Function Blocks
Function Block Reference Guide
3/99
64
2.18 DEWP Function Block,
continued
Table 2-19 Dewpoint Function Block Parameters
Properties Group
Parameter
Index#
Parameter Description
Value or Selection
Furnace
Properties
Furnace
Factor
2
Allows you to adjust the %
Carbon as measured by the
controller to agree with the
results of actual shim stock
tests. This adjustment may
be needed to correct for
specific furnace
characteristics such as
atmosphere differences,
probe location, and furnace
leaks.
-0.5 to +0.5%C
3
Activates anti-sooting feature
that limits the working
setpoint of the carbon control
loop to a value that prevents
sooting in the furnace.
Click on block to select
SP HLIM is used for anti-
soot.
Low
Temperature
Limit
5
Holds controller output to 0%
until limit is exceeded.
0 to 2500 degrees F
(1400
°
recommended)
Unit should match C/F
selection
4
Probe temperature units for
display.
Click on radio button
to select
Percent
Hydrogen
7
Percent Hydrogen
1 to 100
default = 40
CO Properties
%CO
0
Allows you to adjust %
Carbon measurement to
compensate for variations in
the amount of CO in the
carrier gas.
2.0 to 35.0
default = 20
1
Function block will use the
actual %Carbon Monoxide
that is defined through an
analog input.
Click on block to select
O2 Probe
Manufacturer
Carbon Probe
Manufacturer
N/A
Select from Drop Down List
of Manufacturers.
•
Advanced
Atmosphere Control
Corp.
•
Furnace
Control
Corp.
•
Marathon
Monitors
•
Super Systems Inc.