T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS
3
EN1B-0291GE51
R1111B
Table 2. Wiring terminal references for non-Excel 10/12 devices
signal
T7460A
terminal
T7460B
terminal
T7460C
terminal
Excel 800
XF82x
terminal
(example)
Excel 500
XF52xB
terminal
(example)
Excel 500
XFL52x
terminal
(example)
Excel 100
terminal
(example)
Excel 50
terminal
(example)
Excel 20
terminal
(example)
CPO-
FB22344R
terminal
(example)
Smart I/O
XFC2 / XFC3
terminal
(example)
sensor signal
1
1
2
XF821: 1 (AI)
XF521: 1 (AI)
XFL521: 1 (AI)
1 (AI)
33 (AI)
19 (AI)
39 (AI)
11 (AI)
COM/GND
3 3 1
XF821: 11
(AI GND)
XF521: 2
(AI GND)
XFL521: 18
(AI GND)
55 (GND)
34 (AI GND) 20 (AI GND)
40 (AI GND)
10 (AI GND)
SETPT
--
2
3
XF821: 2 (AI)
XF521: 3 (AI)
XFL521: 2 (AI)
2 (AI)
35 (AI)
21 (AI)
41 (AI)
14 (AI)
BYP/FAN
(no fan)
--
--
4
XF823: 1 (DI)
XF523: 1 (DI)
XFL523: 1 (DI)
13 (DI)
23 (DI)
34 (DI)
36 (DI)
6 (DI)
BYP/RTN --
--
6
XF823: 13
(DI GND)
XF523: 14
(DI GND)
XFL523: 18
(DI GND)
56 (GND)
24 (DI GND)
18 (COM)
37 (DI GND)
5 (DI)
LED
(10Vdc/3mA
permanent)
--
--
5
XF822: 1 (AO) XF522: 1 (AO)
XFL522: 1 (AO)
37 (AO)
15 (AO)
12 (AO)
19 (AO)
32 (AO)
LED/RTN
(0Vdc = LED OFF,
10Vdc = LED ON)
--
--
7
XF822: 2 (AO) XF522: 3 (AO)
XFL522: 2 (AO)
38 (AO)
17 (AO)
13 (AO)
17 (AO)
35 (AO)
signal
T7460D
terminal
T7460D,E,F
terminal
Excel 800
XF82x terminal
(example)
Excel 500
XF52xB terminal
(example)
Excel 500
XFL52x terminal
(example)
Excel 100
terminal
(example)
Excel 50
terminal
(example)
Excel 20
terminal
(example)
CPO-FB22344R
terminal
(example)
sensor signal
2
2
XF821: 1 (AI)
XF521: 1 (AI)
XFL521: 1 (AI)
1 (AI)
33 (AI)
19 (AI)
39 (AI)
COM/GND 1
1
XF821: 11
(AI GND)
XF521: 2
(AI GND)
XFL521: 18
(AI GND)
55 (GND)
34 (AI GND)
20 (AI GND)
40 (AI GND)
SETPT
3
3
XF821: 2 (AI)
XF521: 3 (AI)
XFL521: 2 (AI)
2 (AI)
35 (AI)
21 (AI)
41 (AI)
BYP/FAN
(no fan)
4
4
XF821: 3 (AI)
XF521: 5 (AI)
XFL521: 3 (AI)
3 (AI)
37 (AI)
23 (AI)
alternatively to
SETPT
BYP/RTN 6
6
XF821: 13
(AI GND)
XF521: 6
(AI GND)
XFL521: 20
(AI GND)
56 (GND)
38 (AI GND)
24 (AI GND)
alternatively to
SETPT
LED
(10Vdc/3mA
permanent)
--
5
XF822: 1 (AO)
XF522: 1 (AO)
XFL522: 1 (AO)
37 (AO)
15 (AO)
12 (AO)
19 (AO)
LED/RTN
(0Vdc = LED OFF,
10Vdc = LED ON)
--
7
XF822: 2 (AO)
XF522: 3 (AO)
XFL522: 2 (AO)
38 (AO)
17 (AO)
13 (AO)
17 (AO)
NOTE:
In the case of Excel 10/12 wiring, please refer to the respective Excel 10/12 Installation Instructions.
Jumper Settings
See also Fig. 8. The jumpers on the PCB of the T7460C,D,E,F must be set according to the type of controller connected.
Jumper Setting 1 for W77xx
Const. Vol. Air Handling Unit
W7750A,B
(Smart) Variable Air Volume
W7751B,D,F,H
Fan Coil Unit (FCU2)
W7752D,E,F,G
Fan Coil Unit (FCU3)
W7754
Remote Input/Output Device
W7761A
Hydronic W7762A,B
Chilled Ceiling
W7763C,D,E
Excel 12
W7704xx
Jumper Setting 2 for W7753
Unit Ventilator
W7753
Jumper Setting 3 for XL500
Excel 800
XCL8010A
Excel 500
XC5010x, XC5210x
Excel 100
XL100x
Excel 50
XL50xxxx
Excel 20
XL20x
CPO-FCU CPO-FB22344R-xxx
Smart I/O