T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2605—09
38
RoomTemp
Local
X
X
Room Temperature Input
Local: Use internal sensor; TR21/TR24: Use remote sensor.
TR22/TR23: Use remote sensor with setpoint adjustment capability (requires
PDA or TStatSpec software and USB-TIM/U cable).
T7771: Use remote sensor with setpoint adjustment capability (requires PDA
or TStatSpec software and USB-TIM/U cable); changes T7771 LED and
bypass button operation: LED on means either occupied or bypass, pushing
bypass can cancel bypass.
RoomRelHumidity
a
X
X
Room Relative Humidity Input.
None: No humidity sensor; Local: Use internal humidity sensor;
Remote: Use remote humidity sensor (0-10 Vdc signal).
Discharge AirTemp None
X
X
Discharge Air Temperature Input.
None: No discharge air sensor; or Remote: Remote discharge air sensor.
Outdoor AirTemp
None
X
X
Outdoor Air Temperature Input.
None: No outdoor air sensor; or Remote: Remote outdoor air sensor.
OccSensor
0
X
X
None: No occupancy sensor; or Remote: Remote occupancy sensor.
AuxDO
Time of Day
X
X
Auxiliary Contact Operation:
Time of Day, Economizer, Dehumid Hot Gas BP, or Simple Dehumid.
Auxiliary contact not available if heat pump selected with T7350A.
Key Pad (Lockout) Enable All
X
X
Keypad lockout enable/disable through special keypad sequence.
Enable All (0): No lockout.
SetPts & Ovrrd (1): Lockout all keys except: Temporary (Not) Occupied, 5, 6
and .
Info Only (2): Lockout all keys except
.
The special keypress features are never locked out.
Recovery Heat
RampMin
5° F/hr
X
Minimum heating recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Heat
RampMax
8° F/hr
X
Maximum heating recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Cool
RampMin
3° F/hr
X
Minimum cooling recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Cool
RampMax
6° F/hr
X
Maximum heating recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Heat
OAT@Min
0° F
X
Minimum heating outdoor air temperature. Range: -20 to 100° F.
Recovery Heat
OAT@Max
40° F
X
Maximum heating outdoor air temperature. Range: -20 to 100° F.
Recovery Cool
OAT@Min
90° F
X
Minimum cooling outdoor air temperature. Range: -20 to 100° F.
Recovery Cool
OAT@Max
70° F
X
Maximum cooling outdoor air temperature. Range: -20 to 100° F.
Demand Limit
Control Bump
3° F
X
Demand limit control set point bump. Range: 0 to 10° F.
Power Failure Seq
Start
0 (x10 sec)
X
X
Delays start of equipment (fan, heat, cool) after power restored to thermostat.
Range: 0 to 150 seconds (in 10-second increments).
Enable DAT High
Limit
None
X
X
None: No Discharge Air Temperature (DAT) high limit; Enable: Use DAT High
Limit.
Enable DAT Low
Limit
None
X
X
None: No Discharge Air Temperature (DAT) low limit; Enable: Use DAT Low
Limit.
High Limit DAT
Setpoint
110° F
X
Discharge Air Temperature High Limit Setpoint. Range: 65 to 140° F.
Low Limit DAT
Setpoint
45° F
X
Discharge Air Temperature Low Limit Setpoint. Range: 35 to 60° F.
Dehumidification
Min On
None
X
X
None: No Minimum On Time dehumidification;
Enable: Dehumidification using Minimum On Time.
Table 20. Thermostat Setup Options Through PDA. (Continued)
Configuration
Option
Factory
Default
a
PDA
Tool CnfgID
Description