T8611G CHRONOTHERM

®

 IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT

68-0165—1

22

Table 14. Thermostat Cross Reference Information (continued).

Model  

Number

Description

TRADELINE®

Replacement

Remarks

T8611R1067

ArcoAire; part no. 1506-744.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal.

T8611R1075

Comfortmaker.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal.

T8611R1083

Amana; part no. D9807605.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal.

T8611R1091

Trane.

T8611G2002

Wiring differences (old=new): B=C, F=L,
X2=E, W1=W2; configure O/B terminal to  
O in Installer Setup 29; jumper W1 to Y1.

T8611R1109

Trane; part no. THT-0602; ordering no.
X13510323-12-7.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal.

T8611R1117

Trane; part no. ASYSTAT700.

T8611G2002

Wiring differences (old=new): B=C, F=L,
X2=E, W1=W2; configure O/B terminal to O
in Installer Setup 29; jumper W1 to Y1.

T8611R1125

Trol-A-Temp®

 

by Honeywell thermostat.

T8611G2051

a

Jumper Y1 to W1.

T8611R1133

TRADELINE®

 

thermostat; Honeywell

logo.

T8611G2002

Wiring differences (old=new): B=C, H=B,
X=L; configure O/B terminal in Installer
Setup 29.

T8611R1141

TRADELINE®

 

thermostat; Honeywell

logo; Premier White® color.

T8611G2002

Configure O/B terminal in Installer Setup
29; no P terminal; taupe color.

T8611R1158

TRADELINE®

 

thermostat; Honeywell

logo; Premier White® color.

T8611G2002

Wiring differences (old=new): B=C, H=B,
X=L; configure O/B terminal in Installer
Setup 29; taupe color.

T8611R1174

Phillilps Energy.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal.

T8611R1182

Armstrong; Premier White® color.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal; taupe color.

T8611R1190

Inter-City Products; Premier White® color;
part no. HQ1149375HW.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal; taupe color.

T8611R1208

Carrier Weathermaker; part no.
HH07AX114.

T8611G2002

Configure heating cycle rate in Installer
Setup no. 4, 5, 7 and O/B terminal in 29;  
no P terminal.

T8611R1216

Carrier Zone Perfect; part no.
HH07AX115.

T8611G2002

Configure heating cycle rate in Installer
Setup no. 4, 5, 7 and O/B terminal in 29;  
no P terminal.

T8611R1224

Consolidated logo; Premier White® color.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal; taupe color.

T8611R1240

Millbrook Industries logo; Premier White®
color.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal; taupe color.

CT8611R

Two-stage heat  and one-stage cool retail heat pump thermostat; powered direct from 24 Vac trans-
former; system switch—EM HEAT-HEAT-OFF-COOL; fan switch—ON-AUTO; O and B terminals

CT8611R1006

Retail Honeywell logo; clamshell
packaging; off-white color.

T8611G2002

Configure O/B terminal in Installer  
Setup 29; no P terminal; TRADELINE®
packaging; taupe color.

a Contact Trol-A-Temp® for thermostat.

Содержание T8611G Chronotherm IV Deluxe

Страница 1: ...door temperature sensor capability for homeowner convenience The sensor is also more accurate than a thermometer Configurable features allows one model to be used to replace many different models less inventory no longer need to carry separate models to get these features F or C temperature display automatic or manual changeover adjustable heating cycle rate Minimum off time protects the equipment...

Страница 2: ...Vac 50 60 Hz 20 to 30 Vac 50 60 Hz Batteries No batteries required Auxiliary Heat and Emergency Heat Indication Thermostat display indicates when Auxiliary Heat or Emergency Heat are activated Loss of Power The thermostat will maintain programmed times and temperatures for the life of the product The clock and day information is retained for a minimum of 30 minutes Light Emitting Diodes LEDs Two u...

Страница 3: ...e to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 5 ft ...

Страница 4: ... 1 5 METERS YES NO NO NO M10106 Fig 3 Mounting the wallplate 3 Remove the wallplate from the wall and drill two 3 16 inch holes in the wall if drywall as marked For firmer material such as plaster drill two 7 32 inch holes Gently tap anchors provided into the drilled holes until flush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening 5 Loosely insert th...

Страница 5: ...W1 H1 R3 Stage 1 heating relay Output 24V powered contact W2 H2 R4 W3 Y Stage 2 heating relay or auxiliary heat relay Output 24V powered contact X1 X2 X3 X4 A A1 A2 C L X Z User defined Light Emitting Diodes LEDs Annunciation Y Y1 C1 M Y Stage 1 compressor contactor Output 24V powered contact a Some OEM models label the terminal for transformer common B Table 4 Terminal Designations and Descriptio...

Страница 6: ...ptions M10405A Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE RETURN TO NORMAL OPE...

Страница 7: ...se and decrease keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 9 and 10 To advance to the next Installer Setup press the Time key To change a setting use the increase or decrease key To scroll the Installer Setup numbers backwards press the Time key To exit the Installer Setup press Run Program Fig 8 T8611...

