background image

T8024D PROGRAMMABLE MULTISTAGE THERMOSTAT

69-1387-1

4

Slide the SYSTEM switch in the bottom right corner of 
the thermostat to select the desired system setting.

Fig. 7. Digital display and system 

switches (FAN and SYSTEM).

INSTALLER SETUP

Setting °F/°C Indication and Heat 
Cycle Rate

The following instructions provide information to change 

the heating cycle rate to match the heating equipment 
and to choose either Fahrenheit (°F) or Celsius (°C).

NOTE:  All four steps must be completed to save 

changes to °F/°C indication and heat cycle rate.

1.

Enter Installer Setup.
a. Use 

 or 

 key to set the temperature setpoint 

to 52°F (11°C)

.

b. Press the 

 and 

 keys simultaneously for 

more than two seconds to enter installer setup.

c. When released, a software revision code is dis-

played.

d. Press the 

 key. Factory configuration (FC) is 

displayed A typical example is shown, but infor-

mation displayed varies by model. This infor-
mation is for factory use only.

OPTIONAL SYSTEM CHECKOUT 

When in steps 1c and 1d only, pressing the 

▼ 

key can be 

used to turn heat or cool outputs on and off. Change the 
SYSTEM switch setting to test heat or cool outputs. No 

action takes place If the system switch is in the Off 
position.

Examples:System setting at HEAT: If heat is on, pressing 

the 

 key turns it off; if heat is off, pressing the 

 key 

turns it on.

System setting at COOL: If cool is on, pressing the 

 

key turns it off; if cool is off, pressing the 

 key turns it 

on. The five minute minimum off time is bypassed.

CAUTION

Equipment Damage Hazard.

Can short equipment.

Allow compressor to remain off for 5 minutes 

before restarting. Refer to manufacturer 
recommendations.

NOTE: In Installer Setup only, each press of the 

 key 

momentarily displays 1. Each press of the 

 

key momentarily displays 2. When the keys are 

released, these one-digit codes are no longer 
displayed. 

2.

Setting °C or °F.

a. Press the 

 key again to display the current 

setting.

b. Press the 

▼ 

key to change the °C or °F 

indication.

3.

Setting Number of Cool/Heat Stages (T8024 only). 

a. Press 

 to display number of cooling stages.

SYST

EM

Cool  Of

f  Heat 

Auto  On

FAN

T8024

M18504

Hold

Select

TUE

PM

M12582A

SET

HT.

M12583A

SET

HT.

M12584A

M12587A

M12586A

M20216

Содержание Tradeline T8024D

Страница 1: ...duct is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation Location Install the thermostat about 5 ft 1 5m above the f...

Страница 2: ...e shape of the terminals permits insertion of straight or wraparound wiring connections either method is acceptable See Fig 4 The T8024 Thermostat is powered through the system transformer and is adaptable to most 24 Vac multistage heating cooling systems Refer to Fig 5 for typical wiring hookups Fig 3 Restrict wiring to shaded area 5 FEET 1 5 METERS YES NO NO NO M11338 M12202A WALL WALL ANCHORS 2...

Страница 3: ...nutes after the heating equipment turns on on most systems When using an electric heat thermostat the fan starts and stops with the heating equipment Slide the FAN switch in the bottom left corner of the thermostat to select the desired fan setting SYSTEM Switch System switch settings control thermostat operation as follows Cool The thermostat controls the cooling system Off Both heating and cooli...

Страница 4: ... 1d only pressing the key can be used to turn heat or cool outputs on and off Change the SYSTEM switch setting to test heat or cool outputs No action takes place If the system switch is in the Off position Examples System setting at HEAT If heat is on pressing the key turns it off if heat is off pressing the key turns it on System setting at COOL If cool is on pressing the key turns it off if cool...

Страница 5: ...ey to save all changes and return to normal operation Table 1 Heating Cycle Rates for Stage Two Heating a High efficiency furnace bRefer to equipment manufacturer s instructions PROGRAMMING The thermostat is flexible and can be programmed for different schedules for weekdays and weekends Four time periods are available during weekdays and weekends WAKE LEAVE RETURN and SLEEP IMPORTANT Always press...

Страница 6: ...C Refer to manufacturer s recommendations Allow compressor to remain off for five minutes before restarting 1 Slide the SYSTEM switch to Cool and the FAN switch to Auto 2 Press the key to lower the temperature setting several degrees below the room temperature After approximately five minutes the cooling equipment should start The fan starts and stops with the cool ing equipment 3 Press the key to...

Отзывы: