
T8611G CHRONOTHERM
®
IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT
68-0165—1
19
TROUBLESHOOTING GUIDE
Refer to Table 12 for troubleshooting information.
Table 12. Troubleshooting Information.
Symptom
Possible Cause
Action
Display will not come
on.
Thermostat is not being powered.
•
Check for 24 Vac between R and C terminals.
—
If missing 24 Vac:
—
check if the circuit breaker is tripped—reset the
circuit breaker.
—
check if the system fuse is blown—replace the fuse.
—
check if the power switch on the HVAC equipment
is in the Off position—set to the On position.
—
check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
—
If 24 Vac is present, proceed with troubleshooting.
Temperature display
is incorrect.
Room temperature display has
been reconfigured.
Enter Installer Setup number 37 and reconfigure the display.
Thermostat is configured for °F or
°C display.
Enter Installer Setup number 14 and reconfigure the display.
Bad thermostat location.
Relocate the thermostat.
Temperature settings
will not change.
(Example: Cannot set
The upper or lower temperature
limits were reached.
Check the temperature setpoints:
•
Heating limits are 40 to 90°F (7 to 31°C)
•
Cooling limits are 48 to 99°F (9 to 37°C)
the heating higher or
the cooling lower.)
The setpoint temperature range
stops were configured.
Check Installer Setup numbers 34 and 35 and reconfigure the
setpoint stops.
Heating will not come
on.
No power to the thermostat.
•
Check for 24 Vac between R and C terminals.
—
If missing 24 Vac:
—
check if the circuit breaker is tripped—reset the
circuit breaker.
—
check if the system fuse is blown—replace the fuse.
—
check if the power switch on the HVAC equipment
is in the Off position—set to the On position.
—
check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
—
If 24 Vac is present, proceed with troubleshooting.
Heating will not come
on.
Thermostat minimum off time is
activated.
Wait up to five minutes for the system to respond.
System selection is not set to Heat.
Set system selection to Heat.
Heating setpoint is below room
temperature.
Check heating setpoint. Set heating setpoint to desired
temperature.
Cooling will not come
on.
No power to the thermostat.
•
Check for 24 Vac between R and C.
—
If missing 24 Vac:
—
check if the circuit breaker is tripped—reset the
circuit breaker.
—
check if the system fuse is blown—replace the fuse.
—
check if the power switch on the HVAC equipment
is in the Off position—set to the On position.
—
check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
—
If 24 Vac is present, proceed with troubleshooting.
(continued)