TR80 - Installation and Operation Guide
3.3 Temporary Commissioning Mode
User can set TR80 in a temporary commissioning mode, by setting time in parameter 17.
• The sleep mode will not be activated on timeout. The display will remain on.
• The protected mode will not be activated on timeout. The device will remain unlocked.
• Entering the configuration menu will not require PIN.
• The symbol
will be flashing.
This mode can be set up to 336 hours (14 days). It can be cancelled at any time by setting the
same parameter to 0.
3.4 Factory Reset
The factory reset procedure is as follows:
1. Turn off and turn ON the unit .
2. Wait until the version info is displayed.
3. Press and hold for 30 seconds.
Device will restart and all parameter values will return to default value.
3.5 DEVICE
3. 5. 1 Save Changes
When configuration parameters are modified through the TR80 keypad, the changes are
immediately saved to flash memory. However, when parameters are changed by a master con
-
troller via Modbus, they are saved in volatile memory, to save the parameters in non-volatile
flash memory use below.
The master controller needs to write a value of 1 (true) to this register to commit changes to
flash memory. The write to flash memory only occurs on a change from 0 to 1.The text 'SAVE' on
the screen is displayed when this function is triggered.
Register
type
Relative
Address
Absolute
Address
Dir
Name
Default value
Coil
0
00001
W
Save Changes
0