For mounting on a flush wallbox of depth greater than 25mm.
•
Wiring to terminals must be done before wallplate is screwed to wallbox.
•
Product requires a permanent 230Vac mains power supply to operate
•
Switch output is potential-free 24V … 230Vac
•
Installation should be carried out by a competent person.
•
All wiring must be in accordance with IEE regulations.
•
This unit is for fixed wiring only.
•
A switch, having contact separation of at least 3mm in all poles must be incorporated in the
fixed wiring as a means of disconnecting the supply.
•
The system must be appropriately fused. A fuse rating of no more than 5Amps should be installed.
•
The unit is Class II (double insulated ) so device earthing is not required. A hook is provided for
parking an earth wire.
Installation notes — read these prior to installation