Страница 8: ...ver Adaptive Intelligent Recovery control 13 0 Adaptive Intelligent Recovery control is activated system starts early so setpoint is reached by start of program period 1 Conventional recovery system starts recovery at programmed time Degree temperature display 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not used 15 Clock format 16 0 12 hour clock format 1 24 hour clock forma...

Страница 9: ...actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Display adjusts to 3 F lower than actual room temperature IMPO...

Страница 10: ...nd hold the increase and decrease keys at the same time until 10 appears All segments of the display are displayed for three seconds before 10 appears See Fig 11 and 12 M10316 Time Set Program System Fan Run Program Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Auto System Fan Wake Room AM DST Tue Heat Aux Ht Heat Auto System Fan Off A...

Страница 11: ...n code Example 02 software ID code 2 M4932A Key to Press Test Number Description Heating Equipment System Test Time 10 Enter heating equipment System Test 11 Stage one heat comes on The system fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 11 Stage two heat turns off 10 Stage one heat and system fan turn off Emergency Heating Equipment System Test Time 20 ...

Страница 12: ...rn until the time is blank The fan setting feature is available on select thermostat models M10229 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 M4933A 6 Press the Run Program key to exit the system test The system test times out after four minutes without any key presses Table 9 Default Time Setpoints and Fan Settings Period Start Time Heat Set...

Страница 13: ...M Tue Set Day Time M10314 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Time Heat Cool Settings Daylight Time Copy AM Tue Set Day Time NOTE If the current time is Daylight Savings Time press Daylight Time until DST is displayed M10315 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Set...

Страница 14: ... and cooling M10321 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Heat Cool Settings Daylight Time Copy Auto System Fan Wake Mon AM Cool Set Program Start Time Setting Heat Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Auto System Fan Wa...

Страница 15: ...nd temperature setting are cleared approximately 3 seconds NOTE Wake cannot be cleared M10331 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Heat Sat Leave Set Program Start Time Setting Leave 4 Repeat steps 2 and 3 for all the periods to be cleared 5 Press Run Program M10332 Time Set Program System Fan Run P...

Страница 16: ...days is displayed 1 to 256 days Example 18 Hold will override the daily programs for 18 days M10338 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Heat Wake Hold for Setting Time 3 Press Wake Leave Return or Sleep to select the period the program will start Example Return thermostat will stop the Hold at the ...

Страница 17: ... and electromechanical thermostats See Fig 13 Operation Sequence The thermostat energizes specific terminals depending what the Fan and System are set to The LCD will display the time room temperature system and fan selection Symbols will be displayed when the heating cooling or fan is energized See Table 10 for specific information NOTE Not all the thermostat models have all the terminals listed ...

Страница 18: ...rees away from the desired setpoint previous equipment performance and weather history to initiate recovery at the optimal time to achieve the comfort setting at the desired time The Chronotherm IV uses two recovery ramps one for the compressor and one for the auxiliary heat Once the room temperature intersects the compressor ramp the compressor snaps on until the setpoint is reached If the temper...

Страница 19: ...eating higher or the cooling lower The setpoint temperature range stops were configured Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops Heating will not come on No power to the thermostat Check for 24 Vac between R and C terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check i...

Страница 20: ...nimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup number 33 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool Cool setpoint is above room temperature Check cooling setpoint Set cooling setpoint to desired temperature Heating or cooling come on momentarily and shut off Heat or cool circuit is o...

Страница 21: ...figure changeover in Installer Setup 12 and O B terminal in 29 jumper Y1 to W1 taupe color T8611G1111 Trane Premier White color part no TAYSTAT501 T8611G2002 Wiring differences old new F L B C configure changeover in Installer Setup 12 and O B terminal to O in 29 taupe color T8611G1145 Canadian TRADELINE thermostat Honeywell logo Premier White color degree C T8611G2002 Configure changeover in Inst...

Страница 22: ...DELINE thermostat Honeywell logo Premier White color T8611G2002 Wiring differences old new B C H B X L configure O B terminal in Installer Setup 29 taupe color T8611R1174 Phillilps Energy T8611G2002 Configure O B terminal in Installer Setup 29 no P terminal T8611R1182 Armstrong Premier White color T8611G2002 Configure O B terminal in Installer Setup 29 no P terminal taupe color T8611R1190 Inter Ci...

Страница 23: ...ORMER HEAT RELAY 2 OT OT OUTDOOR SENSOR COOLING OR HEATING CHANGEOVER VALVE O B X2 L X1 EQUIPMENT MONITOR 2 EQUIPMENT MONITOR 1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 W2 L1 HOT L2 M10823 FAN RELAY Y1 G E THERMOSTAT C R W1 COMPRESSOR CONTACTOR EM HT RELAY TRANSFORMER HEAT RELAY 2 OT OT OUTDOOR SENSOR COOLING OR HEATING CHANGEOVER VALVE O B X2 L X1 EQUIPMENT MO...

Страница 24: ...ilding Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 Helping You Control Your World 68 0165 1 J H Rev 10 97 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 pos...

Отзывы: