53
TR80 - Installation and Operation Guide
3. 14. 5 Light Group 4 configuration & control
The group 3 configuration parameters are explained in below table. Refer lighting group1 for
explanation.
The group 3 control parameters are explained in below table
.
Refer lighting group1 for
explanation.
3. 14. 6 Scene definitions for Power Button
If the power button is configured to turn lights on/off (see register 2110/2111, config parame
-
ter 108/109), the wall module will need to know what scenes to recall for that purpose. Set to
zero if no such scene is configured on the DALI side. If set to zero, TR80 will send absolute light
level commands (0% / 100%) to turn lights off / on.
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
Parameter
Unit
Range
Default
value
Holding
2314
42315
R/W
Light Group 4
allow dimming
314
enum
0: only on/off
control
1: allow dimming
1
Holding
2315
42316
R/W
Light Group 4
min level
315
%
0…100%
1%
Holding
2316
42317
R/W
Light Group 4
max level
316
%
0…100%
100%
Holding
2317
42318
R/W
Light Group 4
max Scene No
317
int
0-16
4
Register
type
Relative
Address
Absolute
Address
Dir
Name
Unit
Range
Default
value
Holding
1306
41307
R/W
Light Group 4 last level
%
0-100%
(255: unknown)
255
Holding
1307
41308
R/W
Light Group 4 last scene
int
0-15
(255: unknown)
255
Input
306
30307
R/W
Light Group 4 new level
%
0-100%
32767
Input
307
30308
R/W
Light Group 4 new scene
int
0-15
32767
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Unit
Range
Default
value
Holding
2318
42319
R/W
Scene For Lights ON
318
Int
0-16
0
Holding
2319
42320
R/W
Scene For Lights OFF
319
Int
0-16
0