Honeywell V4295A,S Скачать руководство пользователя страница 8

V4295A,S; V8295A,S SOLENOID GAS VALVES

Automation and Control Solutions

Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN  55422

Toronto, Ontario  M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark
© 2009 Honeywell International Inc.
65-0194—04    M.S.  Rev. 02-09

1. If the valve will not open when the thermostat or 

controller is calling for heat:

a. Check that there is voltage at the valve actuator 

lead wires or terminal block.

CAUTION

Line voltage (120 Vac) should be present when the 

primary safety control energizes the V4295A,S 

valve actuator. 24 Vac should be present when the 

primary safety control energizes the V8295A,S 

valve actuator.

b. If there is no voltage at the actuator, first ensure line 

voltage power is connected to the master switch, the 

master switch is closed and overload protection (cir-

cuit breaker, fuse or similar device) has not opened 

the power line.

c. If there is still no voltage at the actuator, make sure 

all appropriate contacts in the thermostat (or control-

ler), limit(s) and flame safeguard control are closed. 

If one or more are open, determine the cause(s) and 

correct condition(s) before proceeding.

d. If there is proper voltage at the actuator but the 

valve still does not open, first check that the gas 

pressure is normal.

e. If the valve still does not open, replace valve.

2. If the valve will not close when one or more of the 

appropriate contacts in the thermostat (or control-

ler), limit(s) or flame safeguard control is open:

a. Make sure that the gas flow is in the direction of the 

arrow on the valve body.

b. Make sure the valve actuator is wired in the correct 

circuit. Open the master switch to remove power 

from the actuator. If the valve closes now, the actua-

tor may not be wired properly.

c. Look for a short in the electrical circuit.

SERVICE INFORMATION

CAUTION

1. Only qualified service technicians should 

attempt to service or repair flame safeguard 

control and burner.

2. Line voltage is present in the electrical circuits 

to the valve. Open the master switch before 

replacing the valve.

CAUTION

1. Label all wires prior to disconnection when 

servicing valves. Wiring errors can cause 

improper and dangerous operation.

2. Verify proper operation after servicing.

Scheduled inspection and maintenance

For periodic inspection and maintenance, set up a schedule 

and follow it. Include the burner, valves and all other burner 

controls. It is recommended that “Valve Leak Test (Fig. 8)” on 

page 6 be included in the schedule. Refer to the flame 

safeguard control instructions for more information.

Содержание V4295A,S

Страница 1: ...dels for vent double block and bleed valve applications consist of a direct electric on off operator for closing and opening of the valve Models are suitable for the control of gaseous fluids in gas consuming appliances according to international standards Models have 1 4 inch NPT inlet and outlet pressure taps Models have inlet screen to protect the valve from the entry of dirt SPECIFICATIONS Mod...

Страница 2: ...Models Available Model Voltage Frequency Maximum Pressure Pipe size inch Thread type psi mbar V4295A N C 110 120 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 NPT V4295A N C 110 120 Vac 50 60 Hz 5 0 350 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V4295S N O 110 120 Vac 50 60 Hz 2 0 140 3 4 1 1 1 4 NPT V8295A N C 24 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V8295S N O 24 Vac 50 60 Hz 2 0 ...

Страница 3: ... 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA X 100 Vg NATURAL GAS SG 0 64 CFH P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN 2 1 2 IN 3 IN M28667 6 24 5 20 4 16 3 12 2 8 1 4 0 8 3 2 0 6 2 4 0 5 2 0 0 4 1 6 0 3 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN X 1...

Страница 4: ...8662 E Table 4 Normally Closed See Fig 3 Pipe size A inch B inch C inch D inch E inch both sides Weight lbs 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 3 8 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 1 2 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 3 4 in NPT 3 7 16 5 1 4 5 13 16 2 3 16 2 1 2 3 3 4 4 1 16 2 3 4 4 0 4 4 1 in NPT 3 15 16 5 1 4 6 5 1...

Страница 5: ...far thest from the pipe being inserted may distort the cast ing resulting in malfunction on the gas valve 6 The gas flow must be in the same direction as the arrow on the body of the valve WARNING If the flow is not in the same direction of arrow valve may not shut off Fig 5 Mounting position 7 Make electrical connections as illustrated in the wiring diagrams see Fig 6 8 Turn on main gas and with ...

Страница 6: ... valve and make sure valve is closed when setting up pressure measuring equipment 3 Set thermostat or controller to energize the valve and check final outlet pressure 4 Start the system and observe its operation through at least one complete cycle to ensure the valve functions as described in the section Operation on page 6 Valve Leak Test Fig 8 This is a test for checking the closure tightness of...

Страница 7: ...em to normal operation If two safety shutoff valves are used check each valve separately for closure tightness TROUBLESHOOTING CAUTION Use utmost care during troubleshooting Line voltage is present at the actuator for V4295A S and present in controller circuits Low voltage 24 Vac is present at the actuator for V8295A S and present in controller circuits IMPORTANT Do not assume that the valve must ...

Страница 8: ...eeding d If there is proper voltage at the actuator but the valve still does not open first check that the gas pressure is normal e If the valve still does not open replace valve 2 If the valve will not close when one or more of the appropriate contacts in the thermostat or control ler limit s or flame safeguard control is open a Make sure that the gas flow is in the direction of the arrow on the ...