V4295A,S; V8295A,S SOLENOID GAS VALVES

65-0194—04

6

Fig. 6. Wiring, V4295A,S.

Fig. 7. Wiring, V8295A,S.

OPERATION

The V4295A and V8295A Normally Closed series gas valves 

are Class B fail safe shut off valves. The valve is opened by 

energizing the direct ON/OFF operator. The direct ON/OFF 

operator consists of a coil and stop sleeve assembly. Inside 

the stop sleeve assembly is a plunger which is able to move 

up and down, thus opening or closing the valve. The plunger 

glides on two anti-friction bearings. A strainer, made of AISI 

303 stainless steel, is incorporated into the valve.

CHECKOUT AND TROUBLESHOOTING

WARNING

Do not allow fuel to accumulate in the combustion 

chamber. If fuel is allowed to enter the chamber for 

longer than a few seconds without igniting, an 

explosive mixture could result.

CAUTION

1. Do not put the system into service until you 

have satisfactorily completed all applicable tests 

described in the Checkout section of the 

instructions for the flame safeguard control and 

any other test required by the burner 

manufacturer.

2. Close 

all

 manual fuel shut off valves as soon as 

trouble occurs.

CHECKOUT

1.

Check the performance of the valve by measuring the 

pressures at the inlet and outlet pressure taps. The 

pressure reading at the outlet tap may be slightly higher 

than a downstream measurement due to dynamic gas 

flow effects. The measurement at the outlet tap is for 

reference only.

2.

Shut off gas supply to valve and make sure valve is 

closed when setting up pressure measuring equipment.

3.

Set thermostat or controller to energize the valve and 

check final outlet pressure.

4.

Start the system and observe its operation through at 

least one complete cycle to ensure the valve functions 

as described in the section “Operation” on page 6.

Valve Leak Test (Fig. 8)

This is a test for checking the closure tightness of the gas 

safety shutoff valve. It should be performed only by trained, 

experienced flame safeguard control technicians during the 

initial startup of the burner system or whenever the valve is 

replaced (see Service Information section). It is recommended 

that this test also be included in the scheduled inspection and 

maintenance procedures.

1.

De-energize the control system to make sure no power 

goes to the valve (

C

, Fig. 8).

2.

Close the upstream manual gas cock (

A

).

3.

Make sure the manual test petcock (

F

) is closed in the 

leak test tap assembly (

D

).

4.

Remove the leak test tap plug and connect the test 

apparatus to the leak test tap (

D

).

5.

Close the downstream manual gas cock (

E

).

6.

Open the upstream manual gas cock (

A

).

7.

Run the V4/8295A Valve to is open position (through the 

safety system); then immediately de-energize the sys-

tem to close the V4/8295A Valve.

8.

Immerse a 1/4 in. (6 mm) tube vertically 1/2 in. (13 mm) 

into a jar of water.

9.

Slowly open the manual test petcock (

F

).

M28664

120 VAC

GROUND

G

4

N

L

9

NEUTRAL

LINE

VOLTAGE

MAIN VALVE

V4295A,S

RM7800

(TYPICAL)

L2

M28665

LIMIT(S)

TRANSFORMER

L1
(HOT)

L2

V8295A,S

G

N

L

24 VOLT
THERMOSTAT

FLAME
SAFEGUARD
CONTROL

POWER SUPPLY. PROVIDE DISCONNECT 
MEANS AND OVERLOAD PROTECTION 
AS REQUIRED.

Содержание V4295A,S

Страница 1: ...dels for vent double block and bleed valve applications consist of a direct electric on off operator for closing and opening of the valve Models are suitable for the control of gaseous fluids in gas consuming appliances according to international standards Models have 1 4 inch NPT inlet and outlet pressure taps Models have inlet screen to protect the valve from the entry of dirt SPECIFICATIONS Mod...

Страница 2: ...Models Available Model Voltage Frequency Maximum Pressure Pipe size inch Thread type psi mbar V4295A N C 110 120 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 NPT V4295A N C 110 120 Vac 50 60 Hz 5 0 350 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V4295S N O 110 120 Vac 50 60 Hz 2 0 140 3 4 1 1 1 4 NPT V8295A N C 24 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V8295S N O 24 Vac 50 60 Hz 2 0 ...

Страница 3: ... 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA X 100 Vg NATURAL GAS SG 0 64 CFH P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN 2 1 2 IN 3 IN M28667 6 24 5 20 4 16 3 12 2 8 1 4 0 8 3 2 0 6 2 4 0 5 2 0 0 4 1 6 0 3 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN X 1...

Страница 4: ...8662 E Table 4 Normally Closed See Fig 3 Pipe size A inch B inch C inch D inch E inch both sides Weight lbs 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 3 8 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 1 2 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 3 4 in NPT 3 7 16 5 1 4 5 13 16 2 3 16 2 1 2 3 3 4 4 1 16 2 3 4 4 0 4 4 1 in NPT 3 15 16 5 1 4 6 5 1...

Страница 5: ...far thest from the pipe being inserted may distort the cast ing resulting in malfunction on the gas valve 6 The gas flow must be in the same direction as the arrow on the body of the valve WARNING If the flow is not in the same direction of arrow valve may not shut off Fig 5 Mounting position 7 Make electrical connections as illustrated in the wiring diagrams see Fig 6 8 Turn on main gas and with ...

Страница 6: ... valve and make sure valve is closed when setting up pressure measuring equipment 3 Set thermostat or controller to energize the valve and check final outlet pressure 4 Start the system and observe its operation through at least one complete cycle to ensure the valve functions as described in the section Operation on page 6 Valve Leak Test Fig 8 This is a test for checking the closure tightness of...

Страница 7: ...em to normal operation If two safety shutoff valves are used check each valve separately for closure tightness TROUBLESHOOTING CAUTION Use utmost care during troubleshooting Line voltage is present at the actuator for V4295A S and present in controller circuits Low voltage 24 Vac is present at the actuator for V8295A S and present in controller circuits IMPORTANT Do not assume that the valve must ...

Страница 8: ...eeding d If there is proper voltage at the actuator but the valve still does not open first check that the gas pressure is normal e If the valve still does not open replace valve 2 If the valve will not close when one or more of the appropriate contacts in the thermostat or control ler limit s or flame safeguard control is open a Make sure that the gas flow is in the direction of the arrow on the ...

Отзывы: