V5055A-F INDUSTRIAL GAS VALVES

60-2307—15

8

Fig. 6. Installing a 4 in. V5055 Valve.

CAUTION

Equipment Damage Hazard.

Operation without proper checkout can damage 

the equipment.

1. Do not put the system into service until you have 

satisfactorily completed the following Valve Leak 

Test, all applicable tests described in the Checkout 

section of the Instructions for the flame safeguard 

control, and any other tests required by the burner 

manufacturer.

2. All tests must be performed by a trained, 

experienced flame safeguard control technician.

3. Close all manual fuel shutoff valves as soon as 

trouble occurs.

After the installation is complete, cycle the valve several times 

with the manual fuel shutoff cock closed. Make sure the valve 

and actuator function properly. Also perform the Valve Leak 

Test that follows before putting the valve into service.

Valve Leak Test (Fig. 7)

This is a test for checking the closure tightness of a gas 

safety shutoff valve. It should be performed by qualified 

personnel during the initial startup of a burner system, or 

whenever the valve or valve bonnet is replaced (see 

Service Information section). It is recommended that this 

test also be included in the scheduled inspection and 

maintenance procedures. For a periodic inspection test, 

follow steps 1, 3, 4, 5, 8, 9, 10, 12, 13, 16, and 17.

Fig. 7. Valve leak test.

1.

De-energize the control system to assure that there is 

no power to the safety shutoff valve (

C

) shown in Fig. 7.

2.

Close the upstream manual gas cock (

A

).

3.

Make sure the manual test petcock (

F

) is closed in the 

leak test tap assembly (

D

).

NUT AND WASHER

(NOT INCLUDED)

4 IN. VALVE

4 IN. PIPE

M9581

GASKET 

(2 INCLUDED WITH VALVE)

THREADED COMPANION 

FLANGE (2 - NOT INCLUDED)

5/8 X 3 IN. [76] BOLT

(16 - NOT INCLUDED)

M9547F

GAS

SUPPLY

UPSTREAM

MANUAL

GAS COCK

DOWNSTREAM

MANUAL

GAS COCK

BURNER

   D

A

B

C

E

F

PRV

MANUAL

TEST

PETCOCK

SSOV

1/4 IN. (6 MM) 

FLEXIBLE

TUBING
1/4 IN. (6 MM)

ALUMINUM OR 

COPPER PILOT 

TUBING

JAR OR GLASS

WITH WATER

CUT AT

45 DEGREE

ANGLE

CAN ALSO BE A PERMANENT PETCOCK.

PRV = PRESSURE REGULATING VALVE.

SSOV = SAFETY SHUTOFF VALVE.

 USE ONLY ONE OF THE DOWNSTREAM TAPS ON THE SS0V.

1

2

3

4

4

2

3

1

1

2

(13 MM)

LEAK 

TEST 

TAP

Содержание V5055A

Страница 1: ...Valves have a double seal and are used with V4055D E Actuators to provide proof of closure switch and valve seal overtravel interlock V5055D E F Valves are for high pressure applications see Table 1 Seven valve sizes from 3 4 to 3 inches have NPT threaded connections Models are available with BSP PL threads V5055A B C Valves are available in a 4 inch size and have flange connections Most models ha...

Страница 2: ...nly Pipe Size 3 4 1 1 1 4 1 1 2 2 2 1 2 3 and 4 in only V5055A B C available in 4 in size Pipe Threads NPT or BSP PL Threads equivalent to ISO R7 and DIN 2999 Available on inlet and outlet of 3 4 to 3 inch valves Four inch valves have flange connections Pressure Ratings See Table 1 Valve Body Rating 75 psi 517 1 kPa Valve Capacities At 1 in 0 25 kPa pressure drop based on gas with specific gravity...

Страница 3: ...cf h cu m hr 3 4 665 18 8 1 960 27 2 1 1 4 1406 39 8 1 1 2 1717 48 6 2 3620 102 5 2 1 2 4250 120 3 3 5230 148 1 4 V5055A 10200 288 8 4 V5055B C 9180 259 9 M9542 100 2 8 1 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 1 0 0 25 10 0 2 5 100 0 25 9 8 7 6 5 4 3 2 1 100 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 1000 28 10 000 283 100 000 2...

Страница 4: ... ft for type of gas used 3 Find the capacity in cf h If the capacity is listed in Btu h convert to cfh by the following formula Capacity in cf h Btu h from burner nameplate Btu cu ft from gas utility 4 For gases with specific gravities other than 0 64 multiply the burner cfh by the proper conversion factor See Table 4 Table 4 Gas Conversion Factors 5 Use the corrected burner capacity in cf h when ...

Страница 5: ...08 0 208 0 211 1 223 8 223 8 5 3 4 5 3 4 5 3 4 5 3 4 8 3 8 9 1 4 9 1 4 146 1 146 1 146 1 146 1 212 7 235 0 235 0 2 1 4 2 1 4 2 1 4 2 1 4 2 3 4 2 3 4 2 3 4 57 2 57 2 57 2 57 2 69 9 69 9 69 9 4 13 16 4 13 16 4 13 16 4 13 16 7 19 32 7 19 32 7 19 32 122 2 122 2 122 2 122 2 192 9 192 9 192 9 2 13 16 2 13 16 2 13 16 2 13 16 3 1 2 4 1 2 4 1 2 71 4 71 4 71 4 71 4 88 9 114 3 114 3 DIM A IN MM DIM B IN MM D...

Страница 6: ... must be a trained experienced flame safeguard control technician 4 After installation is complete check out product operations as provided in these instructions WARNING Electrical Shock Hazard and Explosion Hazard Can cause serious injury death or property damage 1 Turn off gas supply before starting installation 2 Disconnect power supply for valve actuator before beginning installation to preven...

Страница 7: ...5 9 Make sure the power supply is disconnected from the valve actuator Then mount the actuator on the valve body and complete the electrical and linkage connections following the instructions packed with the actuator OPERATION AND CHECKOUT Operation A V5055 Industrial Gas Valve is operated by a V4055 V4062 or V9055 Fluid Power Gas Valve Actuator The valve opens when the actuator is energized and c...

Страница 8: ...med by qualified personnel during the initial startup of a burner system or whenever the valve or valve bonnet is replaced see Service Information section It is recommended that this test also be included in the scheduled inspection and maintenance procedures For a periodic inspection test follow steps 1 3 4 5 8 9 10 12 13 16 and 17 Fig 7 Valve leak test 1 De energize the control system to assure ...

Страница 9: ...f the gas supply and disconnect all electrical power to the valve actuator 2 Only qualified service technicians should attempt to service or repair flame safeguard controls and burner systems 3 Do not disassemble the valve bonnet assembly the valve seat is not replaceable 4 Failure to properly position and seat the seals in the valve body may result in a hazardous gas leak Scheduled Inspection and...

Страница 10: ...GAS VALVES 60 2307 15 10 Fig 8 Proper positions of valve and bonnet seals in 3 4 through 3 in valves Fig 9 Proper positions of valve and bonnet seals in 4 in valve s M9578 VALVE SEAL BONNET SEAL SMALL SEAL LARGE SEAL M9579 ...

Страница 11: ...11 60 2307 15 ...

Страница 12: ...neywell com Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 V5055A F INDUSTRIAL GAS VALVES ...

Отзывы: