UVL-FCU ULTRAVIOLET LAMP KITS FOR FAN COIL AND PTAC UNITS
Honeywell Building Technologies
In the U.S.:
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
buildingcontrols.honeywell.com
® U.S. Registered Trademark
©2020 Honeywell International Inc.
31-00403—02 M.S. Rev. 09-20
Printed in United States
Fig. 7. Electrical Connections
Connect Lamps and Cables
When all the other components are properly installed
connect the UV lamp cable to the power supply cable.
Make sure the flanges are aligned and then push the
connectors firmly together. A tight connection ensures a
proper water-resistant seal.
Fig. 8. UV Lamp Connection
MAINTENANCE
Honeywell UVC lights are made of Hard Quartz. Unlike
Soft Quartz, these lamps do NOT need to be wiped of
grease or other contaminants, and are NOT affected by
humidity. They are warranted for 2 years of UVC output, to
60% of their original output. Sizing guidelines are based
on the end of lamp life output levels.
Honeywell UV lamps are rated for two years germicidal
effectiveness. The visible blue light will continue to
illuminate, but does NOT have any germicidal
effectiveness. Bulbs must be replaced on schedule for the
system to function properly.
IMPORTANT
Use only Honeywell replacement lamps. Use of
replacement lamps from other manufacturers
voids the warranty. See Table 1 for replacement
lamp part numbers.
120-277 VAC
POWER SUPPLY
UV LAMP
BLUE CABLE
DISCONNECT
L1-BLACK
L2 or N-WHITE
GND-GREEN
Line-voltage
"LINE"
wiring
IMPORTANT! Must be wired to constant power - do not connect to blower relay.
AIR HANDLER
24 VAC
TRANSFORMER
24 VAC
POWER SUPPLY
UV LAMP
BLUE CABLE
BLACK
RED
Low-voltage
"LOW"
wiring
24 VAC TRANSFORMER
COMMON / BLUE
HOT / RED
Align Flanges
2.
1.