background image

UVL-FCU ULTRAVIOLET LAMP KITS FOR FAN COIL AND PTAC UNITS

Honeywell Building Technologies

In the U.S.:

Honeywell

715 Peachtree Street NE

Atlanta, GA 30308

customer.honeywell.com

buildingcontrols.honeywell.com

® U.S. Registered Trademark
©2020 Honeywell International Inc.
31-00403—02   M.S.  Rev. 09-20
Printed in United States

Fig. 7. Electrical Connections

Connect Lamps and Cables

When all the other components are properly installed 
connect the UV lamp cable to the power supply cable. 
Make sure the flanges are aligned and then push the 
connectors firmly together. A tight connection ensures a 
proper water-resistant seal.

Fig. 8. UV Lamp Connection

MAINTENANCE

Honeywell UVC lights are made of Hard Quartz.  Unlike 
Soft Quartz, these lamps do NOT need to be wiped of 
grease or other  contaminants, and are NOT affected by 
humidity.  They are warranted for 2 years of UVC output, to 
60% of their original output.   Sizing guidelines are based 
on the end of lamp life output levels.  

Honeywell UV lamps are rated for two years germicidal 
effectiveness. The visible blue light will continue to 
illuminate, but does NOT have any germicidal 
effectiveness. Bulbs must be replaced on schedule for the 
system to function properly.

IMPORTANT

Use only Honeywell replacement lamps. Use of 
replacement lamps from other manufacturers 
voids the warranty. See Table 1 
for replacement 
lamp part numbers.

120-277 VAC

POWER SUPPLY

UV LAMP

BLUE CABLE

DISCONNECT

L1-BLACK
L2 or N-WHITE
GND-GREEN

Line-voltage 

"LINE"

 wiring

IMPORTANT! Must be wired to constant power - do not connect to blower relay.

AIR HANDLER

24 VAC

TRANSFORMER

24 VAC

POWER SUPPLY

UV LAMP

BLUE CABLE

BLACK

RED

Low-voltage 

"LOW"

 wiring

24 VAC TRANSFORMER

COMMON / BLUE

HOT / RED

Align Flanges

2. 

1. 

Содержание UVL-FCU-LINE

Страница 1: ...ic mounting hardware and panel indicator SPECIFICATIONS Models See Table 1 Efficiencies 99 9 disinfection of irradiated surfaces when properly positioned Approvals ETL CSA RoHS standard 2011 65 EU EPA Est No 075179 FL 2 Electrical Ratings Power Rating UVL FCU LINE 120 277 Vac 50 60 Hz UVL FCU LOW 18 32 Vac 60Hz Current Rating UVL FCU LINE 0 51 A 120 Vac 0 22 A 277 Vac UVL FCU LOW 0 68 A 16 VA Dime...

Страница 2: ...se Kit includes one power supply LOW or LINE depending on model Fig 1 Parts WARNING Be careful of damage to equipment Ultraviolet light can cause color fading or degraded structure of plastic material found in HVAC equipment avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation WARNING UV Light Hazard Harmful to bare skin and eyes Can cau...

Страница 3: ...d Can cause electrical shock or equipment damage Do not connect to power before installation is complete Installation in PTACs and Fan Coils 1 Determine the best position for placement of the UV lamp and power supply Fig 2 Fig 4 2 Position lamp for best UV exposure and to minimize light leakage into the room 3 Locate lamp so it irradiates wet side of coil and or blower areas where fouling is prese...

Страница 4: ...uded slit loom tubing for addi tional protection of the power supply wires that may be mounted near the heating elements Find a suitable location for the power supply inside the control panel of the air handler Install using the self tapping screws Fig 5 Power Supply Installation Sight Glass Installation Sight glass may not be needed if reflected UV light is visible 1 Find a suitable location on t...

Страница 5: ...f grease or other contaminants and are NOT affected by humidity They are warranted for 2 years of UVC output to 60 of their original output Sizing guidelines are based on the end of lamp life output levels Honeywell UV lamps are rated for two years germicidal effectiveness The visible blue light will continue to illuminate but does NOT have any germicidal effectiveness Bulbs must be replaced on sc...

Отзывы: