T7560A,B,C DIGITAL WALL MODULES 

 5 

EN0B-0237GE51 

R0208 

Set Fan Mode 

The UNIT ENABLE button switches the fan mode between 

AUTO and MANU OFF: 

 

AUTO 

(fan speed from controller) 

 

 

MANU OFF 

(fan off) 

With this setting, depending on 

configuration, the display may 

also read: 

 

 

Humidity Display 

If applicable, the humidity is indicated by the bargraph at the 

top of the LCD. Each segment of the bargraph represents 4% 

of relative humidity: 

 

NOTE:

  Humidity display is not available with fan control. 

 

Humidity mode 

(e.g. left 12 segments ON = 

50% relative humidity) 

 

 

Set Bypass/Occupancy Mode Display 

The bypass function can be used to override the control 

algorithm generated by the controller (e.g. for an event after 

normal office hours, or for a room known to be unused). 

The status of the occupancy mode can be seen from the sun, 

moon, and snowflake symbols. The following LCD behaviors 

are possible, depending on configuration. See T7560A,B,C 

Installation Instructions (product literature no.: EN1B-

0146GE51) for configuration options: 

Occupancy mode display for Excel 10 LCD signaling 
(Excel 10 set to LCD_DISPLAY; with FCU, HYD, and 
CHC, only.) 

 

Effective Occupancy or Bypass mode 

(SUN continuously ON) 

 

 

 

Effective Standby mode; generated by 

time program 

(HALF-SUN continuously ON) 

 

 

Effective Unoccupancy mode 

(MOON continuously ON) 

 

 

 

Unit Off, No Frost Protection 

(OFF without snowflake) 

 

 

 

Unit Off, With Frost Protection 

(OFF WITH SNOWFLAKE) 

 

Override Standby mode (from central) 

(HALF-SUN FLASHING) 

 

 

 

Wink mode (NEURON

©

 ID sent) 

(SUN/MOON/SNOWFL. FLASHING) 

(Only with FCU, HYD, CHC) 

 
Press the BYPASS button to set the desired mode: 

 

To activate Override Occupancy or Bypass mode, 
press and release the BYPASS button. 

 

To activate Override Unoccupancy mode, press 
and hold the BYPASS button for at least 5 sec. 

 

To return to normal mode, press and release the 
BYPASS button again. 

 

NOTE:

  Pressing the BYPASS button for more than 5 

seconds sends the NEURON

©

 ID of the connected 

Excel 10 controller via the L

ON

W

ORKS

©

 network. 

 

Override Occupancy or Bypass mode 

(SUN FLASHING) 

 

 

 

Override Unoccupancy mode 

(MOON FLASHING) 

 

 

 

Override mode display for Excel 10 LED signaling (Excel 
10 set to LED_OVERRIDE) 

 

Off Conditions, No Override, Overr. 

Occupancy, Overr. Standby (NO 

SYMBOLS) 

 

 

Wink mode (NEURON

©

 ID sent) 

(SUN/MOON/SNOWFL. FLASHING) 

(Only with FCU, HYD, CHC) 

 

Press the BYPASS button to set the desired mode: 

 

To activate Override Bypass mode, press and release 

the BYPASS button. 

 

To activate Override Unoccupancy mode, press and hold 

BYPASS button for at least 5 sec. 

 

To return to normal mode, press and release the 

BYPASS button again. 

NOTE:

  Pressing the BYPASS button for more than 5 

seconds sends the NEURON

©

 ID of the connected 

Excel 10 controller via the L

ON

W

ORKS

©

 network. 

 

Override Bypass mode 

(SUN FLASHING) 

 

 

AUTO

MANU

MANU

 

 

 

MANU

MANU

 

 

 

 

 

 

 

Содержание T7560B

Страница 1: ...hange configuration information such as the DWM s engineering units The T7560C Digital Wall Module see inset above has no user interface e g LCD buttons or setpoint dial and issues only temperature and humidity values These wall modules are not compatible with Honeywell W7751A C E G VAV1 and W7752D1 FCU1 Controllers FEATURES Fully compatible with all current Excel 10 and Excel 20 to 600 controller...

Страница 2: ...ominal re sistance Ω 15 5 0 29 31543 18 3 0 27 27511 21 1 0 27 24047 26 7 0 27 18490 29 5 0 29 16264 Humidity Sensor Table 3 Humidity sensor specifications parameter value humidity sensing range 5 95 r h output signal 0 5 10 Vdc 5 100 r h accuracy 5 full scale Fan Speed Button T7560A B only Table 4 Fan speed resistances switch position resistance Ω fan behavior auto 1681 4 100 runs as scheduled 0 ...

Страница 3: ... 3 4142 0 79 3053 0 4 3689 3 81 2509 3 5 3236 7 83 1965 6 6 2784 0 85 1421 9 7 2331 3 8 1878 7 9 1426 0 10 973 3 Field Wiring 16 to 22 AWG 1 5 to 0 34 mm2 depending on application 18 AWG 1 0 mm 2 min for 24 Vac power wiring Max length of wire from a device to a wall module is 164 ft 50 m Twisted pair wire recommended for wire runs longer than 100 ft 30 5 m Setpoint Adjustment Range A and B Setpoin...

Страница 4: ...n to decrease increase the room temperature setpoint The display toggles the setpoint value either relative or absolute as configured After the new setpoint has been set the display returns to normal mode after approx 5 sec Set Fan Speed The manually set fan speed is represented by a bargraph Depending on configuration the fan speed can be set as follows Three speed fan override AUTO OFF 1 2 3 Two...

Страница 5: ...ode MOON continuously ON Unit Off No Frost Protection OFF without snowflake Unit Off With Frost Protection OFF WITH SNOWFLAKE Override Standby mode from central HALF SUN FLASHING Wink mode NEURON ID sent SUN MOON SNOWFL FLASHING Only with FCU HYD CHC Press the BYPASS button to set the desired mode To activate Override Occupancy or Bypass mode press and release the BYPASS button To activate Overrid...

Страница 6: ...e further options depend on the configuration of the controller Occupancy mode SUN continuously ON Standby mode generated by time program HALF SUN continuously ON Unoccupancy mode MOON continuously ON To adapt the T7560 to the CARE control strategies for Excel 20 to 600 a standard ModAL software module is available Contact your local Honeywell distributor or refer to T7560A B C Installation Instru...

Отзывы: