T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS 

EN1B-0291GE51 R1111B 

2-11/16 (68)

2-

3/

8 (

6

0)

4

-1

/8 (1

04)

3

-7/

16

 (86

)

4 (1

00

)

3-7/8 (97)

3-15/16 (99)

1-3/16

(30)

1-1/16

(27)

1 2 3 4 5 6 7

 

Fig. 3. T7460A,B,C,D,E,F dimensions in in. (mm) 

 

Mounting Procedure 

1.

  Disassemble the cover as is shown in Fig. 1. 

2.

  (T7460B,C,D,E,F only) Remove the setpoint dial by 

pulling it off. 

3. a)

 Mount the wall module onto the wall outlet box, 

or 

b) 

bore wall holes as is specified in Fig. 2 and mount 

the wall module with appropriate screws. 

4.

  Connect the wires to the terminal block according to the 

specifications in the “Wiring” section. 

5.

  (T7460B,C,D,E,F only) Insert the setpoint dial and turn 

it clockwise as far as possible. 

6.

  (T7460B,C,D,E,F only) Make sure that the dial's 

position is such that the 30 (Celsius absolute scale) or 

the +5 (Celsius relative scale) point to the right-hand 

side of the wall module (see Fig. 4). 

   

 

 

Fig. 4. Mounting position of setpoint dial 

7.

  (T7460B,C,D,E,F, only) If the dial does not have the 

correct position, pull the dial off again and reinsert it 

with the correct orientation. 

8.

  Remount the cover as depicted in Fig. 5 and make sure 

that the tab on the underside engages. 

 

 

Fig. 5. Mounting cover of T7460 wall modules 

 

Wiring 

Attach the wires from the device sensor terminals to the 

appropriate wall module terminals and set the jumpers 

according to the connected controller. See Fig. 6 through 

Fig. 8. 

 

IMPORTANT 

Screw type terminal blocks are designed to accept 

no more than one 16 AWG (1.5 mm

2

) conductor. 

 

Wire the terminal blocks as follows: 

 

1. 

Strip 3/16 in. (5 mm) of insulation from the conductor. 

2.

  Insert the wire in the required terminal location and 

tighten the screw to complete the termination. 

3.

  Verify jumper setting with Fig. 8 and wall module wiring 

with Fig. 6 and Fig. 7. 

 

Содержание T7460A

Страница 1: ...dules on an inside wall approximately 54 in 1 3 m from the floor or in the specified location to allow exposure to the average zone temperature NOTE Maintain a mounting clearance of approx 4 in 10 cm to the left hand side of the module in order to allow a free airflow for the temperature sensor and accessibility of the setpoint dial Do not mount the wall modules on an outside wall on a wall contai...

Страница 2: ...solute scale or the 5 Celsius relative scale point to the right hand side of the wall module see Fig 4 Fig 4 Mounting position of setpoint dial 7 T7460B C D E F only If the dial does not have the correct position pull the dial off again and reinsert it with the correct orientation 8 Remount the cover as depicted in Fig 5 and make sure that the tab on the underside engages Fig 5 Mounting cover of T...

Страница 3: ...minal example Excel 50 terminal example Excel 20 terminal example CPO FB22344R terminal example sensor signal 2 2 XF821 1 AI XF521 1 AI XFL521 1 AI 1 AI 33 AI 19 AI 39 AI COM GND 1 1 XF821 11 AI GND XF521 2 AI GND XFL521 18 AI GND 55 GND 34 AI GND 20 AI GND 40 AI GND SETPT 3 3 XF821 2 AI XF521 3 AI XFL521 2 AI 2 AI 35 AI 21 AI 41 AI BYP FAN no fan 4 4 XF821 3 AI XF521 5 AI XFL521 3 AI 3 AI 37 AI 2...

Страница 4: ...A 1 W77xx 1 W77xx B 2 W7753 2 W7753 3 XL500 3 XL500 SETPOINT NOTE Terminal 5 LED of the T7460C E F is reserved for connection to a 4 20 Vdc 3 5 mA LED input only hen using the T7460C E F wall module in conjunction with the Excel 10 UV Controller W7753 connect terminal 6 BYP RTN with the controller s bypass input W BYPASS BUTTON T7460C E F only IMPORTANT The gray shaded terminals are internally con...

Страница 5: ...d and allows easy access to LONWORKS or BACnet via the correspondingly wired wall module apply appropriate wiring guidelines for LONWORKS or BACnet networks as the case may be The T7460 LONJACK provides an additional 3 5 mm jack socket for a 3 5 mm jack plug Order quantity set with 5 pieces LonWorks connection terminals PC con nection 3 5 mm jack plug Fig 9 T7460 LONJACK Mounting Remove the setpoi...

Страница 6: ...chnologies Sàrl Rolle Z A La Pièce 16 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 7031 63701 Fax 49 7031 637493 http ecc emea honeywell com Subject to change without notice Printed in Germany EN1B 0291GE51 R1111B 95 7610 4 rev Nov 2011 Printed in Germany ...

Отзывы: