INSTALLATION INSTRUCTIONS

65-0194-04

V4295A,S; V8295A,S 

Solenoid Gas Valves

APPLICATION

The electrically operated V4295A, S and V8295A, S Solenoid 

Gas Valves control the flow of natural and LP (liquefied 

petroleum) gases.

These valves are used on atmospheric boilers, commercial 

water heaters, roof-top make-up air burners, power burners 

and boilers.

FEATURES

• V4295A,S are used with 120 Vac controllers;

V8295A,S are used with 24 Vac controllers.

• Models available in Normally Closed and Normally 

Open configurations.

• Normally Closed models, for safety shut-off 

applications, consist of a direct on/off operator for 

opening and closing of the valve.

• Normally Open models, for vent (double block and 

bleed) valve applications, consist of a direct electric 

on/off operator for closing and opening of the valve.

• Models are suitable for the control of gaseous fluids in 

gas consuming appliances according to international 

standards.

• Models have 1/4 inch NPT inlet and outlet pressure 

taps.

• Models have inlet screen to protect the valve from the 

entry of dirt.

SPECIFICATIONS

Models

V4295A Normally Closed (N.C.) Safety shut-off Valve, 120V

V4295S Normally Open (N.O.) Vent Valve, 120V

V8295A Normally Closed (N.C.) Safety shut-off Valve, 24V

V8295S Normally Open (N.O.) Vent Valve, 24V

Type of gas

Air, Natural, Manufactured, Mixed and LP gas.

Valve capacities

Refer to Figures 1 and 2

Valve pattern

Straight through, non-offset

Body Material

Die cast aluminum

Electrical terminations

Screw terminal connections

Valve opening time

Less than 1 second

Содержание V4295A,S

Страница 1: ...dels for vent double block and bleed valve applications consist of a direct electric on off operator for closing and opening of the valve Models are suitable for the control of gaseous fluids in gas consuming appliances according to international standards Models have 1 4 inch NPT inlet and outlet pressure taps Models have inlet screen to protect the valve from the entry of dirt SPECIFICATIONS Mod...

Страница 2: ...Models Available Model Voltage Frequency Maximum Pressure Pipe size inch Thread type psi mbar V4295A N C 110 120 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 NPT V4295A N C 110 120 Vac 50 60 Hz 5 0 350 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V4295S N O 110 120 Vac 50 60 Hz 2 0 140 3 4 1 1 1 4 NPT V8295A N C 24 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V8295S N O 24 Vac 50 60 Hz 2 0 ...

Страница 3: ... 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA X 100 Vg NATURAL GAS SG 0 64 CFH P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN 2 1 2 IN 3 IN M28667 6 24 5 20 4 16 3 12 2 8 1 4 0 8 3 2 0 6 2 4 0 5 2 0 0 4 1 6 0 3 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN X 1...

Страница 4: ...8662 E Table 4 Normally Closed See Fig 3 Pipe size A inch B inch C inch D inch E inch both sides Weight lbs 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 3 8 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 1 2 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 3 4 in NPT 3 7 16 5 1 4 5 13 16 2 3 16 2 1 2 3 3 4 4 1 16 2 3 4 4 0 4 4 1 in NPT 3 15 16 5 1 4 6 5 1...

Страница 5: ...far thest from the pipe being inserted may distort the cast ing resulting in malfunction on the gas valve 6 The gas flow must be in the same direction as the arrow on the body of the valve WARNING If the flow is not in the same direction of arrow valve may not shut off Fig 5 Mounting position 7 Make electrical connections as illustrated in the wiring diagrams see Fig 6 8 Turn on main gas and with ...

Страница 6: ... valve and make sure valve is closed when setting up pressure measuring equipment 3 Set thermostat or controller to energize the valve and check final outlet pressure 4 Start the system and observe its operation through at least one complete cycle to ensure the valve functions as described in the section Operation on page 6 Valve Leak Test Fig 8 This is a test for checking the closure tightness of...

Страница 7: ...em to normal operation If two safety shutoff valves are used check each valve separately for closure tightness TROUBLESHOOTING CAUTION Use utmost care during troubleshooting Line voltage is present at the actuator for V4295A S and present in controller circuits Low voltage 24 Vac is present at the actuator for V8295A S and present in controller circuits IMPORTANT Do not assume that the valve must ...

Страница 8: ...eeding d If there is proper voltage at the actuator but the valve still does not open first check that the gas pressure is normal e If the valve still does not open replace valve 2 If the valve will not close when one or more of the appropriate contacts in the thermostat or control ler limit s or flame safeguard control is open a Make sure that the gas flow is in the direction of the arrow on the ...

Отзывы: