Setting Parameter S-04: PRESETTING
Table 4. Setting parameter S-04: Presetting
Valve
V5004TF
1050
V5004TF
1065
V5004TF
1080
V5004TF
1100
V5004TF
1125
V5004TF
1150
V5004TF
1200LF
V5004TF
1200HF
V5004TF
1250LF
V5004TF
1250HF
Max. pre-
setting flow
rate (m
3
/h)
20
30
30
55
90
150
200
300
300
500
Min. pre-
setting flow
rate (m
3
/h)
2
3
3
5.5
9
15
20
30
30
50
The presetting flow rate of valve V5004TF can be set through parameter S-04 of the M5004 actuator: The parameter should be
set to a value between the valve's max. and the min. presetting flow rates. S-03 should be left at 0.
RATIO OF VALUE OF FLOW ACCORDING TO FLOW CURVE
Table 5. Ratio of value of flow according to flow curve
POSITION of VALVE LIFT (unit: %)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
LINEAR CURVE (unit: %)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
EQUAL PERCENT CURVE (unit: %)
0 2 3 4 4 5 6 8 10 12 14 17 21 25 31 38 46 56 68 82 100
100
90
80
70
60
50
40
30
20
10
10
20
30
40
50
60
70
80
90 100
LINE
AR CUR
VE
EQUAL % CURVE
%
%
Fig. 6. Linear curve vs. equal-percent curve
20
VOLTAGE
FLOW
(cu. m/h)
0V
0
10
9
18
10V
818
40
= 0
0 - 10
E.g.: DN50,
max. flow =
20 m3/h
= 20
= 18
Fig. 7. Example settings