background image

UVL-FCU ULTRAVIOLET LAMP KITS FOR FAN COIL AND PTAC UNITS

31-00403—02

4

CAUTION

Breakable Glass Hazard.
Can cause personal injury.

Be careful when inserting bulb(s) into lamp base. 
Wear protective gloves when handling bulb(s).

MERCURY NOTICE

This device contains mercury in the sealed 
ultraviolet bulb(s). Do not place your used bulb(s) 
in the trash. Dispose of properly.

Broken Bulb Cleanup.

Do not use a household vacuum. Sweep debris into a 
plastic bag and dispose of properly.

Contact your local waste management authority for 
instructions regarding recycling and the proper disposal 
of old bulb(s).

Power Supply Installation

IMPORTANT

The UVL-FCU components are designed to with-
stand the typical ambient temperatures found 
near fan coil and PTAC heating elements up to a 
constant 194°F (90°C). If installing the lamp near 
a heating element, secure the wires as far away 
from the heating elements’ wires as possible to 
prevent them from touching the element. In addi-
tion, use the included slit loom tubing for addi-
tional protection of the power supply wires that 
may be mounted near the heating elements.

Find a suitable location for the power supply inside the 
control panel of the air handler. Install using the self-
tapping screws. 

Fig. 5. Power Supply Installation

Sight Glass Installation

Sight glass may not be needed if reflected UV light is 
visible.

1.

Find a suitable location on the outside of the unit 
near the UV lamp installation and apply the warn-
ing/lamp replacement sticker.

2.

Drill a ½ inch hole through the orange circle on the 
sticker. Press the UV safety viewport into the hole.

3.

When power is connected the sight glass can be 
used to confirm the UV lamp is operating.

Fig. 6. Sight Glass Installation

WIRING

WARNING

Electric Shock Hazard.
Can cause personal injury.

Turn off main power before making electrical 
connections.

IMPORTANT

Check which power supply is included with your 
UVL-FCU kit before connecting to power.

Use the wiring diagrams below (Fig. 7) to connect to 
power. The low voltage power supply (18 to 32 VAC) is 
marked “LOW”. The high voltage (120 to 277 VAC) power 
supply is marked “LINE”.

 18 - 32 VAC Power Supply

 110 - 277 VAC Power Supply

24 VAC

Содержание UVL-FCU-LINE

Страница 1: ...ic mounting hardware and panel indicator SPECIFICATIONS Models See Table 1 Efficiencies 99 9 disinfection of irradiated surfaces when properly positioned Approvals ETL CSA RoHS standard 2011 65 EU EPA Est No 075179 FL 2 Electrical Ratings Power Rating UVL FCU LINE 120 277 Vac 50 60 Hz UVL FCU LOW 18 32 Vac 60Hz Current Rating UVL FCU LINE 0 51 A 120 Vac 0 22 A 277 Vac UVL FCU LOW 0 68 A 16 VA Dime...

Страница 2: ...se Kit includes one power supply LOW or LINE depending on model Fig 1 Parts WARNING Be careful of damage to equipment Ultraviolet light can cause color fading or degraded structure of plastic material found in HVAC equipment avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation WARNING UV Light Hazard Harmful to bare skin and eyes Can cau...

Страница 3: ...d Can cause electrical shock or equipment damage Do not connect to power before installation is complete Installation in PTACs and Fan Coils 1 Determine the best position for placement of the UV lamp and power supply Fig 2 Fig 4 2 Position lamp for best UV exposure and to minimize light leakage into the room 3 Locate lamp so it irradiates wet side of coil and or blower areas where fouling is prese...

Страница 4: ...uded slit loom tubing for addi tional protection of the power supply wires that may be mounted near the heating elements Find a suitable location for the power supply inside the control panel of the air handler Install using the self tapping screws Fig 5 Power Supply Installation Sight Glass Installation Sight glass may not be needed if reflected UV light is visible 1 Find a suitable location on t...

Страница 5: ...f grease or other contaminants and are NOT affected by humidity They are warranted for 2 years of UVC output to 60 of their original output Sizing guidelines are based on the end of lamp life output levels Honeywell UV lamps are rated for two years germicidal effectiveness The visible blue light will continue to illuminate but does NOT have any germicidal effectiveness Bulbs must be replaced on sc...

Отзывы: