V5004TF ACTUATOR – INSTALLATION INSTRUCTIONS 

MU1B-0655GE51 R1019A 

4

6. Exercising and Cleaning 

6a. Weekly Exercising 

To ensure continued smooth valve movement, the valve 
should be operated (exercised) once a week over its entire 
operating range. 
 

6b. Cleaning 

Use a damp cloth to clean the actuator. 
Do not use any detergent or chemical product that may 
seriously damage or compromise the function of the valve. 
 

6c. "Error" in Actuator's Display 

If the actuator's shaft encounters excessively high torque, the 
digital display of the V5004TF actuator will show: 

 

Fig. 4. "Error" in actuator display 

 
This can be caused by: 
•  The valve (which may be worn-out or defective); 
•  Manual operation while the actuator is powered. 
After correcting the cause of the error, reset the ERROR 
display by pressing the UP and DOWN buttons simul-
taneously for 3 seconds. 
 

6d. Cleaning the Valve's Adjustment Screw 

The adjustment screw of the V5004T Kombi-QM should be 
cleaned regularly – usually, once annually or after every 5,000 
cycles. Under certain environmental and operational con-
ditions, it may be necessary to perform this task more 
frequently. 
 

6e. Dismounting the Actuator 

To dismount the actuator, proceed as follows: 
Turn the connection ring between the valve and the actuator 
and remove the actuator. 

 

1

2

 

Fig. 5. Dismounting the actuator 

 

NOTE:

 

To avoid damage due to condensation from the 
valve stem, be sure that the actuator is not 
mounted upside down. Please note that care must 
be taken when installing the actuator: Even only 
minor angular deviations can compromise proper 
actuator operation. 

 

7. Initial Setting 

Upon powering up the device, the display indicates "Go-0" 
and the initial setting to the valve zero point is automatically 
adjusted. 
Do not press any buttons during this adjustment process as 
this might interfere with the automatic adjustment of the initial 
setting of the valve zero point and thus result in incorrect flow 
control. 
How to set: To enter the setting mode, press the MODE 
button several times until the required setting is displayed 
(e.g., S-01). After 2 s, the value of the selected setting is 
displayed and can now be changed, if desired, using the UP 
and DOWN buttons. After changing the value, you must press 
the MODE button within 5 s in order to save the changed 
value – otherwise, the change will not be saved and the 
display will return to its basic value. 
 

Содержание V5004T

Страница 1: ...mmissioned actuator Proportional flow control Analog voltage and current floating and ON OFF Position feedback 4 digit display 3 buttons to set parameters Position control method to set the flow rate INSTALLATION INSTRUCTIONS 1 Mount the valve with the arrow in the direction of the flow CAUTION Mounting the valve in the wrong direction may damage the system and the valve itself If flow reversal is...

Страница 2: ...ON INSTRUCTIONS MU1B 0655GE51 R1019A 2 3 Turn the key while continuing to push down the release button located on the bottom of the actuator 1 2 Fig 1 Manual override M5004 4b Valve Actuator Assembly Fig 2 Valve actuator assembly ...

Страница 3: ...ing Table 2 Wire guidelines Input Number 1 2 3 4 5 Remarks Color Black BK Red RD White WH Green GN Blue BU Internal control A Common 24 AC DC Feedback 0 2 10 V 0 4 20 mA Power cable 1 2 Voltage signal Common 24 AC DC 0 10 VDC 2 10 VDC Feedback 0 2 10 V 0 4 20 mA Power cable 1 2 Voltage signal cable 1 3 Current signal Common 24 AC DC 0 20 mA 4 20 mA Feedback 0 2 10 V 0 4 20 mA Power cable 1 2 Curre...

Страница 4: ... to perform this task more frequently 6e Dismounting the Actuator To dismount the actuator proceed as follows Turn the connection ring between the valve and the actuator and remove the actuator 1 2 Fig 5 Dismounting the actuator NOTE To avoid damage due to condensation from the valve stem be sure that the actuator is not mounted upside down Please note that care must be taken when installing the a...

Страница 5: ... OFF 24 V open 0 V close Floating input 24 V open if white wire 3 connected 24 V close if green wire 4 connected Remote control Not available PWM 5 sec PWM 0 1 5 sec PWM 25 sec PWM 0 1 25 sec Internal input Flow rate set by onboard display and buttons Push MODE button wait until SET is replaced by flow rate indication or flow rate depending upon S 01 set the flow rate using the UP DOWN buttons and...

Страница 6: ...splay is shown Value on display flow rate offset default 0 Select using the UP DOWN buttons and then press the MODE button to confirm Power failure mode not available Unit of SI m3 h Select using the UP DOWN buttons and then press the MODE button to confirm Unit of GPM gal min Linear control curve Select using the UP DOWN buttons and then press the MODE button to confirm Equal percentage control c...

Страница 7: ...rameter should be set to a value between the valve s max and the min presetting flow rates S 03 should be left at 0 RATIO OF VALUE OF FLOW ACCORDING TO FLOW CURVE Table 5 Ratio of value of flow according to flow curve POSITION of VALVE LIFT unit 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 LINEAR CURVE unit 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 EQUAL PERCEN...

Страница 8: ... non condensing Storage temp range 20 80 C non condensing Specifications Weight 0 975 kg Power supply 24 VAC DC 50 60 Hz Power consumption 5 W 2 5 W stand by Connecting cable length 0 25 m Connection to valve 8 mm square Easy fitting gear Operating life 50 000 cycles Control signal 0 2 10 V 250 kΩ burden 0 4 20 mA 500 Ω burden ON OFF 24 VAC DC 30 mA AC 6 mA DC 3 point floating 24 VAC DC 30 mA AC 6...

Страница 9: ...til beschädigen Honeywell lehnt jegliche Haftung für die unsachgemäße oder fehlerhafte Nutzung dieses Produktes ab MERKMALE Betriebsbereiter Stellantrieb Proportionale Steuerung Analoge Spannung und Strom 3 Punkt und AUF ZU Stellsignaleingang Positionsrückmeldung 4 stelliges Display 3 Tasten zur Parametereinstellung Positionssteuerungsmethode zum Einstellen des Durchflusses INSTALLATIONSANWEISUNG ...

Страница 10: ...kel auf der Oberseite des Stallantriebs und stecken Sie den 6 mm Inbussschlüssel ein 3 Drehen Sie den Schlüssel und halten Sie dabei den entsicherten Knopf unter dem Stellantrieb gedrückt 1 2 Abb 1 Manuelle Übersteuerung M5004 4b Ventil Stellantrieb Baugruppe Abb 2 Ventil Stellantrieb Baugruppe ...

Страница 11: ...inien Eingangswert Nr 1 2 3 4 5 Anmerkungen Farbe Schwarz BK Rot RD Weiß WH Grün GN Blau BU Interne Kontrolle A Masse 24 AC DC Rückmeldung 0 2 10 V 0 4 20 mA Leistung Kabel 1 2 Spannungssignal Masse 24 AC DC 0 10 VDC 2 10 VDC Rückmeldung 0 2 10 V 0 4 20 mA Leistung Kabel 1 2 Spannungssignal Kabel 1 3 Stromsignal Masse 24 AC DC 0 20 mA 4 20 mA Rückmeldung 0 2 10 V 0 4 20 mA Leistung Kabel 1 2 Strom...

Страница 12: ...n in der Regel einmal jährlich bzw nach 5 000 Zyklen Unter bestimmten Umwelt und Betriebsbedingungen könnte es nötig sein diese Reinigung öfter durchzuführen 6e Demontage des Stellantriebs Wenn der Stellantrieb demontiert werden muß gehen Sie wie folgt vor Drehen Sie den Verbindungsring zwischen Ventil und Stellantrieb und demontieren Sie den Stellantrieb 1 2 Abb 5 Demontage des Stellantriebs HINW...

Страница 13: ...geschlossen 3 Punkt Eingang 24 V offen wenn weißer Draht 3 angeschlossen ist 24 V geschlossen wenn grüner Draht 4 angeschlossen ist Fernsteuerung Nicht verfügbar PWM 5 Sek PWM 0 1 5 Sek PWM 25 Sek PWM 0 1 25 Sek Festsollwert Volumenstrom eingestellt über On board Display und Tasten Modustaste drücken warten bis Set durch Anzeige des Volumenstroms ersetzt wird oder Volumenstrom je nach S 01 Volumen...

Страница 14: ... angezeigt ist Wert auf dem Display des Volumenstrom Offsets Vorgabe 0 Auswählen mit der Nach oben Nach unten Taste und Bestätigung mit der Modustaste Versorgungsunterbrechungsmodus nicht erhältlich SI Einheit m3 h Auswählen mit der Nach oben Nach unten Taste und Bestätigung mit der Modustaste GPM Einheit gal min Lineare Kennlinie Auswählen mit der Nach oben Nach unten Taste und Bestätigung mit de...

Страница 15: ... max und dem min Voreinstellungs Volumenstroms des Ventils liegen S 03 sollte auf 0 eingestellt bleiben VERHÄLTNIS DES VOLUMENSTROMWERTS GEMÄSS VOLUMENSTROMKENNLINIE Tabelle 5 Verhältnis des Volumenstromwerts gemäß Volumenstromkennlinie POSITION der VENTILÖFFNUNG Einheit 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 LINEARE KENNLINIE Einheit 0 5 10 15 20 25 30 35 40 45 50 55 60 65 ...

Страница 16: ...gertemperatur 20 80 C nicht kondensierend Spezifikationen Gewicht 0 975 kg Spannungsversorgung 24 VAC DC 50 60 Hz Stromaufnahme 5 W 2 5 W Standby Betrieb Verbindungskabel Länge 0 25 m Verbindung zum Ventil 8 mm Vierkant Einfache Montageausrüstung Betriebsdauer 50 000 Zyklen Stellsignal 0 2 10 V 250 kΩ Last 0 4 20 mA 500 Ω Last AUF ZU 24 VAC DC 30 mA AC 6 mA DC 3 Pkt Steuerung 24 VAC DC 30 mA AC 6 ...

Отзывы: