V5055A-F INDUSTRIAL GAS VALVES

60-2307—15

6

INSTALLATION

IMPORTANT:

 The V5055 Valve is designed to provide control 

of gaseous fuel (natural and LP gas) flow in 

applications in which there is minimal exposure to 

water. V5055 Valves used in maritime, beverage, 

food processing, outdoor and other installations in 

which occasional exposure to water is experienced 

may be subject to valve stem and spring corrosion. 

The presence of corrosion decreases the operating 

life of the valve. V5055 Valves used in such 

installations should be inspected at least annually 

and should have the valve bonnets replaced if 

corrosion is noted.

A V4055 Valve Actuator with a NEMA 4 rating is also 

recommended for such installations. The water-tight 

design of the NEMA 4 rated V4055 Actuator prevents 

water from entering the V4055 valve stem and spring 

chamber through the actuator. Under certain 

conditions, some water may be retained by the 

external upper portion of the valve body. The 

retained water is effectively excluded from the valve 

stem and spring chamber by a functional seal that is 

incorporated into the NEMA 4 rated actuator.

When Installing This Product…

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced, flame 

safeguard control technician.

4.

After installation is complete, check out product 

operations as provided in these instructions.

WARNING

Electrical Shock Hazard and Explosion Hazard.

Can cause serious injury, death or property 

damage.

1. Turn off gas supply before starting installation.

2. Disconnect power supply for valve actuator before 

beginning installation to prevent electrical shock 

and equipment damage.

3. Be sure the valve is installed so the arrow on 

the valve points in the direction of gas flow. 

(Gas pressure helps to close the valve.)

Location

Install the valve in the gas supply line downstream from the 

pressure regulator. The valve and actuator may be mounted in 

any position that allows sufficient clearance for installation and 

for repair or replacement.

1.

The valve position indicators should be easily visible 

with the valve and actuator in the final position.

2.

The final position of the valve and actuator must allow 

for damper linkage, if used.

IMPORTANT:

 Allow room for turning the valve body (actuator not 

attached) onto the gas piping. Swing dimensions, 

measured from the center of the pipe are: 

         3/4 through 1-1/2 in. valves: 4 in. (101.6 mm). 

         2 through 3 in. valves: 5 in. (127.0 mm). 

         4 in. valves: 7 in. (177.8 mm).

Mounting (Figs. 4 through 6)

WARNING

Explosion Hazard.

Can cause serious injury, death or property 

damage.

If flow is not in the direction of the arrow on the valve 

body, the valve may not shut off.

1.

Use new, properly reamed, pipe, free from chips.

2.

Do not thread pipe too far (Fig. 4). Valve distortion or 

malfunction may result from excess pipe in the valve.

Содержание V5055A

Страница 1: ...Valves have a double seal and are used with V4055D E Actuators to provide proof of closure switch and valve seal overtravel interlock V5055D E F Valves are for high pressure applications see Table 1 Seven valve sizes from 3 4 to 3 inches have NPT threaded connections Models are available with BSP PL threads V5055A B C Valves are available in a 4 inch size and have flange connections Most models ha...

Страница 2: ...nly Pipe Size 3 4 1 1 1 4 1 1 2 2 2 1 2 3 and 4 in only V5055A B C available in 4 in size Pipe Threads NPT or BSP PL Threads equivalent to ISO R7 and DIN 2999 Available on inlet and outlet of 3 4 to 3 inch valves Four inch valves have flange connections Pressure Ratings See Table 1 Valve Body Rating 75 psi 517 1 kPa Valve Capacities At 1 in 0 25 kPa pressure drop based on gas with specific gravity...

Страница 3: ...cf h cu m hr 3 4 665 18 8 1 960 27 2 1 1 4 1406 39 8 1 1 2 1717 48 6 2 3620 102 5 2 1 2 4250 120 3 3 5230 148 1 4 V5055A 10200 288 8 4 V5055B C 9180 259 9 M9542 100 2 8 1 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 1 0 0 25 10 0 2 5 100 0 25 9 8 7 6 5 4 3 2 1 100 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 1000 28 10 000 283 100 000 2...

Страница 4: ... ft for type of gas used 3 Find the capacity in cf h If the capacity is listed in Btu h convert to cfh by the following formula Capacity in cf h Btu h from burner nameplate Btu cu ft from gas utility 4 For gases with specific gravities other than 0 64 multiply the burner cfh by the proper conversion factor See Table 4 Table 4 Gas Conversion Factors 5 Use the corrected burner capacity in cf h when ...

Страница 5: ...08 0 208 0 211 1 223 8 223 8 5 3 4 5 3 4 5 3 4 5 3 4 8 3 8 9 1 4 9 1 4 146 1 146 1 146 1 146 1 212 7 235 0 235 0 2 1 4 2 1 4 2 1 4 2 1 4 2 3 4 2 3 4 2 3 4 57 2 57 2 57 2 57 2 69 9 69 9 69 9 4 13 16 4 13 16 4 13 16 4 13 16 7 19 32 7 19 32 7 19 32 122 2 122 2 122 2 122 2 192 9 192 9 192 9 2 13 16 2 13 16 2 13 16 2 13 16 3 1 2 4 1 2 4 1 2 71 4 71 4 71 4 71 4 88 9 114 3 114 3 DIM A IN MM DIM B IN MM D...

Страница 6: ... must be a trained experienced flame safeguard control technician 4 After installation is complete check out product operations as provided in these instructions WARNING Electrical Shock Hazard and Explosion Hazard Can cause serious injury death or property damage 1 Turn off gas supply before starting installation 2 Disconnect power supply for valve actuator before beginning installation to preven...

Страница 7: ...5 9 Make sure the power supply is disconnected from the valve actuator Then mount the actuator on the valve body and complete the electrical and linkage connections following the instructions packed with the actuator OPERATION AND CHECKOUT Operation A V5055 Industrial Gas Valve is operated by a V4055 V4062 or V9055 Fluid Power Gas Valve Actuator The valve opens when the actuator is energized and c...

Страница 8: ...med by qualified personnel during the initial startup of a burner system or whenever the valve or valve bonnet is replaced see Service Information section It is recommended that this test also be included in the scheduled inspection and maintenance procedures For a periodic inspection test follow steps 1 3 4 5 8 9 10 12 13 16 and 17 Fig 7 Valve leak test 1 De energize the control system to assure ...

Страница 9: ...f the gas supply and disconnect all electrical power to the valve actuator 2 Only qualified service technicians should attempt to service or repair flame safeguard controls and burner systems 3 Do not disassemble the valve bonnet assembly the valve seat is not replaceable 4 Failure to properly position and seat the seals in the valve body may result in a hazardous gas leak Scheduled Inspection and...

Страница 10: ...GAS VALVES 60 2307 15 10 Fig 8 Proper positions of valve and bonnet seals in 3 4 through 3 in valves Fig 9 Proper positions of valve and bonnet seals in 4 in valve s M9578 VALVE SEAL BONNET SEAL SMALL SEAL LARGE SEAL M9579 ...

Страница 11: ...11 60 2307 15 ...

Страница 12: ...neywell com Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 V5055A F INDUSTRIAL GAS VALVES ...

Отзывы: