TR80 - Installation and Operation Guide
3. Modbus with override from button: In this case, the master controller determines the
occupancy mode based on a time schedule, presence detector and/or other inputs.
However, the user may be allowed to override the current mode using the occupancy
button.This allows user to select further modes such as holiday or bypass.
3. 13. 2 Occupancy control
The master controller should read the user selected occupancy mode from the ‘Effective Occu
-
pancy Mode’ register. This is the register that reflects the current effective mode and that is
used for display on the wall module.
Unless the very simple, button-only selection mode is being used, the master controller should
also write its calculated occupancy mode to the ‘master occupancy mode’ register. This is nec
-
essary for display, override functionality and to determine which overrides are allowed. It would
typically be occupied, unoccupied, standby or off.
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Type
Range
Default
value
Holding
2500
42501
R/W
Occupancy
Source
500
enum
0: Modbus only
1: Button only
2: Modbus &
override from
button
0
Register
type
Relative
Address
Absolute
Address
Dir
Name
Type
Range
Default
value
Holding
1500
41501
R/W
Master
Occupancy Mode
enum
0: unknown
1: not used
2: occupied
3: off
4: holiday
5: unoccupied
6: standby
7: bypass
0
Holding
1501
41502
R/W
User Occupancy
Mode
enum
0: auto
1: not used
2: occupied
3: off
4: holiday
5: unoccupied
6: standby
7: bypass
0
Input
500
30501
R
Effective
Occupancy Mode
enum
0: unknown
1: not used
2: occupied
3: off
4: holiday
5: unoccupied
6: standby
7: bypass
0
Input
501
30502
R
Occupancy
Override Status
enum
0: not overriden
1: overriden
0