T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
39
63-2605—09
a
The Factory defaults listed here apply to all subbase models with the exceptions of the items listed in Table 21.
b
12:00 Noon is the default start point when time is unknown.
Dehumidification
Min On Time
5
X
Minimum on time used with “Dehumidify Minimum On”. Range: 5 to 15
minutes.
Dehumidification
Reset Temp
None
X
X
None: No Reset dehumidification; Enable: Dehumidification using Reset.
Dehumidification
Reset Temp Setpt
2° F
X
Amount of reset used with “Dehumidify Reset”. Range: 1 to 5° F.
Must be smaller than occupied zero energy band (ZEB) or standby ZEB.
Dehumidification
Reheat
None
X
X
None: No Reheat dehumidification; Enable: Dehumidification using Reheat.
Dehumidification
High Limit
65%
X
X
c
Dehumidification High Limit. Range: 10 to 90%.
Clock Year
1999
X
Range: 2000 to 2035.
Clock Month
12
X
1: January… 12: December.
Clock Day
Wed
X
Day of the Week: Sun, Mon, Tue, Wed, Thu, Fri, Sat
Clock Minutes
11:15 p.m.
b
X
X
12:00 a.m.: Midnight (first minute of the day); 12:00 p.m.: Noon.
Holiday Month
0
X
Unprogrammed; January…December.
Holiday Day
0
X
Unprogrammed; 1; 2…31; LASTDAYOFMONTH…LAST_SAT
Holiday Duration
0 days
X
Duration of given Holiday (in days). Range: 0 to 99 days.
Delays
On
X
X
On: Delays (on relays, sequential start, etc.) are active.
Off: Delays disabled (also called Test Mode).
System Switch
Auto
X
X
System settings: Auto; Cool; Off; Heat; Emergency Heat (valid if Heat Pump)
Fan Switch
On
X
X
Fan setting: On; Auto
Occupied Heat
Setpt Stop
55° F
X
Occupied Minimum Heat Setpoint: Lowest the programmed occupied heating
setpoint can be adjusted. Range: 40 to 90° F; Value
≤
OccHt
≤
OccCl - 2° F.
Occupied Cool
Setpt Stop
85° F
X
Occupied Maximum Cool Setpoint: Highest the programmed occupied cooling
setpoint can be adjusted. Range: 45 to 99° F. Value
≥
OccCl
≥
OccHt + 2° F.
Not Occupied Heat
Setpoint
55° F
X
X
Not Occupied heating setpoint. Range: 40 to 90° F.
UnoccHt
≤
OccHt
≤
OccCl - 2° F; UnoccHt
≤
StdByHt
≤
StdByCl - 2° F
Standby Heat
Setpoint
67° F
X
d
Standby heating setpoint. Range: 40 to 90° F.
Occupied Heat
Setpoint
70° F
X
X
Occupied heating setpoint. Range: 40 to 90° F.
Occupied Cool
Setpoint
75° F
X
X
Occupied cooling setpoint. Range: 45 to 99° F.
Standby Cool
Setpoint
78° F
X
d
Standby cooling setpoint. Range: 45 to 99° F.
Not Occupied Cool
Setpoint
85° F
X
X
Not Occupied cooling setpoint. Range: 45 to 99° F.
UnoccCl
≥
OccCl
≥
OccHt + 2° F; UnoccCl
≥
StdByCl
≥
S 2° F.
Event 1 State
Occupied
X
X
Day Schedule is a structure of 8 days of 4 events each day. Defaults listed are
for Monday through Friday. Saturday/Sunday/Holiday default to
Unprogrammed (None / 12:00 a.m.). All Events can be set for: Standby or
None.
Only Events 1 and 3 can be set for Occupied.
Only Events 2 and 4 can be set for Not Occupied.
Note: The Config ID cannot set an event to Standby, but it can change the
time.
Event 2 State
Not Occupied
X
X
Event 3 State
None
X
X
Event 4 State
None
X
X
Event 1 Time
8:00 a.m.
X
X
Scheduled time for event change.
12:00 p.m.: Noon
12:00 a.m.: Midnight
Event 2 Time
10:00 p.m.
X
X
Event 3 Time
12:00 a.m
(midnight)
X
X
Event 4 Time
X
X
Table 20. Thermostat Setup Options Through PDA. (Continued)
Configuration
Option
Factory
Default
a
PDA
Tool CnfgID
Description