Function Blocks
Function Block Reference Guide
3/99
124
2.45 ON/OFF Function Block,
continued
Configuration Parameters,
continued
RANGE/LIMIT
TAB, continued
Table 2-36 Range/Limit Tab Configuration Parameters
Properties
Function
Parameter
Index#
Parameter Description
Value or Selection
Ranging
PV High
range
0
PV High Range Value
-99999 to 99999
PV Low
Range
1
PV Low Range Value
-99999 to 99999
Display
Decimal
Places
N/A
Number of digits to display after
decimal point.
0 to 5
Units
N/A
Text to display for EU
4 characters
DEV Bar
Range (EU)
N/A
Deviation Bar Range on the
Operator Interface
-99999 to 99999
Limiting
SP High Limit
6
Setpoint High Limit Value -
prevents the local and remote
setpoints from going above the
value set here.
-99999 to 99999
SP Low limit
7
Setpoint Low Limit Value -
prevents the local and remote
setpoints from going below the
value set here.
-99999 to 99999
SP Rate
Down
9
Setpoint Rate Down value -
when making a setpoint
change, this is the rate at which
setpoint will change from the
original setpoint
down
to the
new one.
0 (off) to 9999 (eu/min)
SP Rate Up
10
Setpoint Rate Up value - when
making a setpoint change, this
is the rate at which setpoint will
change from the original
setpoint
up
to the new one.
0 (off) to 9999 (eu/min)
Continued next page