS VALVES ...

Отзывы: