T7560A,B,C DIGITAL WALL MODULES 

 3 

EN0B-0237GE51 

R0208 

Table 5. Setpoint values vs. resistances (Celsius) 

setpoint 

rel./K 

nom. res. 

(

 

setpoint 

abs./°C 

nom. res. 

(

-5 9574.0 

  12 9958.0 

-4 8759.2 

  13 9468.7 

-3 7944.4 

  14 8979.3 

-2 7129.6 

  15 8490.0 

-1 6314.8 

  16 8000.7 

0 5500.0 

  17 7511.3 

1 4685.2 

  18 7022.0 

2 3870.4 

  19 6532.7 

3 3055.6 

  20 6043.3 

4 2240.8 

  21 5554.0 

5 1426.0 

  22 5064.7 

  

 

23 

4575.3 

  

 

24 

4086.0 

  

 

25 

3596.7 

  

 

26 

3107.3 

  

 

27 

2618.0 

  

 

28 

2128.7 

  

 

29 

1639.3 

  

 

30 

1150.0 

 

Table 6. Setpoint values vs. resistances (Fahrenheit) 

setpoint 

rel./K 

nom. res. 

(

 

setpoint 

abs./°C 

nom. res. 

(

-10 10026.7 

  55  9577.4 

-9 9574.0 

  57 9033.7 

-8 9121.3 

  59 8490.0 

-7 8668.7 

  61 7946.3 

-6 8263.7 

  63 7402.6 

-5 7763.3 

  65 6858.9 

-4 7310.7 

  67 6315.2 

-3 6858.0 

  69 5771.5 

-2 6405.3 

  70 5499.6 

-1 5952.7 

  71 5227.8 

0 5500.0 

  73 4684.1 

1 5047.3 

  75 4140.4 

2 4594.7 

  77 3596.7 

3 4142.0 

  79 3053.0 

4 3689.3 

  81 2509.3 

5 3236.7 

  83 1965.6 

6 2784.0 

  85 1421.9 

7 2331.3 

   

 

8 1878.7 

   

 

9 1426.0 

   

 

10 973.3 

   

 

 

Field Wiring 

  16 to 22 AWG (1.5 to 0.34 mm

2

) depending on 

application. 

  18 AWG (1.0 mm

2

) min. for 24 Vac power wiring. 

  Max. length of wire from a device to a wall module is 

164 ft (50 m). 

  Twisted pair wire recommended for wire runs longer 

than 100 ft (30.5 m). 

 

Setpoint Adjustment Range (A and B) 

Setpoint can be configured for 

  Fahrenheit absolute (55 ... 85 °F) 

 Fahrenheit 

relative 

(

±

 10) 

  Celsius absolute (12 ... 30 °C) 

  Celsius relative (

±

 5) 

 

Temperature Value Display Resolution (A and B) 

Degree Celsius 

 0.1 °C 

Degree Fahrenheit 

 0.1 °F 

 

Setpoint Value Display Resolution (A and B) 

Degree Celsius 

 0.5 °C 

Degree Fahrenheit 

 1.0 °F 

 

Mounting Options 

Wall mounting 

 

Dimensions(H/W/D) 

4-1/8 x 3-15/16 x 1-3/16 in. (104 x 99 x 30 mm) 

 

Environmental Ratings 

Shipping temperature: -22 ... +140 °F (-30 ... 60 °C) 

Operating temperature: 32 ... 104 °F (0 ... +40 °C) 

Relative humidity: 5% to 95% non-condensing 

Measurement range: +6 … +40 °C 

 

Approval Bodies 

UL 916, NEC Class 2 

CE 

 

 

Содержание T7560B

Страница 1: ...hange configuration information such as the DWM s engineering units The T7560C Digital Wall Module see inset above has no user interface e g LCD buttons or setpoint dial and issues only temperature and humidity values These wall modules are not compatible with Honeywell W7751A C E G VAV1 and W7752D1 FCU1 Controllers FEATURES Fully compatible with all current Excel 10 and Excel 20 to 600 controller...

Страница 2: ...ominal re sistance Ω 15 5 0 29 31543 18 3 0 27 27511 21 1 0 27 24047 26 7 0 27 18490 29 5 0 29 16264 Humidity Sensor Table 3 Humidity sensor specifications parameter value humidity sensing range 5 95 r h output signal 0 5 10 Vdc 5 100 r h accuracy 5 full scale Fan Speed Button T7560A B only Table 4 Fan speed resistances switch position resistance Ω fan behavior auto 1681 4 100 runs as scheduled 0 ...

Страница 3: ... 3 4142 0 79 3053 0 4 3689 3 81 2509 3 5 3236 7 83 1965 6 6 2784 0 85 1421 9 7 2331 3 8 1878 7 9 1426 0 10 973 3 Field Wiring 16 to 22 AWG 1 5 to 0 34 mm2 depending on application 18 AWG 1 0 mm 2 min for 24 Vac power wiring Max length of wire from a device to a wall module is 164 ft 50 m Twisted pair wire recommended for wire runs longer than 100 ft 30 5 m Setpoint Adjustment Range A and B Setpoin...

Страница 4: ...n to decrease increase the room temperature setpoint The display toggles the setpoint value either relative or absolute as configured After the new setpoint has been set the display returns to normal mode after approx 5 sec Set Fan Speed The manually set fan speed is represented by a bargraph Depending on configuration the fan speed can be set as follows Three speed fan override AUTO OFF 1 2 3 Two...

Страница 5: ...ode MOON continuously ON Unit Off No Frost Protection OFF without snowflake Unit Off With Frost Protection OFF WITH SNOWFLAKE Override Standby mode from central HALF SUN FLASHING Wink mode NEURON ID sent SUN MOON SNOWFL FLASHING Only with FCU HYD CHC Press the BYPASS button to set the desired mode To activate Override Occupancy or Bypass mode press and release the BYPASS button To activate Overrid...

Страница 6: ...e further options depend on the configuration of the controller Occupancy mode SUN continuously ON Standby mode generated by time program HALF SUN continuously ON Unoccupancy mode MOON continuously ON To adapt the T7560 to the CARE control strategies for Excel 20 to 600 a standard ModAL software module is available Contact your local Honeywell distributor or refer to T7560A B C Installation Instru...

Отзывы: